HomeMy WebLinkAboutMechanical DrawingsM0-1 A.SUBSTITUTIONS: SUBSTITUTION OF SPECIFIED EQUIPMENT WILL BE ALLOWED THROUGH A PRIOR APPROVAL PROCESS INITIATED BY THE CONTRACTOR. CONTRACTOR SHALL SUBMIT INTENDED SUBSTITUTION AT LEAST FIVE DAYS PRIOR TO BID FOR APPROVAL FROM ENGINEER. SUBMITTAL SHALL INCLUDE CAPACITIES, DIMENSIONS AND OPERATING INSTRUCTIONS FOR EACH PIECE OF EQUIPMENT. SUBSTITUTION SHALL OCCUR AT NO COST TO THE OWNER. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF APPROVED SUBSTITUTION AND SHALL INCUR ALL COSTS ASSOCIATED WITH THE SUBSTITUTION INCLUDING STRUCTURAL MODIFICATIONS, SPACE LAYOUT AND REDESIGN COSTS. SEE ALSO DIVISION I GENERAL REQUIREMENTS. EXAMINATION OF SITE, DRAWINGS, SPECIFICATIONS: A.EXAMINE CAREFULLY THE SITE AND CONDITIONS OF THE SITE. PROVIDE ALL NECESSARY EQUIPMENT AND LABOR TO INSTALL A COMPLETE WORKING SYSTEM WITHIN THE SITE CONDITIONS. B.EXAMINE THE DRAWINGS AND SPECIFICATIONS AND 5 DAYS PRIOR TO BIDDING REPORT ANY ERRORS, OMISSIONS, INCONSISTENCIES, AND CONFLICTS TO THE ENGINEER TO BE REMEDIED IN AN ADDENDUM TO THE PROJECT PRIOR TO BID TIME. C.DRAWINGS ARE DIAGRAMMATIC AND CATALOG NUMBERS GIVEN ARE FOR REFERENCE ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE CAPACITY OF THE EQUIPMENT MEETS THE DRAWING REQUIREMENTS AND SHALL NOT DIMENSION FROM THE MECHANICAL, PLUMBING, OR PIPING DRAWINGS. D.THE LATEST ADOPTED VERSIONS OF THE INTERNATIONAL BUILDING CODES SHALL BE USED AS REQUIRED. THIS WILL ALSO INCLUDE THE LATEST ADOPTED VERSIONS OF THE MECHANICAL, PLUMBING, AND ENERGY CONSERVATION CODES. ALL METHODS AND MATERIALS REQUIRED BY THESE CODES SHALL BE REQUIRED BY THESE SPECIFICATIONS UNLESS INDICATED OTHERWISE. OTHER APPLICABLE LOCAL CODES AND ORDINANCES SHALL BE AS REQUIRED AND IT SHALL BE THE CONTRACTOR’S RESPONSIBILITY TO BE KNOWLEDGEABLE OF THESE REQUIREMENTS. E.WHERE INSTALLATION PROCEDURES OR ANY PART THEREOF ARE REQUIRED TO BE IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE MANUFACTURER OF THE MATERIAL BEING INSTALLED, PRINTED COPIES OF THESE RECOMMENDATIONS SHALL BE FURNISHED TO THE ENGINEER PRIOR TO INSTALLATION. INSTALLATION OF THE ITEM WILL NOT BE ALLOWED TO PROCEED UNTIL THE RECOMMENDATIONS ARE RECEIVED. FAILURE TO FURNISH THESE RECOMMENDATIONS CAN BE CAUSE FOR REJECTION OF THE MATERIAL. 