HomeMy WebLinkAboutFire Marshall-Plan Review CommentsPlan Review: Carbondale & Rural Fire Protection District
Plans for an automatic sprinkler system will be submitted to Karl Oliver
(Fire Marshal)for review and approval. Rough-in and final inspections
will be completed.
Fire alarm and detection:
a
Hydrants:
a
Sprinkler System:
a
a 804.4.L.6 Group R-2. (tEBC 201s).
A fire alarm system shall be installed in work oreos of Group R-2 apartment
buildings as required by the lnternotional Fire Code for existing Group R-2
occupancies.
907.2.11.2 Groups R-2 IFC 20L5
Single or multiple-station smoke alarms shall be installed and maintained
in Groups R-2, R-3, R-4 and l-1 regardless of occupant load at all of the
following locations:
t. On the ceiling or wall outside of each separate sleeping area in the
immediate vicinity of bedrooms.
2. ln each room used for sleeping purposes.
3. ln each story within adwelling unit, including basements but not
including crawl spaces and uninhabitable attics.
ln dwellings or dwelling units with split levels and without an
intervening door between the adjacent levels, a smoke alarm installed
on the upper level shall suffice for the adjacent lower level provided
that the lower level is less than one full story below the upper level.
Hydrant 331203 is located on the North East corner of the building site.
This hydrant has not been flow tested and we will get it on the schedule
to do so.
Karl Oliver
Prevention Division Chief
Fire Marshal
Carbondale & Rural Fire Protection District