Onsite Wastewater Treatment System Design (Septic Tank Replacement)
3-Bedroom Residence + 2-Bedroom Accessory Dwelling Unit (ADU)
310 Flying Fish Road
Garfield County, Colorado
Projoct No. C1942
Drew,
CBO lnc. completed a septlc tank replacement design for the subject residence. The 2,O-acre properly is
located outside of Carbondale, in an area where OWTSs and wells are necessary,
Legal Description: Section: 32 Township: 7 Range: 87 A TR lN LOT 19 2 ACRES
Parcel lD: 2391 -322-04-032
SITE CONDITIONS
The property is currently developed with a 3-bedroom residence and Accessory Dwelling Unit (ADU).
The residences are served by an existing OWTS. The permit (enclosed) was provided by Garfield
County Community Development Department. The subject OWTS consists of one 1O00-gallon, two-
compartment concrete septic tank followed by a soiltreatment area (STA) comprised of a 50' x 50' lined
Evaporation Transpiration (ET) bed. lndividualSewage DisposalSystem (ISDS) Permit 1383 documents
the system, The system was slzed to accommodate 3 bedrooms. The permit received finalapproval
on December 14, 1984.
An upgrade to the entire OWTS is anticipated; however, the existing septic tank has been reported to be
in poor condition and there is a desire to replace the septic tank near term, Replacement of the STA will
follow, pending completion of design documents.
The residences are served by a private well located in the west central portion of the property.
The existing STA will remain temporarily until new design documents have been completed and
construclion can be coordinated.
DESIGN SPECIFICATIONS
The existing septic tank will be abandoned by pumping the tank and removing it or crushing the top,
bottom, and sides and filling in the voidswith onsite materials, We recommend removalof the septic
tank due to the presence of high seasonal groundwater on the property.
The OWTS design is based on 3-bedrooms in the residence and 2-bedrooms ADU. An average daily
wastewater flow of 750 GPD will be used.
Page2
For the purposes of this OWTS design, Benchmark Elevation has been established as 100' as the
existing Bewer lines on the north side of the residence. An additional sewer line exits the residence near
the entry. A sewer line also exits the south side of the ADU. Elevations of the existing septic tank
inlet and outlet should be match for propertie into the existing sewer llnes and STA. CBO lnc.
should be notified of any discrepancies or problems with grade elevations of proposed components
during installation of the OWTS.
*Elevations are based upon practices. Component elevations may change
installation due to site conditions. Minimum grade refes to piping between components.
The sewer lines exiting the residence and ADU must be 4-inch diameter SDR-35 sewer lines with double-
sweep clean outs and a minimum2o/o grade to the septic tank.
A new 150O-gallon, two-compartment lnfiltrator@ poly septic tank with an Orenco@ Biotube effluent filter
on the outlet tee must be installed. Risers must bring the manhole lids to grade for access. lf more than
one riser is added to the septic tank, an extension handle must be installed on the effluent filter.
The subsurface was explored and groundwater was encountered at approximately 3-feet below grade
with mottling present at approimately 2-feet below grade. We are estimating high seasonal groundwater
at 2-feet below grade. We have included specifications for buoyancy control of the septic tank, if deemed
necessary.
Effluent will gravity flow to the existing STA. Plans to replace the STA are pending,
COMPONENT SPECIFICATIONS
The component manufacturers are typical of applications used by contractors and engineers in this area,
CBO Inc. must approve altematlve components prior to installation of the OWT$. Requests must
be submitted, ln writing, to our offlce for approval prior to installation. Component technical data
sheets are available upon request.
Construc{ion must be according to the jurisdiction's adopted On-Site Wastewater Treatment System
Regulations, the OWTS Permit, and this design.
OWTS Comnonent Minimum Elevatlon
Primary Tank lnlet lnvert Approximate horizontal distance from northern-
most sewer line exiting the residence64' lmin,2o/o
fall / min. {6" fall
Existing STA (approximate)
Recommend using a camera to verify exact
loation and elevation and/or location of the
existing sewer line between the existing septic tank
and SIA
Approximate horizontal distance 29' I min. 1o/o fall I
min. 3.625" fall
GOMPONENT MANUFACTURER MODEL NO.COMMENTS
Septic Tank lnfiltrator@ rM-1530-2CP 1500-gallon, two-
rcmpartment poly septic
lank
h,rotuDe tsfiluent Frner ()rencoB)Full slze 4" qrameler
Tank Risers and Lids Orenco@ Double-walled PVC Risers and
lids (24" diameter)
Page 3
PERMIT APPLICATION INSTRUCTIONS
An OWTS Permit Application (TANK ONLY) must be submitted to Garfield County Environmental
Health Department, https:/ftvwrv.qarfield-countv.com/r;nvironmenlal-health/fi.lesqcco/sites/16/OWT{r!
Applicatipn-Complete-Packet-Dtec.-2019.pdf. We encourage communication with Garfield County
Environmental Health to determine proper permitting protocol to implement the near-term STA
replacement.
All questions regarding permit submission can be directed to Garfield County EnvironmentalHealth
Department, 970-945-66 1 4 xB 1 50.
INSTALIATION CONTRACTOR
CBO lnc. expects that the installer be experienced and qualilied to perform the scope of work outlined in this
design. The installer must review this design thoroughly and coordinate with our ofiice in advance of
installation, Any additional conditions in this design or county permit must be completed and documented
priorto final approval of the OWTS installation. Communication between the installer and this ofiice is
expected th roughout the installation,
I NSTALLATION OBSERVATIONS
CBO lnc. must view the OWTS during construction. The OWTS observation should be performed before
backfill, afier placement of OWTS components. Septic tanks, distribution devices, pumps, _dosing
siphons, and other plumbing, as applicable, must also be observed. CBO lnc. should be notified 48 hours
in advance to observe the installation.
ln an effort to improve the accuracy of the record drawing, we rcquest that the installer provide a
sketch of the installation, including path of the sewer line8, water line installation (if applicable),
septic tank locatlon, STA location, and measur€ments from buildlng comens oranotherfixed
objects on the property. This sketch is most easily provided on Sheet \42.0 of the OWTS Design
pa-ct<et. Photogiaphs of the installation and final cover are also requested to supplement our installation
documentation.
RB/EGETATION REQUIREMENTS
An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire
disturbed area of the OWTS installation. A mixture of natiw grass seed that has good soil stabilizing
characteristics (but without taproots), provides a rnaximum transpiration rate, and competes well with
succesgional species. No trees or shrubs, or any vegetation requiring regular inigation shall be placed over
the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented
and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation
cover.
OPERATION I}IFORMATION AND MAINTENANCE
The property owner shall be responsible for the operation and maintenance of eaoh OWTS seMcing the
property. The property owner is responsible for maintaining service contracts for manufactured units,
alternating STAs, and any other components needing maintenance.
Geo-fabrics or plastics should not be used over the STA, No heavy equipment, machinery, or materials
should be placed on the backfilled STA. Machines with tracks (not wheels) should be used during
construction of the STA br better weight distribution. Livestock should not graze on the STA. Plumbing
fixtures should be checked to ensure that no additionalwater is being discharged to OWTS. For example, a
running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA.
Page 4
lf an efiluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned
annually, or as needed. lf the OWTS consists of a pressurized pump system, wo recommend the laterals be
flushed annually, or as needed.
The homeowner should pump the septic tank every two years, or as needed gauged by measurement of
solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not
be placed into the OWIS. Grease should not be placed in household drains. Loading from a water softener
should not be discharged into the OWTS. No hazardous wastes should be directed into the O\AffS.
