HVAC Load Calculations
for
t ^',t.\ tl V. ,,f{,,\,tBaltzer Residence
138 Sunlight Drive
Garfield County, Co
RHVAC FIEETpNNNAL
HVAG Lonne
a
Lt
\
\\
s
Prepared By:
M. Dunne
MDA Design Consulting, LLC
5001 N Blazingstar Trail
Castle Rock, Co.80109
888-903-6255
Friday, March 21, 2025
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2.50, and ACCA Manual D.
t I
Rhvac - Residential & Light Gommercial HVAG Loads
MDA Desiqn Consultinq. LLC G Elite Sofiivare Development, lnc.
Project Date:
Client Name:
Clicnt Addross:
Client City:
Company Name:
Cotr rparty Repl eselrtalive:
Company Address:
Company City:
Company Phone:
Company E-Mail Address:
Company Website:
3-18-2025
Baltzer Residence
138 Sunlight Drive
Garfield County, Co
MDA Design Consulting, LLC
M. Dunne
5001 N Blazingstar Trail
Castle Rock, Co.80109
888-903-6255
mdunne@mdadesginconsulting.com
mdadesignconsulting.com
Reference City:
Building Orientation:
Daily Temperature Range
Latitude:
Elevation:
Altitude Factor:
39
6275
0.793
Gatfield Cuutrty, Cululado
Front door faces North
Medium
Degrees
ft.
Winter:
Summer:
Outdoor
Dry Bulb
0
94
Outdoor
Wet Bulb
5.97
59
Outdoor
Rel.Hum
nla
13Yo
lndoor
Rel.Hum
nla
50%
lndoor
Dry Bulb
74
70
Grains
Difference
nla
-31
Total Building Supply CFM:
Square ft. of Room Area:
Volume (ft3):
1,494
1,056
6
^
A6o'+o
CFM Per Square ft.:
Square ft. Per Ton:
1.415
316
Total Heating Required lncluding Ventilation Air:
TotalSensible Gain:
Total Latent Gain:
Total Cooling Required lncluding Ventilation Air:
38,737 Btuh
29,977 Btuh
10,146 Btuh
40,123 Btuh
38.737
75
25
3.34
MB
ot
TO
ot
TO
H
Tons (Based On Sensible + Latent)
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2.50, and ACCA Manual D
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacture/s performance data at
your design conditions.
C:\ ...\Garfiled Cou ... _3-1 0-25.110 Friday, March 21,2025,12:48 PM
*
Rhvac. Resldential & Ught Gommercial }IVAG Loads
tLcMDADbsisn
Load Preview
Sen
Gain
Lat
Gain
Net
Loss
sys
Htg
CFM
sys
clg
CFM CFM
Net
Ton
ft.
Scope
Buildinq
Svstem 1
Misc. Supplv
Zone 1
1-Livinq Room
2-Master Bedroom
3-His Closet
4-Her Closet
s-Master Bath
6-Bath
7-Bedroom
&Fover
1,056
1,056
1,056
448
168
20
20
120
50
130
100
29,977
29.977
0
29,977
11,886
5,25'l
708
652
3,361
1,157
4,361
2,601
10,146
10,146
9,000
1,146
532
u7
-10
0
45
-10
373
41
40,123
40,123
9,000
31,123
12,418
5,598
708
652
3,361
1,157
4,734
2,601
38,737
15,970
6,320
839
62'l
4,665
1,770
4,574
3,978
634
261
103
14
10
76
29
75
65
't,494
592
262
35
32
168
58
217
t30
,494
592
262
35
32
168
58
2',17
130
3.34
3.34
316
316
1.494 1.494
1A94 1,494
38,737 6v
38,737 6U
C:\ ...\Garfiled Cou ... 3-10-25.110 Friday, March 21,2025, 12:48 PM
Rhvac - Residential & Ught Gommercial HVAG Loads
MDA Desiqn Consultinq, LLC *
Elite Sofhrarc Development, lnc.