44”MOUNTING HEIGHT ABOVE FINISHED FLOOR TO CENTER OF DEVICE A AMPS A.D.ACCESS DOOR AAV AIR ADMITTANCE VALVE ABV ABOVE AC AIR CONDITIONING UNIT AC ABOVE COUNTER AD AREA DRAIN (SEE SYMBOLS) A.F.C.ABOVE FINISHED CEILING A.F.G.ABOVE FINISHED GRADE AIC AMPERE INTERRUPTING CAPACITY AFCI ARC FAULT CIRCUIT INTERRUPTERS A.F.F.ABOVE FINISHED FLOOR AHU AIR HANDLING UNIT ALUM ALUMINUM AP ACCESS PANEL OR DOOR ATS AUTOMATIC TRANSFER SWITCH AV AUDIO / VIDEO AVG AVERAGE AWG AMERICAN WIRE GAGE BAS BUILDING AUTOMATION SYSTEM BB BASEBOARD BD BACK DRAFT DAMPER BFP BACK FLOW PREVENTOR BL BOILER BLDG BUILDING BLW BELOW BOB BOTTOM OF BEAM BOD BOTTOM OF DUCT BOP BOTTOM OF PIPE BSMT BASEMENT BTU BRITISH THERMAL UNIT C CHILLER CAFCI COMBINATION ARC FAULT CIRCUIT INTERRUPTERS CAP CAPACITY CB CIRCUIT BREAKER CBV CIRCUIT BALANCING VALVE CCT CORRELATED COLOR TEMPERATURE CKT CIRCUIT CFH CUBIC FEET PER HOUR CFM CUBIC FEET PER MINUTE CHWR CHILLED WATER RETURN CHWS CHILLED WATER SUPPLY CI CAST IRON CL CENTER LINE CLG CEILING CMU CONCRETE MASONRY UNIT CO CLEAN OUT COL COLUMN COMP COMPRESSOR CONC CONCRETE COND CONDENSATE CONN CONNECTION CONT CONTINUATION CONTR CONTRACTOR CRI COLOR RENDERING INDEX CT COOLING TOWER CT CURRENT TRANSFORMER CU CONDENSING UNIT CU COPPER CUH CABINET UNIT HEATER CVB CONSTANT VOLUME BOX CWR CONDENSER WATER RETURN CWS CONDENSER WATER SUPPLY DB DRY BULB DEPT DEPARTMENT DF DRINKING FOUNTAIN DIA DIAMETER DIAG DIAGRAM DIFF DIFFERENTIAL DISCH DISCHARGE DIV DIVISION DN DOWN DS DUCT SILENCER DWG DRAWING DX DIRECT EXPANSION (E) EXISTING EA EXHAUST AIR GRILLE/REGISTER EAT ENTERING AIR TEMPERATURE EC ELECTRICAL CONTRACTOR ECC ECCENTRIC EF EXHAUST FAN EFF EFFICIENCY EL ELEVATION ELEC ELECTRIC ELEV ELEVATOR EM EMERGENCY FUNCTION ENT ENTERING EMT ELECTRIC METALLIC TUBE EQ EQUAL EQUIP EQUIPMENT EQUIV EQUIVALENT ES END SWITCH ESP EXTERNAL STATIC PRESSURE ET EXPANSION TANK EWC ELECTRIC WATER COOLER EWT ENTERING WATER TEMPERATURE EX EXHAUST EXPAN EXPANSION EXT EXTERNAL F DEGREES FAHRENHEIT FA FREE AREA FC FAN COIL UNIT FC FOOTCANDLE FCV FLOW CONTROL VALVE FD FIRE DAMPER FD FLOOR DRAIN FIN FINISHED FLA FULL LOAD AMPS FLEX FLEXIBLE FLR FLOOR FOB FLAT ON BOTTOM FOT FLAT ON TOP FP FIRE PROTECTION FP FIRE PUMP FPM FEET PER MINUTE FPS FEET PER SECOND FS FLOW SWITCH FSD FIRE/SMOKE DAMPER FT FEET FXC FLEXIBLE CONNECTION GND GROUND GA GAUGE GAL GALLON GALV GALVANIZED GEC GROUND ELECTRODE CONDUCTOR GFCI / GFI GROUND FAULT CIRCUIT INTERRUPTER GC GENERAL CONTRACTOR GPH GALLONS PER HOUR GPM GALLONS PER MINUTE GRS/LB GRAINS PER POUND H 2O WATER HB HOSE BIBB HD HEAD (SEE SCHEDULES) HP HEAT PUMP HP HORSEPOWER HR HOUR HT HEIGHT HTR HEATER HWR HEATING WATER RETURN HWS HEATING WATER SUPPLY HX HEAT EXCHANGER HZ HERTZ ID INSIDE DIAMETER IG ISOLATED GROUND IN INCHES INV INVERT JBOX JUNCTION BOX K KELVIN KW KILOWATT KVA KILO VOLT - AMPS L