Mechanical room drains should not discharge into the OWTS. The OWTS is engineered br domeslic waste
only.
ADDITIONAL CONSTRUCTION NOTES
lf design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of
freezing. The pump shall have an audible and visual alarm notification in the event of excessively high-
water conditions and shall be connected to a control breaker separate from the high-water alarm breaker
and from any other control system circuits. The pump system shall have a switch so the pump can be
manually operated.
Excavation equipment must not drive in the excavation of the STA due to the potentialto compact soil,
Extensions should be placed on all septic tank components to allow access to them from existing grade.
Backfill over the STA must be uniform and granularwith no material greater than minus 3-inch.
LIMITS:
The design is based on information submitted. lf soil conditions encountered are different from conditions
described in report, CBO lnc. should be notified. AIIOWTS construction must be according to the county
regulations. Requirements not specified in this report must follow applicable county regulations. The
contractor should have documented and demonstrated knowledge of the requirements and regulations of
the county in which they are working. Licensing of Systems Contractors may be required by county
regulation.
Please call with questions.
Sincerely,
CBO lnc.
('*,, [rt t)rfthu* E
Carla Ostberg, MPH, REHS
CBOlrc.
129 Cains Lare
Ca6ondale, Colorado I I 6?3
Ptme 970,3@.5259
cadao€lberg@gmal.6m
)
I
U
RESIDENCE
fr'TANK
2€EOROOM
STA
N
A
SCALE: 1 = 50=O'
SLF4tl PVC .\\
\\-\
DO NOT GI-UE
II*9ULATED
IMCER WRE FINISHEO GRAOE
4' Dlq
SEWER LNE
PROPERTY
THE LOCATION OF PROPOSED IMPROTEI,ENTS Sllowl.l ARE
NOT IHE RESULT OF A PROPERTY SIjRVEY. THE LOCATIONS
ARE APPROXIMATE. IT IS THE IIOMEOM/NERS' DUW TO
ENSURE ALt CONSTRUCTIOi.I AND n PROVEMFNT LOCATIONS
ARE ACCURATE" PROPERTY LINES AND SFTBACK DISTAI.ICES
SHO{JLD aE GONRRI\4ED PRIOR TO ExCAVATlOl.l. SCALED
FOR PRINTING ON tI' X 1T PAPER.
Z\CLEAN qIT TETAL\gr'-
0RAWII{GS rffST AE USED $.1
CONJTJNCIION WITH DESIGN
LETTER DATED 03/20,2025
Taylor Residence
310 Rying Fish Road
Garfield County, Colorado
ProjectNumber: C1942
Dale: ogm/2025
Designed by: CBO
Rs/iwed bF KC
DEwnby: DD
w1.0
sH10F2
z
cBO lnc
129 CaiN Lane
Cabondale, Colorado 81 623
Phone 970.309.5259
€da.6be1g@grnalsm
50'
I
I
f enrcx
BARN
J
fo
Taylor Residence
310 Flying Flsh Road
Garffdd County, Colorado
Proiect Numben C1942
Date: 0320/2925
Designed bit CBO
Reviewed by: KC
DrM by: DD
100'
N
LOAFING
SHED
-t
SCALE:1=20'4'
\
4' DIA SDR€s SEWER PIPE WITH CLEANOUT
MIN 2ol5 FALL TO TANK
SEPTIC TANK
TO BE ABANDONED
BM= 10O'
AOGE or coio- asGRA\€L
PARKING proryEo
DRIVEWAY
fo oi\
.\
50.o'
ROAD EASEMENT
\LtsGAL UtssLrtr [q)
3
J
6
I
Ij
I
I
SVTING SET
IREE HOUSE EXISTING STA" 50'X 50'
LINED ET BED. TO REMAINNEW 1sOS.GALLON,
SEPTTC TANK WITH EFFLUENT SCREEN
4" DIASDR-3s SEVVER LINETO STA
(MlN. 17o FALLTO STA)
PROPERTY
GOCAnON At{D ELEVATKTN SHOULD
AE VERIFICD PRIORTO
INSTALLATION OF SEPTIC TANK)
/^PROPOSED OWTS
t
\
wooD
DECX
},SEDROOM
RESIDENCE
I
I
I
t
I
t
I
z€EDROOMADU
w2.0
sH2f2
trq;/;r+
It GARFIELD COUNTY BUILDING AND SANIThTIOT{ DEFARTMENT
2014 Bhko Avrnur
Ghnwood Sprlngt, Colorudo 81601
phonr (3091945.8e4t
". ,r" ;.'i,L,.i' rr*,,
S"t.
J*
rNDrvlD/AL SEWAGE DTSPOSAL PERMTT ill 1383
{
Thic door not conctitutc
t buildint or ulc pormit,
Owner Peter H. 0buhan{ck
t-
Syrtom Location y 82 cOv r t l.otS 19 & eC t2 T7S ,nn7U, *_ ,,
Llc€nred lnil,rller 0wn e r
/t*trl.s /frdl9
May we suggest r+ #,&9A/
Date
FINAL APPROVAL OF SY$TEM:
No ryrtenr. thall ba deemed ro be in compliance wlth the Sewage Disposal Law6 until the rcaambled ryrtom ir approved prior to cover"
ing any pait.
' Conditional Conrtruction approval ir hereby granted for r -l*rO(I0-- sallon
-+J(- Septic Trnk or
--*_
Aerotcd treatment unit.
Ab$orption area {or dispersal area) computed as follows:
Perc rat6 of ono inch in*. tl//-.+ minutos requires r minimum ot . al/*-sq. ltl ot rb:orption trea pcr b6droom.
Therefore the no, of bedroomr 3 x
-e4*
n trut.t
fil<
f)lt
a2R
6'(-
OR
Other
Date lntpector
RETAIN WITH RECEIPT RECORD$ A NSTRUCTION SITE
TCONDITION$:
I ' All inrtollation mu$t comply with oll requirements of the County lndividual Sewage Dlsposrt Regulations, adopted puriuant to au.
thority grrnted in 06.44'4, CRS 1963, arnended 66.3.14. CRS 1903.
2, Thil permit ls velid only fot connection to slructuros which have lully complied.with County roning and building raquiremon6,
Connectiotr to or use with any dwelling or slructures not approved Uy ttre Buitding rnd Zoning oftlce ihalt rutomrtically be s violr.
lion of a requirement of the permit and caure for both legal action and revocation of the permit,
3. Sectlon lll, 3.24 requiree any person who constructs, alterg, or inrtallr rn indlviduol tewego diiporrl ryrtem in a mtnnor which in.
volves a knowing and msterial variation lrom the terms or specilicrtions contained in the epplication of permir commlg o Gla91 l,
Petty Offense {$500.00 fine * 6 month$ in jail or both}.
Sln_ticlTank accers for inrpection and cleaning within 12" ol ground rurflce
turlSce.
Proper materials and assembly,
Trade name ol septic tank or aereted trsalment unit.
Adequate absorption (or dispersal) area.
Adequato complinnce with pormit requiremenlr.