Total B Loads
Gornponent Sen Lat Sen Total
2A-f-d: Glazing-Double pane low-e (e = 0.60), sliding
glass door, insulated fiberglass frame, outdoor insect
screen with 100% coverage, light color drapes with
lrrediunr weave witlr 50% uuverage, U-value 0.028,
SHGC 0.56
2A-f-d: Glazing-Double pane low-e (e = 0.60), sliding
glass door, insulated fiberglass frame, U-value 0.028,
sHGC 0.56
1 1L: Door-Metal - Paper Honeycomb Core, U-value 0.56
12E-6sw: Wall-Frame, R-19 insulation in 2 x 6 stud
cavity, R-6 board insulation, siding finish, wood
studs, U-value 0.049
ceiling: Partition Roof/Celllng (STD=14, WTD=3O)-Roof
Deck (roofing, wood, insulation) or SIP Panels
Supported on Beams, Custom, 1.5" wood plus R-33
to R-35 insulation, U-value 1
20P1 -30op-c: Partition Floor (STD=14, WTD=3O)-Over
open crawl space or garage, Passive, spray foam
insulation, R-30 open cell ll2lb. spray foam
insrrlalion I inches in 2 v 1O ioisf r:avitv namol
' - ,-'-' -- r rr, t vsr Fv-
87.5 181 o 2,405 2,405
7.5 16 402 4020
18
879
746
3,188
1056 31,680
1056 1,108
0 14,784 14,784
519 519
0
0
353
903
353
903
0
covel4g, U:value O035
Subtotals for structure:
People:
Equipment:
Lighting:
Ductwork:
lnfiltration: Winter CFM: 28, Summer CFM: 15
Ventilation: Winter CFM: 0, Summer CFM: 0
Supply Miec. Gain:
7
1950
36,919 0
't,400
0
0
-254
0
9,000
19,366
1,610
1,064
6,650
0
324
0
0
963
19,366
3,010
1,064
6,650
0
70
0
9,000
1,81
0
8
0
0
0AED EXqutsion 0 963
Total Building Load Totals:38,737 10,146 29,977 40,123
Total Building Supply CFM:
Square fi. of Room Area:
Volume (ft3):
1,494
1,056
8,448
CFM Per Square ft,:
Square ft. Per Ton:
1.415
3'16
Total Heating Required lncluding Ventilation Air:
TutalSerrsible Gain:
Total Latent Gain:
Total Cooling Required lncluding Ventilation Air:
38,737 Btuh
29,977 Btuh
10,146 Btuh
40,123 Btuh
38.737 MBH
75 Ya
25%
3.34 Tons (Based On Sensible + Latent)
Rhvac is an ACCA appruved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2.50, and ACCA Manual D.
n ll ^^a^, .r^l -^^. .14^ ^-^ -^r:-^r^^[ vvrrrlJu.Ev tErutrD dtE EDuiltdlt'b a5 uuiluiltg use all(J wt,al,ngr may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\...\Garfiled Cou ... 3-10-25.r10 Friday, March 21,2025, 12:48 PM
Rhvac - Residential & Llght Gommercial HVAC Loads
MDA Design Consulting, LLC s Elite Sofhrare Development, lnc.