LENGTH LAT LEAVING AIR TEMPERATURE LV LAVATORY LB POUND LD LINEAR DIFFUSER LF LINEAR FEET LIN LINEAR LIQ LIQUID LM LUMEN LRA LOCKED ROTOR AMPS LV LOUVER LVG LEAVING LWT LEAVING WATER TEMPERATURE MBH THOUSANDS OF BTU PER HOUR MC MECHANICAL CONTRACTOR MCA MINIMUM CIRCUIT AMPACITY MCB MAIN CIRCUIT BREAKER MD MOTORIZED DAMPER MDP MAIN DISTRIBUTION PANEL MED MEDIUM MFR MANUFACTURER MIN MINIMUM MISC MISCELLANEOUS MLO MAIN LUG ONLY MOCP MAXIMUM OVERCURRENT PROTECTION MTD MOUNTED MUA MAKE-UP AIR UNIT N NEUTRAL NC NORMALLY CLOSED NEG NEGATIVE NIC NOT IN CONTRACT NL NIGHT / SECURITY LIGHT - DO NOT SWITCH NO NORMALLY OPEN NOM NOMINAL NTS NOT TO SCALE OA OUTSIDE AIR OBD OPPOSED BLADE DAMPER OC ON CENTER OCC OCCUPIED OCP OVER CURRENT PROTECTION OD OUTSIDE DIAMETER OL OVERLOAD ORD OVERFLOW ROOF DRAIN OZ OUNCE PBD PARALLEL BLADE DAMPER PD PRESSURE DROP PH PHASE POS POSITIVE PRESSURE POS POINT OF SALES PRV PRESSURE REDUCING VALVE PS PRESSURE SWITCH PSI POUNDS PER SQUARE INCH PT PRESSURE TRANSMITTER PTAC PACKAGED TERMINAL AIR CONDITIONER PV PLUG VALVE PVC POLYVINYL CHLORIDE QTY QUANTITY RA RETURN AIR GRILLE / REGISTER RCP REFLECTED CEILING PLAN RD ROOF DRAIN REL RELIEF REQD REQUIRED RF RETURN FAN RH RELATIVE HUMIDITY RHC REHEAT COIL RLA RATED LOAD AMPS RM ROOM RPM REVOLUTIONS PER MINUTE SA SUPPLY AIR GRILLE / REGISTER SC SHORT CIRCUIT SCA SHORT CIRCUIT AVAILABLE SCCR SHORT CIRCUIT CURRENT RATING SCH SCHEDULE SD SMOKE DAMPER SEF SMOKE EXHAUST FAN SF SUPPLY FAN SH SENSIBLE HEAT SH SHOWER SP STATIC PRESSURE SPD SURGE PROTECTION DEVICE SPEC SPECIFICATION SQ SQUARE SS STAINLESS STEEL SS SAFETY SHOWER STD STANDARD STL STEEL SYS SYSTEM TEMP TEMPERATURE TR TRANSFER GRILLE / REGISTER TR TAMPER RESISTANT TT TEMPERATURE TRANSMITTER TTB TELECOMMUNICATIONS TERMINAL BACKBOARD TYP TYPICAL TX TRANSFORMER UC UNDERCUT DOOR UH UNIT HEATER UNO UNLESS NOTED OTHERWISE UNOCC UNOCCUPIED UR URINAL V VOLTS VA VOLT AMPERE VA VALVE VAV VARIABLE AIR VOLUME UNIT VFD VARIABLE FREQUENCY DRIVE VRF VARIABLE REFRIGERANT FLOW VOLT VOLTAGE VTR VENT THROUGH ROOF W WIDTH W WATTS W/ WITH W/O WITHOUT WB WET BULB WC WATER COLUMN WC WATER CLOSET WG WATER GAUGE WP WEATHERPROOF WPIU WEATHERPROOF IN-USE WSR WITHSTAND RATING XFMR TRANSFORMER SUBSTITUTIONS:RESPONSIBLE DIVISION: UNLESS OTHERWISE INDICATED ALL HEATING, VENTILATING, AIR CONDITIONING, PLUMBING, AND OTHER MECHANICAL EQUIPMENT, MOTORS, AND CONTROLS SHALL BE FURNISHED, SET IN PLACE AND WIRED AS FOLLOWS: ITEM FURNISHED SET POWER CONTROL WIRED WIRED EQUIPMENT 23 23 26 -- COMBINATION MAGNETIC MOTOR STARTERS, MAGNETIC MOTOR