Adequate corntrliance with County and StEte rcgulationr/reguiremenlr,
r
"
-,'n4 i"'+/e.*)O* r"/W
1!ineh, rnnt/4 gr*-n". Ii"/*a,";Wfr_p
/
L
\
(
ADpllcantr Clr.at Copy Oap.rtln.nt: Flnk CoFv
_SUIIIERC0LATI0N JEST RESULTS; (To be completed by Reglstered Professlonal Fnglneer.)--r-.F.'MJnutes'-perinchinho1eNo.llrllnutesperfnchlnholeNo.3'i' t'linutes per lnch in hole No. 2 l'linutes per inch ln hole No,-
NameraddressandtelephoneofRPEwhomadesollabsorptlontests:
Name, address and telephone of RPE responsible for deslgn of the systen:
{ppllcant acknowledges that the completeness of the appllcatlon is condltlonal upon such
further mandatory and additlonal tests and reports as may be requlred by the local health
department to be made and furnlshed by tne applicant or by the'local health department for
purposes of the evaluation of the appilcation; and the lssuance of the pct'ml't,ls'subJect to
such terms and condltions as deemed necessary to lnsure compllance wlth rules and regulatlons
adopted under Artlcle 10, Tttle 25,- C.R.S. 1973, as amended. The undersigned hereby certifiesthat all statements made, lnformatlon and reports submltted herewlth and requlred t0 be
submltted by the appl{cant
of ny knowledge and bellefln evaluating the same for
stand that any falsiflcatl
or revocatlon of anX perml
Jury as provlded by law,
are or wlll be represented to be true and correct to the best
and are deslgned to be relied on by the local department of health
purposes of lssulng the permlt applied for hereln. I further under-
on or mlsrepresentatlon may result in the denial of the appllcatlont granted based upon sald app'lication and in lega'l actlon for per-
Date
PLEASE DRAl.l AND ACCUMTE I'IAP TO YOUR PROPERTY
Slgned
t44tu€
t t*4s ftto@e
TTzt E
ry
C t br/4tE
n
affxaaa{
y@tz^a
Page 3
INOIVIDUAL S ENAGE DISPOSAL SYSTEM APPL I CATION
Appl fcation
Approval by
County 0fflclal:I
ffi
CONTRACTOR-ALgLrrl rle f!n
ADDRESS p.o-ro" zag,ls , HQNE 9A+Ag6l_. -
lFRl,lIT REQUEST F0R: (r ) New Insrallation ( ) Alteration ( ) RepairAttach separate sheets or report shorrlng entiri area wJth respeci ti sui^round
top0grilPhy of area, hab'itable bulldingr locatlon of potable witer wellsr solltest holes, soll proflles in test holes. (See page 4.)
I ng areas ,percolatlon
LOCATION OF FACI L ITY i Cou Guftrli
Near what Clty of Tow n 0e"rboncdelr Lot Slze 2.OO Aor
Legal Descr{pt ioncovrt lotr 19 I f0. eso 1l!.T?5.n87'f of the 6th P.il. Orrftclrt Co..(hlo.
I.|.A$TES_,TW: (x ) Dwel l ins ( ) Transient Use
( ) Conmerclal or Instituttona'l ( ) Non-domestic l,lastes
( )0ther-Describe
BUILDI}IG OR SERVICE TYPE: RrrIdONtlEJ"
l{umber of bedrooms 3 Number of per$0 ns3
F ) Garbage grinder ( X ) Automatlc washer (X ) Dishwasher
SOURCE.AND TY.PE 9f HATER SUPPLYT (r ) well ( ) sprlng ( ) stream or creek
Glve depth of all wells wlth{n 180 feet of system : 6Of
If supplled by commun{ty water, glve name or suppller:_-
GROUNQ CoJ{Dtll0Nsr
Depth to bed rock: ?0 plur ftct,.
Depth to flrst Ground llater Table t 3'4'
Percent ground slope: ---46, - _ . - -- ..._ ..-. _ ..
DISTAIICE T0 NEAREST CoI,IMUNITY SEI.,ER SYSTEI1: X/A
}Jas an effort made to connect to cormunity sy stem?Itrt
TYPE OF INDIVIDUAL SE}IAGE DISPOSAL SYSTEM PROPOSED:
( x) Septlc Tank
( ) Vault Privy
( ) Pit Privy
( ) ChemJcal Toilet
FINAL DISPOSAL BY:
) Absorption Trench, Bed or Plt
) Underground Dispersal
) Above Ground Dispersal
) Aeration Plant ( ) Vault
) Composting Toilet ( ) Recycling, potable use
) lnclneratlon Toflet ( ) Recycling, other use
) Other - Describe:
( ) Evapotranspiration
( ) Sand Filter
( ) llastewater Pond
(
(
(
(
(
(
(
() Other - Describe:
I.'ILL EFFLUENT gE DISCHARGED DIRECTLY INTO WATERS OF THE STATE?
Page 2
EruorflEEfrs & corvsrf,uc7ons
tlovernber 21, 1984
l,lr. &l FeLd
Garfleld County Sanitarian
f09 8th Street
Glsnr,uood Sprirrgsr Oolorado 8f601
REt Obuhanick FII Sysbem
Ibar &lr
the purpose of this letter is to clear Ltp tr,p itenrs relative to the
above systenr deslgn. Ffu'et of all there uas a miscalculatlon in theEize of the Ef, Bed. rtre orrect size ts 2s0CI ft.2 calculated asfolLopsl
(1)
FIop = 450 gfd x .75 = 33?.5 gfi<l(f) 25t kductlon for lor* vater r.Be flxtures
Area = 33?.5 x 237 = 2500 ft.2
32
The slze of tJte E'f Bed may thus be rcduc.ed to 50f x 50,.
lhe seoSd iteq perbatns to peak fror,rs. tile did lpt use the 1..5 peakingfactor that oode requlres for leachfields in qr gr Bsd clesiqn* orrrationale ie that "Deakinq factors" do not apply to EIf ned clesign
becauEe a short term lntermittant peak flow wlll nct have an aeverseeffect on an ET Bed. r?re basis of ET Bed design ie average daily flow.
Flords st(aeeding av€rage daily florr are offset by flcns leis tho lveragedaily flow. Ttris is not tfie case wlth leachflelds nhlch must be
designed to leach tl.e peak florrE elnce ttrey do nct have the storagecapabiltty to average cut hlgh and lovr flow o\rer a long tine peridd.
If you have any questlons please feel freE to mntact ne.
Sincerely,
SCTIMUESER & ASSOCIATES
*
7,rJ- rfl";/,1*/t,t.
0
Rlck Klnshella, P.E.
r{i/JJ
,q
NOVP 8 IgB4
G4n,,
'rrJtli
SCHi'|UE9ER & ASSOCIATES, lt{C.
1512 GRANO AVENUE, SUITE 210 r GLENWOOD SPR|NOg, COLORADO 81001 r (30gls4$.946E
EO [:.:;::,1,i"?i*:.,Map Viewer
I Well Gonstructed
E Ground Water
I counry
Legend
!: I
llLocation
lli
Notes
292 0 146 292 Feet._
1t 1,7U
Thk ptdud ls fq tnfqnfy'.lopl pwposs tl1d nay nd havo b&n pteparcd lq, ot ba ilntue lq l@al,
c|inadng, q ilNaylv putpo$s. lJs# d lhls lnlomtllon drculd Evlow ot @Nilt tlf pdnary dela ad
hlom.lion $owcs to .san.ln ttp us.bilty ol tha Inbnatlgn.
D6t€ Pr€Paredr 31412025 8:04:10 AM0
Legend
? sto Flying Fish Rd
310 Flying Fish Road
G)qPuhlic.net'"' Garfi eld County, Co
Overview
tl
310 FLYING FISH RD
CARBONDALE
TAYLOR, DREWMICHAF.L&
NATALIAC
310 FLYING FISH ROAD
CARBONDALE CO81623
Total Actual
Value
Legend
f, Parcels
Roads
Parcel/Account
Numbers
OwnerName' j Lakes&Rlvers
- CountyBoundary
Llne
$109,340 last2Sales
Date Prlce
6/4/2024 $95o,ooo
6/4/2024 $950,000
Account
Number
Parcel
Number
Acres
Land SqFt
TaxArea
Mlll Levy
R111409
239732200032
2
o
011
74.4740
SCHNEI DER9rogrATral
Physical
Address
Owner
Address
81623
Date crealed:3/9/2O25
L.st Deta Uploaded:3/712025 10:43:21 PM
Develooed bv8
3/9/25,1:51 PM
Garfield County, CO
Summary
Aacount
P.rsd
Prcpc*yAddrac
bgrlDocrlpdon
Actrat ndsqFt
TIxAru.
