HomeMy WebLinkAboutElectrical PermitL137123,9:30AM Print Permit
6|1u.m A.xtsef2 77oAttffis
OK
COLORADO STATE ELECTRICAL BOARD
ELECTRICAL PERMIT NUMBER: 967365
Date Paid:31-JAN-23 Expires On: 3I--JAN-24
For inspections, click the 'Request lnspection' link on the permit list screen
Eaker, Andrew Scott
EAKER ELECTRIC, LLC
1.796 ANVIL VIEWAVE
RTFLE, CO 8L650
Daytime Phone: (970) 456-5745
Power Supplier: XCEL
Owner Name: NUTRIENT HOLDINGS
Address: 333 NUTRIENT FARM RD
City: NEW CASTLE, CO.
Registration Number:
LOO492
Trim Permit:N
NUTRIENT FARM
FAX
COMMERCIAL
COMMERCIAL NEW
Driving Directionsi Exit l-70 at New Castle exit. Cross bridge heading south towards
County Road 335. Turn left, going east towards River Bend Subdivision. Property on left side
(South side)of County Road 335. Large green house.
Description: Green House lnstall service gear being fed by a permanent generator. lnstall
various branch circuits for general power and control requirements. lnstall sub feeds for office
trailers.
NOTICE: DO NOT coNrAcrrHE DENVER oFFrcES REGARDTNG rNSpEcloN
SCHEDULING.
CONTACT YOUR INSPECTOR FOR SCHEDULING
INFORMATION.
lnspector Norman Feck
Emai I : norman.feck@state.co.us
Phone: 303-869-3M2
Cost of work: $80,000.00 Fee Amount: $540.00
https://www.dora.state.co.us/pls/real/ep_web_permit_gui.print_permit?p_session_id=3738440&p_app_id=767870 1,t2
COLORADO STATE ELECTRICAL BOARI)
L560 Broadway, Suite 1.350
Denvero CO 80202
Inspection Report
Date lnspected: 03/09 12023
Permit #:
Permit Holder:
Site:
Owner:
967365
Eaker Electric, LLC Andrew Eaker
1796 AnvilView Ave Rifle 81650
Phone: (970) 456-5745 Fax: Email: Eakerelectric@outlook.com
333 Nutrient Farm Rd New Castle, Garfield County,
Nutrient Holdings
Status Partial
lnspection Type: Rough ln
NEW COMMERCIAL
lnspector:Norman Feck 303-869-3442
Corrections:
250.50, 250.52A3,250.53A2 Where no electrodes are present at a building or structure, a ground
ring, ground rods, pipes, plates, or other suitable electrode shall be installed. Chip to concrete
encased electrode in building. Do not sever but use a hinge type clamp. Not typically required to
supplement ufer but the continuos 20'of rebar can't easily be confirmed so supplement with 2 ground
rods. Leave the rebar connection open for inspection.
Comments:
1) HDPE UG ok from generator pad to building MDP
2) HDPE UG ok from MDP to office trailers west side of building
3) HDPE has PVC fittings and the adheisve used was shown to be listed for these transitions. 353.6