STARTERS, VFD'S AND CONTACTORS 23(1)26 26(2)23 FUSED AND UNFUSED DISCONNECT SWITCHES, THERMAL OVERLOAD SWITCHES AND HEATERS, MANUAL MOTOR STARTERS 26 26 26 -- MANUAL-OPERATING AND MULTI-SPEED SWITCHES 23 26 26 26 CONTROLS, RELAYS, TRANSFORMERS 23 23 26 23 THERMOSTATS (LOW VOLTAGE) AND TIME SWITCHES 23 23 26 23 THERMOSTATS (LINE VOLTAGE) 23 23 26 26 TEMPERATURE CONTROL PANELS 23 23 26 23 MOTOR AND SOLENOID VALVES, DAMPER MOTORS, PE & EP SWITCHES 23 23(2)--23(2) PUSH-BUTTON STATIONS AND PILOT LIGHTS 23 23(2)-- 23(2) HEATING, COOLING, VENTILATION AND AIR CONDITIONING CONTROLS 23 23 26 23 EXHAUST FAN SWITCHES 23 26 26 23(2) SUBSCRIPT FOOTNOTES: 1.MOTOR STARTER TO INCLUDE CONTROL TRANSFORMER, HOA SWITCH, (1) NO AND (1)NC AUXILIARY CONTACT, AND “ON” AND “OFF” PILOT LIGHTS. 2.IF ITEM IS FOR LINE VOLTAGE, SET IN PLACE AND CONNECT UNDER DIVISION 26. WHERE FACTORY MOUNTED ON EQUIPMENT OR ATTACHED TO PIPING OR DUCTS AND USING LINE VOLTAGE FURNISH AND SET UNDER DIVISION 23, CONNECT UNDER DIVISION 26. ABBREVIATIONS: SECTION THROUGH RETURN DUCT SECTION THROUGH SUPPLY OR OUTSIDE AIR DUCT SUPPLY OR OUTSIDE AIR DUCT ACCESS DOOR (BOTTOM OR SIDE) ACOUSTICALLY LINED DUCT FIRE DAMPER, SMOKE DAMPER, FIRE/SMOKE DAMPER MANUAL VOLUME DAMPER INCLINED DROP IN DIRECTION OF ARROW INCLINED RISE IN DIRECTION OF ARROW TRANSITION, RECTANGULAR TO ROUND FLEXIBLE DUCT IN-LINE FAN TRANSITION, RECTANGULAR SPIN-IN COLLAR INTO ADAPTER ON TOP OF DUCT CEILING SUPPLY AIR REGISTER/GRILLE SIDEWALL SUPPLY AIR REGISTER (SR) ELBOW TURNED DOWN ELBOW TURNED UP ELBOW, RADIUS TYPE ELBOW, SQUARE OR RECTANGULAR TYPE WITH AIRFOIL TURNING VANES CEILING RETURN AIR REGISTER (RR) OPEN END DUCT FLEXIBLE CONNECTION SIDEWALL RETURN AIR REGISTER (RR) VD FXC RR DD PIPE DROPPING DOWN PIPE RISING UP DIRECTION OF FLOW RELIEF/SAFETY VALVE FLOW METER-VENTURI FLOW METER-ORIFICE AUTOMATIC AIR VENT (EXTEND AUTOMATIC FILL VALVE DISCHARGE TO DRAIN) MANUAL AIR VENT CONCENTRIC REDUCER ECCENTRIC REDUCER STEAM LEAK DETECTOR TPV S CBV R D STRAINER MV AV GAS COCK AQUASTAT VB VACUUM BREAKER EXPANSION LOOP GAS PRESSURE STEAM TRAP ANCHOR EJ TT FS TH PT/PS G PRESSURE SWITCH & SYPHON (STEAM) GAUGE COCK TRANSMITTER OR THERMOMETER EXPANSION JOINT TEMPERATURE FLOW SWITCH GUIDE A DIRECTION OF PITCH-RISE OR DROP STRAINER WITH BLOW OFF VALVE UNION - SCREWED OR FLANGED FLOAT OPERATED CO CD T CARBON MONOXIDE CARBON DIOXIDE THERMOSTAT CONTROL VALVE REGULATOR TRANSMITTER PRESSURE GAUGE WITH FSD FIRE SMOKE DAMPER RELIEF VALVE SOLENOID VALVE TEMPERATURE/PRESSURE DIAPHRAGM VALVE BALANCING VALVE BALL VALVE GLOBE VALVE, ANGLE