Mllllart
SubdMrlon
qPubllc.net - Gadleld County, CO - Propcrty Rccord Card: R'111409
R1t1409
2g9tsat&$z
310 FLYING FISH RD, CARBONDALE, CO 81623
Scdlonr 32Torrrnshlp:7 Rrnge:87ATR lN LOf 19 2ACRES
2
0
L7
74.4740
Map
VlewMap
Owner
TAYIOR" DREW MICHAEL & NATALIA C
3lOFLYING FISH ROAD
CARBONDALE CO 81623
Land
Unltllrp. SINGLE FAM,RES,-LAND - 1112 {RESIDENTIAL PROPERTVI
SqurrcFr3t O
Buildings
BulHlnrt
Unltr
BulHlqrlpo
AbatrrtCodcc / (Propcfi npcl
Arttrltccturd Style
Storl€s
frem
AchlrlYc|r Bullt
GrocrUvlniArur
Tot.lHG.t dSqFt
Bcdruomtgrtir
HertlnSFud
HcrtlnilYpc
AhCondftlonln3
Rooflypa
RoofCow
1
t
SFR
STNGLE FeM,RES-TMPROVEMTS-1212 (RESIDENTIAL PROpERTY)
l.STORYI
WOODFRAME
tgs4
7,632
7,632
3
t
GAS
FORCEDAIR
NONE
RIDGE FRME
PREFAB MET
https://qpubllc.schnoldsrcorp.com/Appllcatlon.aspx?ApplD=1038&LayerlD=22381&PageTypelDa4&PagelD=9447&Q=40355943&KeyValue=R111409 114
3/9/25, 1:51 PM qPubllc.net - Garllcld County, CO - Property Rccord Card: R'1'11409
Bulldln5*
Unlb
Bu[dlnSTvpa
Abstnct Cod!r / (Propcrty
ArdrhictunlSVr
Stod.B
Framg
ActrlYG.rBullt
GrooUvln6Arcr
Totel lhrtd 9qFt
Bcdroorrc
Brths
HcrtlnS Fud
hrtlnsTYpc
ArCondltlonlnr
RoofTlp:
Roof Cowr
lyp6l
2
7
5FR
SINGLE FAM,RES. IMPROVEMTS.T2l2 (RESIDENTIAL PROPERTY)
l.STORY
2
WOOD FRAME
1990
768
768
1
0
GAS
HOTWATER
NONE
RIDGE FRME
PREFAB MET
1gt,'g
Tax History
Trx Ycrr 2gin
Taxcs Billed $7,732.36
Click here to vir:wthe tax lnformation for this pj,!ql@1rveb5ite,
Transfers
Sele Detc DaGd lVpc
$253s36 $4,911.r6
R.crptlon lftrnbcr Book. P.s_Pw
119,109?twztw
2022 2U2L
$497484
5t4t2U21
5/4/2024
. BfRgArN 4l.lD SAL-E qEED
SPECIALWARRANTY DEED
PERSONAL REP DEED
6t3t2024 STATEMENTOFAI'THORITY
6t3t2C24 PERSONALREP DEED ?esz,gi
9291e!
996703
$esqm
5t27t20?1
5t70t2021
LETTENS $o
DEATH CERTIFICATE
!4l20LA SPECIALWARRANWDEED tE_19:
.51]{!ry1?WTI.IDRAWALOF NONCE 818690
pt?1997ALA20LI
7t16tw1 POWEROFA1TORNEY W. 16-07:68
331154 0605{287712717982 WARMNTYDEED
Property Related Public Documents
Click h€re to virw Pro@y Related-&b!!.S-PgEumg.LEE
Photos
$40,000
Sketches
$0,
$o
$0
https://qpublic.schneld€roorp.com/Appllcatlon.aspx?ApplD=1038&LayerlD=22381&PageTypelDo4&PagElD=9t147&Q=40355943&KeyValuesR111409 214
U9/25, 1161 PM qPubllc.nct - Garllcld County, @ - Propcrty Rroord Ced: R1114OS
b
&,r,
zu
FCP
240 sf
(l|l
7',
CAN
r6t st
nN
z4'
EARN fu
768 st i';
r*
FOP
1sg sf
z4'
ooG
768 sfolft
0
WBA
72 sl
ii
- oPENIJAR?HFrN
2[',
https//qpubllc.sahnaldsrclrp.com/Appllaatlon.aspx?ApplD=1038&LaprlD-22381&PageTypelDa4&PagelD=9447&O=40395043&Key\rbluc=R11'1409 Sl4
UOl25, 1:5'l PM qPubllc.nct - Garflcld County, CO - Pmp.ily Rccord Cedl R111409
'fhr 6rr irrrld r'"i;i!rfv A'iis!irir':t C)fur;e irrll r:; *vtry €t'fqirl l$ ttrr.itltJc* th{t ltltri : liti;ur:;te
irrf+rni;rai,ln I:*slil:lu. i'l(l !vi:rr;]ntic:$, exprr: lsccl r:r itflplit:d ar* prcvidt:d fr:l ti.: rj;rta itcrcin, it:;
r.):rf 0f ir i.j rp rcf iliarr, Li;l ta i.l :u biqct tr: *:nr ,:;lan i rh.l[g* I rrl its :ti:ctlt"l: ly nr]cl ,:ilr"rrDlt t$nir:i $
cafl fiot :re gunfrtitced,
i U$r'}riyacylglisY I GDPR Prlvacv Notlgg
Last Dats..Up!9edi!U&0?5.r9;Si?!PM
Crtrtlr:i L|i ilcvr'irrp,:,J l.,Vp scx"t1gtg55
Item #
IM.{53O.2GP
{53O Gallon TWo Gompartment
lnfiltrator@ Poly Tank
61
TA},IKTOP
HAIf
CONTINUOT'8
El.AllTOlvlEIR|C
175.e TANK
,N?ER/OR SEAMCLIP
(80)TOP VIEW
AUONTCNT
DCnEr(ar)TAIKBOTTOilI
l{Arf
2.1'ACCESSPclRT
wTH IOCKNo UD(3)
IHHIfiE
@ ulD+lercur gEAr, gEctor{ DErAL
OIJTLETTEE
'tI)T Lv(L TOT^LVOL
grDE vrEw
EEAMCIJP
r Compliont with CSA ond IAPMO Stondordso PVC risers ovoilobler Secondory sofety screen ovoiloble wlth
PVC rlserr Moximum buriol depth is 48"
o Mlnumum burlol depth ls 6"r Tonk is not roted for vehiculor troffic
loodlngr Exterior of monhole covor includes the
following worning: "DANGER DO NOT
ENTER: POISON GASES"
UF'flI{OSTNAP
oYHerQ
END VIEW
ffir,n*1,,gn.
rnnnlG
Dlgging Specs
f
16' Long x 7' wde
43" below lnlet l
lnvert
lnlet Outlet
47" , 44"
:
Dimenelons Net
Weight
501 lbs.
Net Working Copoclt v
Totol
I
509 9ol
1st Comp. Znd Comp.
