May 3, 2025 Project No. C1921
Richard Chamberlain
rich1470@yahoo.com
Onsite Wastewater Treatment System (OWTS) Installation Observations
248 Basalt Mountain Road
Garfield County, Colorado
OWTS Permit Number SEPT-9007
Richard,
CBO Inc. observed the installation of the onsite wastewater treatment system (OWTS) on March 20, 2025
for the subject property. Finishing Touch Dirtworx installed the system.
The existing septic tank was abandoned by pumping the tank and crushing the top, bottom, and sides
and filling in the void with onsite materials.
The OWTS design is based on 4-bedrooms. An average daily wastewater flow of 525 GPD was used.
A new, 4-inch SDR-35 sewer line ties into the exiting sewer line and a double-sweep clean out was
installed while maintaining a minimum 2% grade to the new septic tank.
The system installation included a 1500-gallon, two-compartment Infiltrator® poly septic tank with an
Orenco® Biotube effluent filter on the outlet tee. This filter must be cleaned annually, or as needed.
A new distribution box was set at an elevation to connect to the existing trenches. The distribution box is
accessible from grade with flow equalizers installed on each outlet pipe in the distribution box to assure
equal flow to each trench.
The existing two trenches consist of 13 ‘Standard’ Infiltrator® chambers for a total of 487.5 square feet of
infiltrative area. Four new trenches consisted of 15 ‘Quick 4’ Standard Plus Infiltrator® chambers each
for a total of 60 chambers and 720 square feet of infiltrative area. There was at least 4-feet of
undisturbed soil between each trench. Inspection ports were installed at the beginning and end of each
trench (both existing and new). Ports were cut to grade and placed in sprinkler boxes for access.
The OWTS was generally installed according to specifications. This observation is not a guarantee of
workmanship and/or parts and materials. CBO Inc. should be notified if changes are made to the OWTS
in the future. Any additional OWTS construction must be according to the county regulations.
LIMITS: Observations are limited to components that are visible at the time of the inspection. The installer must
have documented and demonstrated knowledge of the requirements and regulations of the county in
which they are working. The quality of the installation is dependent on the expertise of the installer, soil
type, and weather conditions.
Please call with questions.
Sincerely,
CBO Inc.
Carla Ostberg, MPH, REHS
New sewer line and clean out tied into existing / new septic tank
Effluent filter on outlet
Distribution box Sewer lines existing distribution box
New trenches
New trenches
See photos of punch list items
62.5'
81.25'
4" DIA SDR-35 INSPECTION PORT AT
BEGINNING AND END OF EACH TRENCH
4" DIA SDR-35 DISTRIBUTION LINE TO EACH
TRENCH
(MIN. 1% SLOPE TO TRENCH)
4" DIA SDR-35 SEWER LINE TO STA
(MIN. 1% FALL TO STA)
NEW D-BOX WITH ACCESS AT GRADE
'QUICK-4' CHAMBER TRENCHES.
4 TRENCHES WITH 15 CHAMBERS
PER TRENCH FOR A TOTAL OF 60
CHAMBERS AND 720 SF.
TIE INTO EXISTING SEWER PIPE WITH 4" DIA
SDR-35 SEWER PIPE. ADD CLEANOUT. MIN
2% FALL TO TANK
1500-GALLON, TWO-COMPARTMENT INFILTRATOR
POLY SEPTIC TANK WITH EFFLUENT SCREEN
EXISTING STANDARD CHAMBER TRENCHES.
2 TRENCHES WITH 13 CHAMBERS PER TRENCH
FOR A TOTAL OF 26 CHAMBERS AND 487.5 SF.
EXISTING SEWER LINE
4-BEDROOM
RESIDENCE
D
R
I
V
E
W
A
Y
PROPERTY LINE
OUT
BUILDING
BASALT MOUNTAIN ROAD
EXISTING SEPTIC TANK ABANDONED
10'10'
2'
3'
10'
60'
Chamberlain Residence
248 Basalt Mountain Road
Garfield County, Colorado
Project Number: C1921
Date: 05/03/2025
Designed by: CBO
Drawn by: DD Sheet 1 0F 1
recordCBO Inc.