GATE VALVE, ANGLE LIFT CHECK VALVE SWING CHECK VALVE GATE VALVE BUTTERFLY VALVE PLUG VALVE GLOBE VALVE CIRCUIT SETTING BALANCING VALVE THREE WAY CONTROL VALVE TWO WAY CONTROL VALVE PRESSURE REDUCING VALVE (PRV) EXISTING EQUIPMENT OR PIPE TO BE REMOVED. CS CONDENSER WATER SUPPLY CR CONDENSER WATER RETURN R REFRIGERANT LIQUID AND VAPOR LINE RS REFRIGERANT SUCTION / VAPOR HWS HOT WATER SUPPLY HWR HOT WATER RETURN HPS HEAT PUMP SUPPLY HPR HEAT PUMP RETURN V VENT PIPING D DRAIN G NATURAL GAS SMS SNOWMELT SUPPLY SMR SNOWMELT RETURN CHWS CHILLED WATER SUPPLY CHWR CHILLED WATER RETURN LINE DESIGNATION SYMBOLS MECHANICAL ELEMENTS / VALVING SMOKE DAMPER FIRE / SMOKE DAMPERFSD SD RH REFRIGERANT HIGH PRESSURE VAPOR CA COMPRESSED AIR FD - SD - FSD SECTION THROUGH EXHAUST AIR DUCT HX S AIR VENT HYDRAULIC SEPARATOR AIR SEPARATOR HEAT EXCHANGER DIGITAL SENSOR OR PUMP HVAC & DUCTWORK SYMBOLS POINT OF CONNECTION OF NEW TO EXISTING ME C H A N I C A L - CO V E R S H E E T DATE:ISSUED FOR: SHEET NUMBER: February 21, 2025 - 1:02:50pm DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 DATE: CHECKED BY: JOB NO: DRAWN BY: SCALE: TH U N D E R R I V E R M A R K E T 68 1 8 U S - 8 2 BRS/GW MH 02/21/2025 24-305 GL E N W O O D S P R I N G , C O 10/07/2024 DESIGN DEVELOPMENT 02/21/2025 100% CD 3 COMPARTMENT SINK DEEP FRYER HAND WASH SINK PIZZA OVEN HOOD & FIRE SUPPRESSION SYSTEM GRILL DEEP FRYER WOMEN'S RESTROOM MEN'S RESTROOM EXISTING TO REMAIN NO WORK MECHANICAL ROOM COOLER 22 " x 1 6 " MAU 1 16 " Ø 12" Ø 12" Ø 12" Ø 12" Ø 22 " x 1 6 " 22"x16" UP TO MAU-1 EF 1 GH 1 20"X20" UP TO EF-1 18 " Ø DATE:ISSUED FOR: SHEET NUMBER: February 21, 2025 - 1:02:50pm DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 DATE: CHECKED BY: JOB NO: DRAWN BY: SCALE: M1-1 ME C H A N I C A L - FL O O R P L A N TH U N D E R R I V E R M A R K E T 68 1 8 U S - 8 2 GL E N W O O D S P R I N G , C O MECHANICAL - FLOOR PLAN SCALE: NORTH SCALE:1/4" = 1'-0" 10/07/2024 DESIGN DEVELOPMENT BRS/GW MH 02/21/2025 24-305 AS SHOWN MECHANICAL GENERAL NOTES: 1.DRAWING IS DIAGRAMMATIC IN NATURE. LOCATIONS AND SIZES MAY VARY DURING FIELD COORDINATION & INSTALLATION OF MECHANICAL, PLUMBING, & ELECTRICAL. DRAWINGS DO NOT NECESSARILY INDICATE EVERY REQUIRED OFFSET, FITTING, ETC. DRAWINGS ARE NOT TO BE SCALED FOR DIMENSIONS. TAKE ALL DIMENSIONS FROM ARCHITECTURAL DRAWINGS, CERTIFIED EQUIPMENT DRAWINGS AND FROM THE STRUCTURE ITSELF BEFORE FABRICATING ANY WORK, VERIFY ALL SPACE REQUIREMENTS COORDINATING WITH OTHER TRADES, AND INSTALL THE SYSTEMS IN THE SPACE PROVIDED WITHOUT EXTRA CHARGES TO THE OWNER. 