Length
175.6"
Width Height
61.7" 54.5"1006 gol 503 gol
o
o
aror.
o
o
r-Or)
iiiltilll
II
Il
lil
IIll
II
II
l{
!iitiii!
llll lItIIlrlltIillili
IIII ITI
ilrlllrli
I
^r:;Ziiiril(
l{
F-A
ir,
'f
SLOTFBEREIES
gUPPORT
mbr&
Werlmffir
r Syfisms
r Productr
tt{sl tot6Tot ffrFco ru'317
P.O.Bqsl5
Fu: f/l9')lrrigtin Bsn\frla co8l2f I
tUrbrlb: www.vdlqpmcd.omEmll:ffonUc@ffi'Irc.r$erylca
Residential Biotube' Eflluent Filters
Applications
Our patented* 4-in. (100-mm) Biotube Effluent Filters, Biorube Jr., Bionrbe
Insert Filters, and Bionrbe Base Inlet Filrers are ided for residential sepric
tanks and have a lifetime warrantF. They prevent large solids from leaving
the tank, dramatically irnproving wastewater quality and extending the lifb
of resider, tiai drainfi elds.
4-in. (100-nm) Biotube Elfluent Fiher 1
4-in. (1 0}-rnnl Biotube Jr.
(4-in, Biotube cara'idge auail-
able separately as Insert Fihei
8-in. (200-wn)
Bae Inlet liiher
4-in, (11}-mnil
Insert Filter
?e
fl
Orenco's superior effIuentfhers ruist cloging bener than all other bmnds' Our st,tn'
dard, fall-sized 4-in. (100-wn) Biotube Efihrcnt Filter prouirles n'ta,rinzunt long-term
protection in a complete pachage, with housing. Aur 4-in. (100-rnm.) BiotabeJr,, at
half the siae of our standard rnodcl, has nzow fheing capacity than the fill-sized f ber
sold by other ntanufncturer.;. For tanhs with existing outlet tees, the Biotube lrcert Fiber
is ideal. Andfor low-profile tanks, theris the Base Inlet Filter.
' Corcred by patent nurnbers 5,492,635 ud 4,439,323
To Order
Call your nearest Orenco Systemso, Inc. distributor. For neares! distribrr-
tor, call Orenco at 800-348-9843 or go to www.orenco.con and click on
"Disrributor Loca[or."
APS.FT-I
Rev. 3.4 O 11/10
0lenco Sydoms@, lnc.
Standard Features & Benefits
Has 5-10 times
more flow area
than other brands,
so lasts many
times longer
between clean-
ings, increasing
homeowner
satisfaction
lnstalls in min-
utes inside new
or existing tanks;
extendible tee
handle for easy
removal
0ptional
Features &
Benefits
. Alarm available,to
signal the need for
cleani ng
. Flow modulating
discharge orifices
available to limit
flow rate leaving
tank, mitigat-
ing surges and
in cre asing
retention time
. Custom and
commercial sizes
available
Easy to clean by
simply hosing off
whenever the tank
needs pumping
Removes about
two-thirds of sus-
pended solids, on
average, extending
drainfield life
Corrosion-proof
construction, to
ensure long life
Lifetime warranty
a
t
t
t
Biotube
Filtering
Process
Effluent from the
relatively clear zone
of the soptic tank,
between the scum
and sludge layers,
horizontally enters
the Bi0tube Effluent
Filter, Hffluent then
enters the annular
space between the
housing and ths
Biotubes, utilizing
the Biotubes'entire
surface for filtering.
Particles larger than
the Biotube's mesh
are prevented from
leaving the tank.
Orenco Systems
I i tt.:C,r l-i,-lr 'i{r-'r-i
t.' I u 4gi t t,u r lr lr,:ir 1' t lr
\\',b r ll I )o r t \\' h t t r' u,, t t r r
T..*.2fr.rG
Nomenclatures
4-in. Biotube Fifter (standardl
FT 04
4-in. Biotube
Effluent Filter
Distributed By:
Extendible PVC handle
Stainless stesl set screws
Top seal plate
Air
Biotube@ filter cartridge
Solid base
Filter housing
&in. Biotube Jr.
Tank wall
Fllter diamster (inch6s)
W = fib Type 3034 outlet pipe
S =flts Schedule 40 outlet oipe
options:
Blank = no ootionsM = flow modulatlon plate installedA = float braclct attached
cartrldge neightr 28" and 36" are standard
Houslng height: 36" and 44, are standard
0ctions:A = float bracket
FS = 2" oiltlet orific8
FSO = 2" outletorificeandoverflowplate-
Base inlet mcdel
Cartridgs heighti 1 4" standard
Housing height: 22" siandard
Filter diameter (inches)
08=8"
f-in. Biotube Filter (base inlet modell
a822-14 B
Blank = 1/S"liltrationP = 1/16" filtration
Biotobe etlluent filter series
Blank = 1/8" filtrationP = 1/16" filtration
Biotube effluent filter serles
Riser
wall
'Also avallable with coupling and sleeve as a "kit"; Fr-0VERFL0V/K[
4-in. BiOtub0 Jf. (includes cartridge and housing)
FTJ 04 t8
0ptions:
Blank = no optionsM = flow modulation plate installedA = float bracket at[acned
Cartrld0e height (lnches)
Filter diameter (incl'es)
W = fits Type 3034 outlet tee
S = fits Scheclule 40 outlst tee
Blank = 1/S" filtrationP = 116'liltration
Junior series
Biohrb€ offluent filtor ssrios
4-in. Biotube Filter lnsert(cartriuse onty)
FTi 04 18
For customizBd options
lndicates North Carolina
(e.g., NC
reglons)
W = fitsTy0s 3034 outht tee
S = fits Schedule 40 outletts|!
Cartridge hehht (inches)
Filter diametsr (lnches)
Blank = 1/S" filtrationP = 1/16" filtration
lnsert
Biotube effluent filter series
Double Walled PVC Riser & Lid Options
Poly Lid
(Shtlc load befietl b 5(XXl bs). Skld lulsten€ rurfeo. Avallable ln grcen. Hlgheet level of W Plobcton lnduded. lndudes a bam gaskstbralrtghtand
wabrtght applicatons. lndudea squaro drlve scilonls b diecourrye
unauthorlzcd enfy. lnsulatlon panele edilevc FlOlnaulaton natng
2'ol
Stended
Orenm o DunaFibern Amss Lids (FLD)
Not rcoommended for vehlcular fiafllc
24'and 30" Dlanffins. Sdld, rceln{nllreed fibaglm onafiuc{on. z0,(XIHb bmakirg silcngtt. Sbndad gmen on brorvn colorgI Avallable wlth orwltlpnt urcftano lld gasket. Avallable wlth carbon frlffion| 4 sfielnless steC {laffied sodct cap sctrrut & hex
keywnrndt. lnsulaied lidr available-t s4i
Double Walled PVC Riser
o Avallable \n24" and 30" Dlamffiro Cut b lcngillI Sdd in +l-2'incromenb. Muet be cut bstwson rlbo
VALLEYm,
mbr&
m$ryvilr
r Syaterm
r Pmducta
IEG. r Sendce
(z{$}805€?oa firFoom'3|z
P"O.Bum5
Fu: fi19) go5'$rzr B^ffi\& CO81211
Wobrlbr www.wlleypmmt@mEmll:fronil@
lnfiltrator lM-Series Tank
Buoyancy Gontrol Guidance t(F",,,,J;:':"
Belore you Begin
Thls document presents a msthod for assosslng buoyancy control
needs for lnflltrator Water Technologles (lnflltrator) lM-56rl6s
tank$. Tenk buoyancy control measures must be lmplemontod
eccordlng to state 6nd/or local r€gulatlons and approvals, whlch
may supersede these guldollnes. lf unsure ol the requlremonts for
a partlcular slte, cont€ct the local hoalth department or permlttlng
authorlty.
ll tenk buoyancy control meesur€s are lmplemented, refer to
lnfiltretor lM-Serles Tank lnstallatlon lnstructlons and Rlser
Connectlon Guldance docum6nts, as eppllcable, for completlng the
lnstallatlon,
How to Use this Document
1 , Using Step 1, Table 1 , and Figures 1 and 2, verify that the level of
unintorrupted satural€d soil is b€low the height of the outlel pip€
saddle and determine if buoyancy control is requirsd,
2. Us€ the appropriate row in St€p 2, Table 2 to dotermine the minimum
buoyancy control m€thods for th€ sit6 condltions,
3, Once the prelerred buoyancy control method is s€l6cted, follow the
impl€mentation procedures provided in Step 3,
Step 1 - Determine Need for Buoyancy Control
Required information: (1) maxlmum height ol uninterrupt€d saturat€d soil
above the tank bottom; and (2) th6 depth of soil cover above the tank top.
