HomeMy WebLinkAboutConditions of Permitc ONDITIONS OF PERMIT
B LRE- 03-25-9 1 62
ZAMP LLC - TED AND KAREN MILLER
NEW SINGLE-FAMILY RESIDENCE W/ ATTACHED GARAGE
1422 HIGH ASPEN DRIVE, GWS
PARCEL # 218725204013
1) THE APPROVED PLANS ARE TO BE ON-SlrE FOR INSPECTIONS.
2) SANITARY FACILITIES ARE REOUIRED TO BE PROVIDED FOR WORKERS.
3) A LIST OF REOUIRED INSPECTIONS WILL BE ATTACHED TO THE PLANS. THE STATE
IS TO PERMIT AND APPROVE THE ELECTRICAL WORK.
RMITS
4) UNDERGROUND UTtLtry LOCATES rS THE RESPONSIBILITY OF THE OWNER OR
CONTRACTOR. B1'I IS THE COLORADO UTILITY LOCATE HOT LINE.
5) DRA|NAGE ACROSS PROPERTY LINES SHALL NOT EXCEED THAT WHICH EXISTED
PRIOR TO GRADING. EXCESS OR CONCENTRATED DRAINAGE SHALL BE
CONTAINED ON SITE OR DIRECTED TO AN APPROVED DRAINAGE FACILITY.
EROSION OF THE GROUND IN THE AREA OF DISCHARGE SHALL BE PREVENTED BY
INSTALLATION OF NON-EROSIVE DOWN DRAINS OR OTHER DEVICES.
6) THE ROOF PLAN INICATES "POTENTIAL22.4 KW SOLAR ARRAY". ANY SOLAR
ARRAY OVER 15 KW REOUIRES A PLANNING PROCESS. IF A SOLAR SYSTEM WILL
OVER 15KW, PLEASE CONTACT COMMUNIry DEVELOPMENT FOR A PRE-APP WITH
PLANNING.
7) ALL BACKFLOW PREVENTERS ARE REOUIRED TO BE TESTED AND CERTIFIED BY A
LICENSED BACKFLOW SPECIALIST AFTER INSTALLATION AND PRIOR TO ISSUANCE
OF THE CERTIFICATE OF OCCUPANCY.
8) ELECTRICAL CODE COMPLIANCE WILL BE DETERMINED BASED ON FIELD
INSPECTIONS PERFORMED BY THE STATE ELECTRICAL INSPECTOR, (303) 869-3458.
PLEASE HAVE THE INSPECTOR SIGN THE BUILDING CARD OR PROVIDE WRITTEN
DOCUMENTATION OF THE INSPECTIONS.
9) GEOTECHNICAL OBSERVATION lS REOUIRED WHEN THE EXCAVATION lS
COMPLETE AND WRITTEN VERIFICATION BE SUPPLIED AT FOOTING INSPECTION,
2000 PSF.
10)ALL EXTERIOR LIGHTING lS TO BE DOWNCAST AND SHIELDED.
1 1)SAFETY GLAZING IS NOT DESIGNATED ON THE PLANS. SAFEry GLAZING WILL BE
cHECKED DURING THE FRAMING AND FINAL INSPECTION. (lBC 2406.4)
,f>
12)A PASSING BLOWER DOOR TEST IS REOUIRED TO BE SUBMITTED PRIOR TO
ISSUING THE CERTIFICATE OF OCCUPANCY.
13)ANY EXPOSED FOAM IS TO BE COVERED WITH AN IGNITION BARRIER OR A
THERMAL BARRTER BASED ON LOCAT|ON. (tRC R316)
14)THE HOME IS TO BE SUPPLIED WITH MECHANICALVENTILATION OF OUTDOOR
ArR. THE MINIMUM VENTTLATTON RATE rS TO BE CFM = (0.01X TOTAL SOUARE
FOOTAGE OF THE HOUSE) + 7.5 X (NUMBER OF BEDROOMS +1)GENERAL NOTES
ON THE PLANS INDICATE WHOLE HOUSE VENTILATION.
15)MINIMULLY THE ICE SHIELD IS TO BE INSTALLED AT THE EAVES TO A MINIMUM 24"
UP FROM THE INSULATED WALLS.
16)ENGINEER STAMPED TRUSS DRAWINGS ARE REOUIRED TO BE PROVIDED TO THE
INSPECTOR AT FRAMING INSPECTION.
17)ALL SHOWER DOORS ARE REQUTRED TO MAtNTA|N 22" tN THE CLEAR AND ARE
REOUIRED TO SWING OUT.
18)IF PART OF THE THERMAL ENVELOPE, ATTIC ACCESSES ARE REOUIRED TO BE
WEATHER STRIPPED AND INSULATION IS TO BE PERMANENTLY ATTACHED TO THE
ACCESS. THE R-VALUE FOR THE ACCESS IS THE SAME AS THE ATTIC.
19)IF THE SLAB ON GRADE IS HEATED, A MINIMUM OF R-5 INSULATION IS REOUIRED
UNDER THE SLAB.
20)TYPICAL GARAGE FIRE SEPARATION IS 5/8" GYPSUM ON THE CEILING AND %'
ON THE WALLS. THE DOOR FROM THE GARAGE TO THE HOME IS TO BE 1 3/8'
SOLID CORE OR 20 MINUTE RATED.
21)FLOOR DRATNS tN GARAGES ARE NOT ALLOWED TO BE T|ED TO SEWER
UNLESS ROUTED THRU A SAND/OIL SEPARATOR. OTHERWSE, DAYLIGHT THE
DRAIN OR RUN TO A DRYWELL.
22)KITCHEN HOODS OVER 4OO CFM REQUIRE MAKE-UP AIR. THE STOVE/OVEN
MANUFACTURER SPECIFIES THE CFM REQUIRED.
23)THE SEPTIC, OWTS PERMIT, IS TO BE APPROVED BY THE GARFIELD COUNTY'S
ENVIRNMENTAL HEALTH DEPARTMENT PRIOR TO THE FINAL BUILDING
INSPECTION AND CERTIFICATE OF OCCUPANCY TO BE ISSUED.