2.DUCT DIMENSIONS DO NOT REFLECT ADDITIONAL DIMENSIONS FOR INSULATION. ALL DUCTING SHALL BE INSULATED PER 2021 IECC CODE REQUIREMENTS. (SUPPLY AND RETURN AIR DUCTS AND PLENUMS SHALL BE INSULATED WITH NOT LESS THAN R-6 INSULATION WHERE LOCATED IN UNCONDITIONED SPACES AND WHERE LOCATED OUTSIDE THE BUILDING WITH NOT LESS THAN R-8 INSULATION IN CLIMATE ZONES 0 THROUGH 4 AND NOT LESS THAN R-12 INSULATION IN CLIMATE ZONES 5 THROUGH 8. DUCTS LOCATED UNDERGROUND BENEATH BUILDINGS SHALL BE INSULATED AS REQUIRED IN THIS SECTION OR HAVE AN EQUIVALENT THERMAL DISTRIBUTION EFFICIENCY. WHERE LOCATED WITHIN A BUILDING ENVELOPE ASSEMBLY, THE DUCT OR PLENUM SHALL BE SEPARATED FROM THE BUILDING EXTERIOR OR UNCONDITIONED OR EXEMPT SPACES BY NOT LESS THAN R-8 INSULATION IN CLIMATE ZONES 0 THROUGH 4 AND NOT LESS THAN R-12 INSULATION IN CLIMATE ZONES 5 THROUGH 8. GARFIELD COUNTY IS ) 3.COORDINATE FINAL LOCATION OF THERMOSTAT WITH OWNER PRIOR TO INSTALLATION. IF THERMOSTAT IS LOCATED ON EXTERIOR WALL PROVIDE THERMOSTAT WITH INSULATED BACKING. 4.ALL MOTORIZED DAMPERS ON OUTDOOR AIR INTAKES AND EXHAUST SHALL BE PROVIDED WITH CLASS IA MOTORIZED DAMPERS WITH A MAXIMUM LEAKAGE RATE OF 4 CFM/FT² AT 1.0 INCH WATER GAUGE WHEN TESTED IN ACCORDANCE WITH AMCA 500D. (PER 2021 IECC) 5.MECHANICAL CONTRACTOR SHALL FIELD LOCATE EXISTING DUCTWORK PRIOR TO CONSTRUCTION. MECHANICAL CONTRACTOR SHALL COORDINATE TIE IN CONNECTION POINTS OF NEW SUPPLY DIFFUSERS WITH EXISTING DUCTWORK AS NECESSARY. 6.MECHANICAL EQUIPMENT MANUFACTURERS AS SCHEDULED ON MECHANICAL DRAWINGS ARE SUGGESTED MANUFACTURER'S. UNLESS NOTED OTHERWISE DUE TO OWNER/CLIENT REQUIREMENTS AND PREFERENCES. MECHANICAL CONTRACTOR CAN SUBMIT EQUIVALENT EQUIPMENT FROM MANUFACTURERS THAT DIFFER FROM SCHEDULED MECHANICAL EQUIPMENT. ALTERNATE MANUFACTURERS OF MECHANICAL EQUIPMENT WILL BE REVIEWED FOR EQUIVALENCE OF PERFORMANCE AND FUNCTIONALITY BY ENGINEER. 7.WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A BUILDING SUCH THAT PERSONNEL WILL HAVE TO CLIMB HIGHER THAN 16 FEET ABOVE GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES IN HEIGHT OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL. SUCH ACCESS SHALL NOT REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE PARAPET WALL. PERMANENT LADDERS SHALL COMPLY WITH REQUIREMENTS LISTED IN SECTION 306.5 OF THE 2018 INTERNATIONAL MECHANICAL CODE. 8.CONTRACTOR TO COORDINATE MAKE UP AIR UNIT AND EF LOCATIONS TO MAINTAIN SEPARATIONS FROM EACH OTHER AND ALL OTHER EXISTING ROOF TOP EQUIPMENT ACCORDING TO IMC 501.3 02/21/2025 100% CD