Tank buoyancy control may be required if:
. the level of unint€rrupted saturated soil outside the tank has the
potential to ris€ 30 inches (750 mm) or more abov6 the bottom of the
tank; and
. less than 12 inches (300 mm) of soil cover is to be placed as backfill
ov6r th€ tank top,
NO BUOYANCY CONTROL IS REQUIRED !F TTIERE ARE AT LEAST
12 |NCHES (300 MM) OF SO|L COVER ABOVE THE TANK TOP.
D6pth of Soil CoverAbove Tank Top
6' (150 mm) min - 48" (1,200 mm) max.
Top
13" (330 mm)
Outlet Pipe
Saddle:
Table 1 lnstructlons
1 . ln the left-hand column of Table 1, locat€ the row conesponding to th€
height of the uninterrupted saturat€d soil elevation outside the tank and
abov€ the tank bottom (Parameter l) tor th€ site condilions, See Figure 2
2, Follow that row to the right until reaching the column corresponding to
th6 depth ot soil cover abov€ th€ tank top (Param€ter ll), S€e Figure 2,
3. lf th€ tank mod6l is listed in thal c€ll, th€n buoyancy control is required
(proceed to Step 2). lf th€ tank mod€l is not listed in that c6ll, th6n no
buoyancy control is required.
4, lM-Series tanks shall not be installed wh€re lhe uninl€rrupted saturated
soil l€vel outsid€ th€ tank exceeds the height ol th6 outl€t pip€ saddlo.
Table 1:
lntiltrator Tank Models' and Condltions Requiring Buoyancy Control
Parem6lcr l:
Posilion of uninl€rruplod salurated
soil oonditiona above tank boltom
Param€ler 1l:
Soil covsr depth abov€ lank top'
A B
I in (t50 mm) to
12 in (300 mm)
Above 12 in
(300 mml
1
AboY6 oullei pipo saddl€'
(grcaler lhan 43" 11,075 mmll Do not install tank Do not install tank
2 30" (900 mm) to 48" (1,075 mm)
(to outlal pipe saddle)All mod6ls Noi Raquirod
s 30" (750 mm) to 36" (900 mml lM-1530 Not R6quired
4 L6ss lhan 30" {750 mm)Not Requl16d Not R6qulr€d
NOTES:
1. lntlltrator tank models lnclude: lM-540, lM-1060, and lM-1530.
2. Mlnlmum 6 lnches (150 mm) soll cov€r backfill is requir€d.
3. lM-Series tanks shall not b6 lnstsllgd wh€re th€ unlnt€rrupt€d saturat€d soll
outslds ths tank €xce€ds tho h€lght of the outl€t pipg saddle. See Figure 1.
For lndlana lnstallatlons, lf the depth of unlnterrupt€d saturated soll condltlons
cannot b6 datermlned from the slte soll ovaluation r€port or other slte-relatod
data and oth6r lnformatlon lndlcat€s the posslble presence of a p€rched ground
water table, no buoyancy controls are required.
Parameter ll
Depth OfSoil Cover
Above Tank Top
Par6meter I
Positlon of
Unlnlorruptod
Soll Conditlons
Above Tank
Uni nt€rupted Saturated
Soil Condltions 43.
(1,075 mm) max.
Above Tank Bottom
mum
Allowable
Subsurface
Unlnt€,rupted
Saturated
Soil Elevatlon
Tank Bottonr
Figure 1
Linritations When Saturated Soil Conditions are Present Above Tank Bottom
Figure 2:
B.royancy Control Paranleters lor Table 1
o lllt'
T I iil
Contact lnllltretor Wat€r Technologies'Technlc,al Son lces D€partment for asslstance at 1-800-221-4436,
Step 2 - Determine Buoyancy Control Method
Step 2 is us€d it the Step 1 analysis shows that buoyancy control is requir€d lor lh€ tank modBl and installation conditions. Th€ sit€-sp€cific maximum
height of unint€rrupted saturat€d soil outsldo of the tank and above th€ tank bottom and th€ d€plh of soil cover abov6 th€ tank top must b€ known to
complet€ St€p 2.
Table 2 lnsiluctions
For the appropriate tank mod€|, select the dosired buoyancy control method under €ach method descriptlon column. Refer to Step 3 - lmpl€mentation and
Compatible Devices and Products sections ol this document for additional information on the buoyancy control methods shown in Table 2.
Tabls 2: Buoyancy Gonlrol Melhod S€lsction
NOTES:
1. See Supplem€ntal Downward Forc€ dlscusslon bolow.
2. lM-Serles outlet plpe saddl€ helght is 43 lnches (1,075 mm) abov€:ank bottom (see Flguro 1).
Supplemental Downward Force
The minimum suppl€m€ntal downward foroe required is included in Table 2 to allow custom buoyancy control methods. These values includ€ a factor of
safely of 1,5 appli€d to the calculated downward lorce requlred to restrain th€ tank, Custom-designed buoyancy control m€thods shall conservatlv€ly
consid€r saturated soil condltions trom the bottom-of-tank el€vation to grouncl surfac€. As long as buoyancy control is provid€d that supplies the minimum
downward force list€d in the table (for poured-concr€te blocks or other methods d€signed by third parties), the tanks ar€ calculatod to be stable for the
uninterruplod saturated soil level outside the tank and above the tank bottom and corresponding soil cover conditions. All lnfiltrator strapping and faetening
recommendations apply for custom-dosigned buoyancy control methods. Contact lnfiltrator's Technical Services Dopartment with any questions regarding
supplem6ntal downward force requlrements,
Step 3 - lmplementation
Efiective buoyancy control ol lnfiltrator tanks requires oarelul preparation,
thorough excavation, pr€cis€ placement, s€cur€ strapping and proper
backfilling, as described and illustrat€d below.
Flguro 3: Plan Vlow
I
I
I
Excavation Requirements
It is recommend€d that th€ excavation width provide a minimum of 36
inches (900 mm) clearance beyond iho tank on all sides when utillzing
buoyancy control, This will allow sutficient space within the excavation to
place anchoring equipment and lasten strapping, The excavation should
provide a minimum 48-inch (1,200 mm) clearance boyond the tank when
using ChancerM No-Wrench Screw Anchors to allow for room to properly
install th€ scr€w anchors, Tha aclual excavation size shall be determined
by the installer. Refer to lnfiltrator lM-Series Tank lnstallation lnstructions
for additional excavation procedures.