1 Whole House S Loads
Component Area Sen Lat Sen Total
2A-f-d: Glazing-Double pane low-e (e = 0.60), sliding
glass door, insulated fiberglass frame, outdoor insect
scrccn with 100% coverago, light color drapes with
medium weave with 50% coverage, U-value 0.028,
SHGC 0.56
2A-f-d: Glazing-Double pane low-e (e = 0.60), sliding
glass door, insulated fiberglass frame, U-value 0.028,
sHGC 0.56
11L: Door-Metal - Paper Honeycomb Core, U-value 0.56
12E-6sw:Wall-Frame, R-19 insulation in 2 x 6 stud
cavity, R-6 board insulation, siding finish, wood
studs, U-value 0.049
ceiling : Partition Roof/Ceiling (STD= 1 4, WTD=3O)-Roof
Deck (roofing, wood, insulation) or SIP Panels
Supported on Beams, Custom, 1.5" wood plus R-33
to R-35 insulation, U-value 1
20Pl -30op-c: Partition Floor (STD=14, WTD=3O)-Over
open crawl space or garage, Passive, spray foam
insulation, R-30 open cell 1l2lb. spray foam
insulation, 8 inches in 2 x 1O joist cavity, carpet
o 2,405 2,405
1056 31,680 o 14,784 14,784
1056 1,108
coverinq, U-value 0.035
87.5 181
7.5
18
879
16
746
3,188
402
519
353
519
402
903
353
903
0
0
0
0
Su btotals for structure:
People: 7
Equipment:Lighting: 1950
Ductwork:
lnfiltration: Winter CFM: 28, Summer CFM: 15
Ventilation: Winter CFM: 0, Summer CFM: 0
Supply Misc. Gain:
AED Excursion:
System 1 Whole House System Load Totals:
36,919 19,366
1,610
1,064
6,650
0
324
0
0
19,366
3,010
1,064
6,650
0
70
0
9,000
9q3
40,123
0
1,400
0
1,81
0
8
0
0
0
0
-254
0
9,000
0 963
38,737 1A,146 29,977
Supply CFM:
Square ft. of Room Area:
Volume (ft3):
1,494
1,056
8,448
CFM Per Square ft.
Squareft. PerTon:
1.415
316
Total Heating Required lncluding Ventilation Air:
Total Sensible Gain:
Total Latent Gain:
Total Cooling Required lncluding Ventilation Air:
38,737 Btuh
29,977 Bluh
10,146 Btuh
40,'t23 Bruh
MBH
ofto
%
737
75
25
3.34
38.
Tons (Based On Sensible + Latent)
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2.50, and ACCA Manual D,
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\...\Garfiled Cou ... 3-10-25.110 Friday, March 21, 2025, 12:48 PM
S ce Data -
Gooling:
Outdoor Dry Bulb:
OutdoorWet Bulb:
lndoor Dry Bulb:
lndoor RH:
Supply Airflow:
0
59
70
50
0
Senslble Galn: -
Latent Gain:
TotalGaln:
Load SHR:
Entering Dry Bulb:
Entering Wet Bulb:
29_977
10.146
40.123
0.75
0
0
Heating:
Outdoor Dry Bulb:
lndoor DryBulb:
Indoor RH:
0
74
30
Sensible Loss:
Entering Dry Bulb:
SupplyAirflow:
38.737
74.O
634
This system's equipment was selected in accordance with ACCA Manual S.
Cooling:
ModelType: Two Stage A'/C, Outdoor Model: RA].M2x,lndoor Model: U*02VA0Z5
Nominal Capacity: 42.OOO, Manufacturer: Ruud
lnterpolation Results:
Sensible Capacity:
Latent Capacity:
TotalCapacity:
32.000
10.000
42.OOO
Load
29.977
10_146
40.123
Percent
of Load
1O7o/o
99o/o
1O5o/o
Heating:
ModelType: Natural Gas Furnace, Model: U802VA075421, Nominal Capacity: 60.000, Manufacturer: Ruud
Results:
PercentLoad ofload
Heating Capacity: 60.000 gg.737 l11o/o
C:\...\Garfiled Cou ... 3-10-25.110 Friday, March 21,2025, 12:48 pM
Att
/4CCF\.
Form
RPER 1.01
8 Mar 10
ATTACHED
e(M*EcffidM
County, Town, Municipality, Jurisdiction
Header lnformation
Contractor
Mechanical License #
Building Plan #
Home Address (Street or Lot#, Block, Subdivision) 138 Sunlight Drive, Garfield County, Co
REQUIRED ATTACHMENTS'
Manual Jl Form (and supporting worksheets): Vesffl
or MJ1AE Form' (and supporting worksheets): yes8
OEM performance data (heating, cooling, ltower):YesE!