129 Cains Lane
Carbondale, Colorado 81623
Phone 970.309.5259
carla.ostberg@gmail.com
N
SCALE: 1" = 30'-0"
Garfield County Public Health
2014 Blake Ave.
Glenwood Springs, CO 81601
Phone: (970) 945-6614 ext. 8150
For inspections, call: 970-945-6614 ext. 8150 and call the Design Engineer, if applicable
Project Address: 248 Basalt Mountain Drive, Carbondale, CO Parcel No.: 239116301028
Owner Name: Richard Chamberlain Owner Phone: (970) 379-2460
Designed By: CBO Inc. Designer Phone: (970) 309-5259
Number of Bedrooms: _4_ Minimum Tank Capacity: 1250-gallon Minimum Absorption: 1050 ft2
OWTS PERMIT
KEEP AVAILABLE AT PROJECT SITE
Permit Number _SEPT-9007_______________________________
Permit Type X New X Repair X Remodel/addition X Tank only
Issue Date _12/13/2024____________________ Expiration Date_12/13/2025_________________
Permit Conditions:
This OWTS Permit is approved on the condition of compliance with the report and design as submitted by
CBO Inc. dated November 7, 2024. Changes to the design and permit must be approved by Garfield
County Public Health and the designer prior to construction.
The new OWTS will expand an existing STA and serve an existing four-bedroom residence which results
from a bedroom addition. The new OWTS components will tie into the existing sewer line. A new 1500-
gallon two compartment septic tank set level with access to grade and an effluent filter installed in the
outlet tee of the tank will be installed. The septic tank shall be on the Colorado Department of Public
Health and Environment’s approved septic tank list. The existing tank will be abandoned in accordance
with Garfield County OWTS Regulations either by removal or crushing. Effluent will gravity flow to a new
distribution box set level with access to grade and then to six distribution lines that will distribute
effluent to 1207.5 ft2 of STA comprised of 487.5 ft2 of existing STA and 720 ft2 of newly installed STA. The
existing STA area, constructed in 1999 as documented by Garfield County Individual Sewage Disposal
System Permit 3179, is comprised of two gravelless chamber trenches, each trench consisting of 13
standard 6.25 ft long chambers (26 chambers total). The new STA area will consist of four gravelless
chamber trenches, each trench consisting of 15 ‘Quick 4’ chambers per trench (60 chambers total).
Inspection ports will be installed at each end of each trench. Maintain all setbacks and elevations as
designed.
Contact the designer and Garfield County Public Health (970-945-6614 ext. 8150) at least 48 hours prior
to requesting final inspection of the installed system prior to backfill. NO OWTS COMPONENT SHALL BE
BACKFILLED WITHOUT PRIOR APPROVAL FROM GARFIELD COUNTY PUBLIC HEALTH AND THE DESIGNER.
Agreement
All installations must comply with all requirements of the Garfield County OWTS regulations
including but not limited to the conditions specified above.
In consideration of the issuance of the permit, the applicant hereby agrees to comply with all
laws and regulations related to the zoning, location, construction, and erection of the proposed
OWTS and associated structures for which this permit is granted. The applicant further agrees
that if the above said regulations are not fully complied with in the zoning, location, erection,
and construction of the above described OWTS and structure, the permit may then be revoked
by notice from the Health Department and immediately become null and void.
The issuance of a permit and specifications of terms and conditions therein will not constitute
assumption of liability, nor create presumption that the local public health agency or its
employees may be liable for the failure or malfunctioning of any system. Permit issuance will
not constitute a certification that the system, the equipment used in the system, or any
component used for system operation will ensure continuous compliance with the provision of
the OWTS Act, the regulations adopted thereunder, or any terms and conditions of a permit.
Permit Approval
Plans and specifications for the proposed OWTS have been reviewed and are considered
satisfactory. Permission is hereby given to the property owner(s) to perform the work indicated
in accordance with the Garfield County OWTS Regulation. This Permit will expire 1 year from
the date of issuance unless construction on the system has commenced. An "as-built" drawing
must be submitted and inspection of the system must be completed by GCPH before final
approval of the system will be issued.
12/13/2024
Issued By: Garfield County Environmental Health
Department
Date
832‐R‐13‐002