Concrets-lilled Half Pipe Gonstruction
Concrete-filled half pipe shall be supported with soil or otlrer stabilizing
means b€low the pipe haunches prior to concrete placemBnt. Th€
stabilization shall prevent the pipe trom rolling during placement and curing
of the concreto, Concrete shall be allowed to cure for a minimum of one
day prior to tank backlilling.
Placement of Deadmen and Anchors
Concrete deadman anchors ar6 to b6 install€d at th€ bottom of lhe tank
oxcavalion, parallel to the long axis of the tank (se€ Flgure 3),
6'MIN EXTENSION 6" MIN EXTENSION
The deadmen should be placed close to, but not touching, th€ tank on
both sides of the tank to allow the placement of backlill between lhe
deadman anchor and lank sld€wall (see Figure 4).
Flguro 4i Soction Vlsw
(TYPTCAL)
DE,ADMAN ANCHOR
DEADMAN ANCHOR
(rYPrcAL)
Tank
Model
Paramgtor l:
Poaition of uointcrrupted
s.turrtod eoil oonditlon! 6bove
tenk bottom
Parametcr ll:
soil covor dopth sbovs
trnk top
Minimum
tupplemental
downward
torce roqulrod'
(total, both tank
sidssl
Buoyanoy Control Methodt
Conorste.lilled
half pipa
(min. length/
ald.l
Conoreto
parking
bumpero
{min,length/
sidsl
Goncteta
traftic
bafflatB
(min, length/
iide,
Holioal
rnchoil
(mln,
no./sldol
concrgts collat
(mln, width r min.
height)
tM-540 36 in (900 mrn) to outlet pipe saddle"6 in (150 mm)to 12 in (300 mm)2,200 lbs (1,000 kg)0.8 ft (1.2 m)3.8 {t (1.2 m}3.8 tt (1.2 m)
0 in (150 mm)
x I in (225 mm)
rMt060 30 in (900 mmlto outl6t pipe saddle'6 in {150 mm)to 12 ln (300 mmi 2,700 lbE (1,225 k9)4,2 ft {1.3 m}4.5 ft (1.4 m)4.2 ft (1,3 m)2
12 in {300 mm)
x I in (225 mnD
tM-1530 30 in (750 nm) to outlot pipe saddlo'6 in (150 mmlto l2 ln (300 mmi 4,300 lbs (1,s55 kg)6,3 ft (2.0 m)8.5 ft (2,0 m)6.3 ft (2.0 m)2
12 in (300 mrn)
x I in (225 mm)
Contact lnfiltrator Water Technologles'Technical Servlces Department for asslstanco at 1-800-221-4436.
Step 3 - lmplementation continued
Helical anchors should be install€d so that the eye loop is level with the
bottom of the tank €xcavation. They must be in line with th6 tank model
strapping locaiions (see Figure 5) or lifting lugs, as appropriate. Anchors
must also be installed at such a dislance from and angl€ to the tank so that
the strapping is within 5" of allgnment with the anchor shatt per lhe anchor
manufacturer's recommendations,
Flgure 5: Strap Positlonlng
lM-540
tM-1530
lM-1080
(1.600 mm)
Concrete Collar
Backfill the tank to the mid-Boam aroa, Concrete (minimum 3,000 psi at
28 days and minimum 6% air entrainmenD shall b€ cast in contact with
the ext€rior surface ot the tank to allow interlock with sidewall ribs and the
mld-height flange. The bottom of the concrete collar shall be ca$t at the
top of the mid-seam flange.
SECTION VIEW
Parts and Supplies
Th€ parts and supplies nocsssary aro to b€ purchased separately from the
tank. All parts and supplies ar€ eith€r comm€rcially available or available
through ln{lltrator's network of tank distributors. Some parts may require
fabrication on sit€ using common construction practic€s,
General Specilications
Compatible Devices and Produots
lnfiltrEtor tqnks are compatible with the following products for buoyancy
control:
. Tie-down straps: high-tensile-strength, 10,000 lb (4,500 kg) minimum
capacity, nylon or polyester, with corrosion-r€sistant hardware,
. Concreto deadmen anchors: concrete-filled plastic half pipe, precast
parking bumper, precast lratfic banier, or precast block.
. Helical anchorsl ChanceTM No-Wrench Scrow Anchors wlth minimum
6-inch ('150 mm) diameter, Class 7 or equal,
. Mid-Seam Concrete Collar: cast-in-place concrete (minimum 3,000 psi
compressive strength at 28 days and minimum 6% air entrainment),
Tie-Down Straps
Straps ar€ commercially
available in varying
lengths and wlth
assort€d hardware
and tight€ning options,
Nylon or polyester strapping with minimum 8,000 lb (3,650 kg) capacity i$
required for buoyancy control use wilh lnfiltrator tanks, Place straps over
the tank at specified locations only (see Figure 5). (Tighten strap$ snugly
with a ratchet or turnbuckle syst€m to remove all slack and slighily pre-
Iosd the syst6m). All connections, flttings, and hardwaro must be corrosion
resistant or coated with epoxy or other corrosion-reslstant materials to
inhibit deterioration in the subsurlace environment. Consider encapsulating
such compon€nts in heat-shrink tubing or applying a conosion-resistant
coating prior to burial,
CONCRETE COLLAR
Strapping
Proper installation ot straps over th6 tank is critical tor tank stability und€r
changing conditions both inside and outside the tank. Straps must be
placed at the specified strapping locations for each model, as illustrated
in Figure 5, Strapping locations are embossed on the exterior surlace
of th€ rank with the tollowing text: "SHIPPING/ANTI-BUOYANOY STRAP
HEBE." The lM-Series tank strapping locations corr€spond to structurally
reinforcod ar€as of the tank body. Straps must never be placed over
access op€nings, lids, or inlet/outl€t piping. (Straps must be tight€n€d with
a ratch€t or turnbuckle system to r€move slack and slightly pre-load the
system),
Sirapplng l{otes:
1. The buoyancy control shall be centered across the straps (excludes helical
anchors). The control shall extend a mlnlmum of 6 inches (150 mm) beyond the
maximum strap wldth (see Flgur€s 3 and 5).
2. The minimum d€adman length cotresponds to the tank model-specific strap
wldth plu$ 12 inches (300 mm).
Concrete Deadmen Anchors
Recommended concrete doadmen anchors include fille<J plastic half pipe,
precast parklng bumpers and traflic barriers, and precast blocks. Tho
w€ight of the d€admen anchors combined with th€ weight of soll above
th€m provides buoyancy control wh€n prop€rly s€cur€d, Deadmen anchors
are placed at tho bottom ot the tank excavation on opposite sides ot the
tank, The deadmen anchors are fastaned to each other with tie-down
straps plac€,d over the tank at the locations specified for each tank model
(s€e Figure 5),
'15 in [375 mm] to
18 in [450 mm]
Steel Rebar
Concrete Parking Bumper
Use commercially available steel-reinforced
parking bumpers wilh typical dimensions of 12
inches wide by 6 inches high (300 rnm x 150
mm). W€ight is 58 lbs/foot (86 kglm) minimum.
Concrete-tillad Plastic Hall Pipe
Us€ Sch€dule 40 PVC plastic pip6 with a
minimum inside diameter ol 15 inch€s (375
mm) or HDPE corrugated pipe with a minimum
inside diameter of 18 inches (450 mm) cut ln half
lengthwise. Fill with concrete having a minimum
unit welght ol 145 lbs/ft3 (2,32 metrlc tons/m")
reinforcsd with three equally spaced 4o-grad€,
1l?-inch (13 mm) diameter st€61 bars. Weight is
61 lbs/ft (91 kg/m) minimum.