Manual D Friction Rate Worksheet: Yeslj
Duct distribution system sketch: Ves[
ruon
no!
rvoI
ruoE
ruoE
Residential Plans Examiner Review Form
DuctsnmentLoadsEulfor HVAC S tem Desi
HVAC LOAD CALCULATTON (lRC M 1401.3)
[\esign Conclitions
Winter Design Gonditions
Outdoor temperature
lndoor temperature
Total heat loss
Latent heat gain
Total heat gain
74 0F
38737 Btu/h
Summer Design Gonditions
outdoortemperature 94 "F
lndoortemperature 70 "F
Grains dlfference -31 A Gr @ 50 o/o Rh
Sensible heat sain 29976 Btu/h
Rr rilding Constrtretion lnformatinn
Building
Orientation (Front door faces)4
North, East, West, South, Northeast, Northwest, Southeast, Southwest
Number of bedrooms 2
Conditioned floor area I fl$fi Sq ft
"F
10146 Btu/h
40122 Btu/h
Number of occupants
Windows
Eave overhang depth
3
0Ft
Drapeslntemal shade
Blinds, dEpes, etc
Roof
Eave
Depth Window
Number of skylights
HVAC EQUIPMENT SELECTION (lRC IV11401.3)
Heating Fqr ripment Flata
Equipment type Natural Gas Furnace
Fumace, Heat pump, Boiler, etc.
Model
Heatins output capacity 60000 Btuih
Heat pumps - €pacily at winter design outdoor conditions
Auxiliary heat output capacity Btu/h
Conling Fquipment f'lata
Equipment type
Air Conditioner, Heat pump, etc
Blower Data
Heatins crv 1 000 Crv
coolins cFM 1500 CFM
Two Staoe A./C
u8o2vAo75421 Model RA!442X
Sensible cooling capacity
Latent cooling capacity
Total cooling capacity
29300
1 70,n
42004
Btu/h
Btu/h
Btu/h
HVAC DUCT DISTRIBUTION SYSTEM DESIGN (lRC M1601.1)
Design airflow 15OO cFM
Extemal Static Pressure (ESP) 1 .0 IWC
Component Pressure Losses (CPL) IWC
Available Siatic Pressure (ASP) IWC
ASP=ESP-CPL
Longestsupplyduct 0 Ft
Longest return duct: 0 Ft
Total Effective Length (TEL) 00 Ft
Frlction Rate: _ IWC
tr'",,on Pslg = (ASP " 100) * TEL
Duct Materials Used (circle)
Trunk Duct: Duct board, Flex, Sheet metal,
Lined sheet metal, Other (sPecifY)
Branch Duct: Duct board, Flex, Sheelnetd-
Lined sheet m"tat,@
0
ldeclare the load calculation, equipmerrt selectron. and duct sys{em design were rigorously perfortned based on the building plan listed
s will be su ect to review arrd vabove. I urrderstand the clainrs nrade
Contractor's Printed Name
Contractor's Signature
Date
Reserved for use by County, Town, Municipality. or ALlthority havirrg jurisdiction
I The AHJ shall have the discretion to accept Required AttachmenG printed from approved ACCA software
2 lf abridged version of Manual J is used for load calculalion, then veriry residence meets requirements, see
vendors, see list on page 2 of instruclions.
Abridged Edition checklist on page 13 of instructions.
Form generated by AccA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program.
A;,rcch."
Form
RPER 1.01
8 Mar 10
ATTACHED
ruoI
Non
ruofl
r,loE
r'roE
AtCffi*pCodd6dArcrb
County, Town, Municipality, Jurisdiction
Header lnformation
Contractor
Mechanical License /f
Buildrng Plan #
Home Address (Street or Lot#, Block, Subdivision) 138 Sunlight Drive, Garfield County, Co
REQUIRED ATTACHMENTSI
Manual J l Form (and supporting worksheets): yesffl
or MJIAE Form! (and suppoftng worksheots); Ycsftl
OEM performance data (heatinq, caaling, bloweQ:YesE
Manual D Friction Rate Worksheet Yesn
Duct distribution system sketch: Yes[
Residential Plans Examiner Review Form
for HVAC S stem Desi n ur ment, Ducts)Loads, E
HVAC LOAD CALCULATION UMC 1 106.1)
Design Conditions
Winter Design Conditions
Outdoor temperature
lndoor temperature
Total heat loss
Summer Design Conditions
Outdoor temperature
lndoor temperalure
7?7 Btu/h
94 "F
7fi "F
Grainsrtifferencn -31 A Gr@ 50 % Rh
sensibre heatsain 29976 Btulh
Latent heat gain
Total heat gain
1O1A Btu/h
L 122 Btu/h
Ruilding Construction lnformation
Building
Orientation (Front door faces)4
North, East, West, Soulh, Northeast, Northwest, Southeast. Southwest
Number of bedrooms 2
1 fl$fi sq Ft
I\.UUI
Ft
o"F
7A OF
Conditioned floor area
Number of occupants
Windows
Eave overhang depth <-
lnternal shade
Blinds, dEpes, etc
Drapes Eave
Depth Window
Number of skylights 0
HVAC EQUIPMENT SELECTION
Heating Equipmpnt fiata
Equipment type Natural Gas Furnace
Fumae, Heal pump, Boiler, etc.
Model U802VA07S421
Heating output capacity
Cooling Equipment Ftata
Equipment type
Air Conditioner, Heat pump, etc
Model
Blower Data
Heatins cFM 1000 CFM
cooling cFM 1 500 CFM
Staqe A/C
RA!442X
Heat pumps - €padty at winter design outd@r onditions
Auxiliary heat output capacity
Btu/h
Btu/h
Sensible cooling capacity
Latent cooling capacity
Total cooling capacity
^9300
12700
L 2000
Btu/h
Btu/h
Btu/h
HVAU IJUCT DISTRIBUTION SYSTEM DESIGN (uMC 601 2)
Design airflow 5OO cFM
Extemal Static Pressure (ESP) 1 .O IWC
Component Pressure Losses (CPL) IWC
Awailqlrla Gfa+ia Draca...-,-ys'rsvrs -E.rv -rse-u-v {Asp}
. . -'-'-----.'.._
,*"
AsP=ESP-cPL
Longest supply duct: 0 Ft
Longest retum duct: ____O ft
Total Effective Length frEL) 00 Ft
E!:^.:^- 6^.^. It^rnr r lklrurr raolE. I vu\/
Friclbn Rate = (ASP x 100) + TEL
Duct Materials Used (circle)
Trunk Duct: Duct board, Flex, Sheet metal,
Lined sheet metal, Other (specify)
Branch Duct: Duct board, Flex, Sheet metal.
Lined sheet metal. 6their. soEil)
0
I declare tlre load calculatiorr, equtprl'terrt selectiorr. arrd ducI system clesign were rigorously per-forrled based on ilre buildinq plan listed
Itese forrls will he srrh rernr arrd verrticatior-rent toclsrrd llre claitrrs
Contractor's Printed Name
Contractor's Signature
Date
Reserved for rrse hy enrrnty Tnrvn, I\4rrrrir-ipality or Arrlhority harrin0 jL.rrirdiction
I l he AHJ shall have the discreiion to accept Required Attachments prinled from approved ACCA soffware
used for load calculation, then vedfy rcsidenr.c meets requiremenlr, see
vendors, see list on page 2
Checklist
of instruclions.
Abridgod Edition on pag@ 13 of inolruotions.
2 lf abridged version of Manual J is
Form generated by AccA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program.