6in
[150 mm]
12 in
[300 mml t*
Backlill and Cover
Place backfill between deadman anchor and tank sidewall to fully fill vold
and tank body corrugations. A mlnimum 6" layer (150 mm) of suitable cov€r
material is required over all lnfiltrator tank installations. Mound cover to
direct surface water drainage away from the tank excavatlon footprint to
prevent filling of the tank excavation with procipitation. Establish erosion'
rosistant vegetation within tho tank installation footprint. Reler to lnfiltrator
lM-Series Tank lnstallation lnstructions for complete backfilling and cover
procedures.
Contact lntlltrator Water Technologies'Technlcel Seruices Depanm€nt for 6ssistonc€ at 1-800-221-4435.
General Speciflcations contlnued
Concrete Tralfic Barrler
Use commercially availabl€ steel-
r€intorced concrete trattic banier or
€quivalent, Typical dimensions include a
24-inch-wide base taperlng to a 6-inch-
wide top, with a height of approximately
32 inches (600 mm x 150 mm x 800
mm). W€ight is 990 lbs/foot (580 kg/m)
minimum.
Precast Bloclts
Concrete pr€oast€rs can fabricate
blocks of various dlmensions and
weights. Blocks are otten an affordabls
option if they satisfy the minimum
weight requirements for use as buoyancy control (see Table 2 and
the Supplemental Force section of Btep 2 for more
information).
be align€d properly for €ach tank model (see Step 3; lmplom€ntation), and
follow th€ anchor manufactur€r installation instructions.
Concrete Collar
A ballast may be constructed along the rnid-height seam ot the tank using
cast-in-place concrete (minimum 3,000 psi compressive strength at 28
days and minimum 6% air entrainm6nt). Concrote shall be cast in contact
with the exterior surface ol th€ tank to allow interlock with sidewall ribs and
the mld-height flange. Reintorcing sleel is not r€quired, but may bo added
if desired.
General lnformation. Prior to ground dislurbanee, check tor subsurface obstruclions ancl
utilities in conformanc€ with applicable regulatory requirements.. ExcavEtion slaf€ty provisions shall conform to applicable government
regulations,. Follow manufacturer instructione for all products and devices used for
lnf iltrator tank buoyancy control.. Buoyancy control mothods descrlb€d her€in do not account lor
unanticlpated conditions such as surface flooding, temporary inundalion
or other natural occurrences, uninlended removal of cover till over tank,
€tc.. Buoyancy control melhods described herein are recommendatlons only;
consult a professional engineer for customized designs, if deslred.
32 in
[800 mm]
l_ 2a in _lI [600 mm] |
HelicalAnchors
ChancerM No-Wrench Screw Anchors with a 6-inch (150
mm) diameter flight, Class 7, or equal. These anchors rely
on the sh€ar strength of tho soil combined with th€ w€ight
of the soil above tho anchor llight to provide holding
strength. Proper installation is to 4 te€t (1.2 m) below the
bottom of th6 tank excavation and to within 5'of alignment
wlth the strap alignment, Dotormin€ the prop€r locatlons
for anchor installation to €nsure that tie-down straps will
Typical working torqus:
%" Hod 400 ft. lbs. (542 l.l.m)
1" Rod 1,000 ft, lbs. (1,356 N'm)
1%" Rod 2,300 ft, lbs. (3,118 N.m)
lnf lltrator Water Technologles' LLG ("lnf lltrator")
INFILTFATOR@ SEPTIC TANK LIMITED WARRANTY FIVE {5} YEAR MATERIALS AND WORKMANSHIP LIMITED WARRANTY
lnfiltrator's liability spaoifically axcludes the coBt of removal and/or lnstallatlon of tho Tank.
(q YOUR EXCLUSIVE REMEDY WTH RESPECT TO ANY AND ALL LOSSES OR DAMAGES RESULTING FROM ANY CAUSE WHATSOEVER SHALL BE SPECIFIED IN SUBPARAGRAPH (A}
ABOVE, INFILTRATOR SHALL IN NO FYENT BE LIABLE FOR ANY CONSEOUENTIAL OR INCIDENTAL DAMAGES OF ANY KIND. HOWEVER OCCASIONED, WHETHER BY NEGLIGENCE
OR OTHERWISE, SOME STATES DO NOT ALLOW THE P(CLUSION OR LIMITATION OF INCIDENTAL OR CONSEOUENNAL OAMAGES, SO THIS LIMITA TION OR E)(CLUSION MAY NOT
APPLY TO YOU, THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO sTATE,
(d) THIS LIMITED WARRANTY IS THE EXCLUSIVE WARMNTY GIVEN BY INFILTRATOR AND SUPERSEDES ANY PRIOR, CONTRARY, AODIIIONAL. OR SUBSEQUENT REPRESENTATIONS,
WHETHER ORAL OR WRITTEN, INFILTRATOR DISCI.AIMS AND EXCLUDES TO THE GREATEST EXTENT ALLOWED BY I.AW ALL OTHER WARRANNES, WHETHER EXPRESS OR
IMPLIED, OR STATUTORY.INCLUDING ANYWARRANTYOF MERCHANTABILITY, FINESSE FORA PARTICUI.AR PURPOSEANDANY IMPLIED WARMNTIES OTHERWISEARISING FROM
COURSE OF OEALING, COURSE OF PERFORMANCE, OB USAGE OF TRADE, NO PERSON (INCLUDING ANY EMPLOYEE, AGENT, DEALER, OR REPRESENTATIVq IS AUTHORIZED TO
MAKE ANY REPRESENTATION OR WARRANTY CONCERNING THIS PRODUCT, EXCEPT TO REFER YOU TO THIS LIMITED WARMNTY. EXCEPT AS E(PRESSLY SET FORTH HEREIN,
THIS WARRANTY IS NOT A WARRANTY OF FUTURE PERFORMAIICE, BUT ONLY A WARRANW TO REPAIR ()R REPLACE,
(6) YOU MAY ASSIGN THIS LIMITED WARRANW To A SUBSEQUENT PURCHASER oF YoUR HOME'
(f) NO REPRESENTATIVE OF INFILTRATOR HAS THE AUTHORITY TO CHANGE THIS LIMITED WARRANTY IN ANY MANNER WHATSOEVER, OR TO PCIEND THIS LIMITED WARRANTY.
(s) No wARMNw oF ANY KIND lS MAoE WITH REGARD TO ANY PRoDucT, COMPONENTS' DEVICES, MEDIA OR TREATMENT UNITS WHIGH ARE MANUFACTURED BY OTHERS AND
ARE INSTALLED IN AN INFILTRATOR TANK, USE OF THESE PRODUCTS ARE AT YOUR OWN RISK,
(h) THE TNFTLTRATOR TANK tS DESTGNED TO BE BURIED UNDERGROUND. NO WARRANTY OF ANY KIND rS MAOE rF YOUR TANK lS NOT BURTED UNDERGROUND AS SPECIFIED lN THE
PRODUCT'S INSTALI.ATION INSTRUCTIONS.
CONDITIONS AND EXCLUSIONS
the installatlon instructions and dispbsing ol chemicals or other materials contrary to normal tank usego.
prior to the purchase of a Tank,
I N FI LTRATOR
4 Businoss Pafk Road
P.O. Box 768
Old Saybrook, CT 06475
860-577-70@' Fax 860-677-7001
1-800-221-4.136
wwwlntlltratoni atsr.com
info@inli ltratonivater,com
tradsmark of TUF-TITE, lNC. Ultra-Rib is a traosmark of IPEX Inc.
o 2019 lnfiltratorwatsrTechnologies, LLc All rights €3€ru6d, Prinied in u,s.A. TANKo3 0519