Loading...
HomeMy WebLinkAboutBlower Door TestRetrotec rCloud 1 Quality Assurance Report Single Direction Multi Point Blower Door Test PASS Your Result: 1.12 ACH50 (873.26 CFM50 * 60 / 46883 ft³) Target < 3 ACH50 Test Information Test Name 143 Maroon Dr Test Date 2025-04-14 08:29 AM (PDT) Export id 2BUCZ02B Company Name Dexter Diagnostics Technician Name Amanda Poindexter Technician Email dexterdiagnostics@gmail.com Building Information Address 143 Maroon Dr City Glenwood Springs State CO Zip/postal Code 81601 Country United States Year Constructed Not available Elevation 6175 ft Address Verified?Yes Building Latitude, Longitude 39.500346, -107.310792 GPS validation Tester location not verified Estimated Distance From Address Not available Test Equipment Fan Model Retrotec 5000 Fan Serial Number 5FN105365 Pressure Gauge Model Retrotec DM32X Gauge Serial Number 502769 Environmental Conditions Pre-test Indoor Temperature 68 °F Pre-test Outdoor Temperature 44 °F Wind Speed 5 MPH Average Barometric Pressure 102.5 kPa Test Dimensions Conditioned Floor Area 4219 ft² Volume 46883 ft³ Retrotec rCloud 2 Test Results Summary Test Type Single Direction Multi Point Blower Door Test Flow Reference Pressure 50 Pa Time Averaging 10 seconds Corrected Flow 873.26 CFM @ 50 Pa Air Changes Per Hour 1.118 Percent Uncertainty 8.0% Correlation, r 0.977 Intercept 11.073 Slope, n 1.116 Test Results Test Data Set 1 Flow Direction Depressurize Gauge Location Inside Baseline, initial (Pa) -6.45 -6.82 -7.09 -7.29 -7.52 -7.69 -7.73 -7.62 -7.47 -7.12 Baseline Duration 10 seconds Average baseline -7.28 Pa Measured Pressure (Pa)-15.26 -23.68 -31.04 -39.24 Fan Pressure [5000 - B2] (Pa)151.38 Fan Pressure [5000 - B4] (Pa)51.63 89.5 176.26 Fan Pressure [5000 - B8] (Pa) Flow (CFM)353.52 436.04 581.42 846.63 Measured Pressure (Pa)-44.14 -53.56 -61.03 Fan Pressure [5000 - B2] (Pa) Fan Pressure [5000 - B4] (Pa) Fan Pressure [5000 - B8] (Pa)44.73 59.31 72.36 Flow (CFM)881.73 1026.51 1143.22 Baseline, final (Pa) -6.44 -6.5 -6.34 -6.23 -6.12 -5.98 -5.93 -5.86 -5.72 -5.42 Baseline Duration 10 seconds Average baseline -6.05 Pa Retrotec rCloud 3 Test Notes No notes entered. Flow Equation Parameters - Retrotec Calibrated Flow Parameters Fan Last Calibrated:2024-09-11 Fan Model Retrotec 5000 Fan Serial Number 5FN105365 Fan Last Calibrated:2024-09-11 Units Used For Flow Parameters in Equation CFM Fan pressure (FP) is the measured fan pressure when using a self-referenced fan or when the room pressure is negative. If using a fan which is not self-referenced, and the room pressure is positive, fan pressure is calculated by subtracting the measured room pressure from the absolute value of the fan pressure. If PrA is greater than 0 or fan is self-referencing: FP = |PrB| - PrA If PrA is less than 0 or fan is self-referencing: FP = PrB Flow calculations are not valid if fan pressure is less than either MF or (K2 x |RP|) FP = fan pressure, RP = room pressure Range N K K1 K2 K3 K4 MF Open 0.4990 555.2054 0.0000 0.3000 0.0000 1 10 A 0.5030 290.8751 0.0000 0.4000 0.0000 1 20 B8 0.5270 121.5413 0.0000 0.7000 0.0000 1 35 flow = (FP - RP x K1)n x (K + K3 x FP) x K4 Range A B C D F G K2 MF B4 0.0000176573 -0.01530302 6.2742 138.42 0.59 50 0.8000 40 B2 0.0000025309 -0.00466154 2.7545 25.71 0.92 50 1.0000 50 B1 0.0000027369 -0.00313712 1.4891 10.71 0.45 50 1.0000 60 B74 0.0000007960 -0.00095010 0.5900 18.00 0.15 25 0.8000 35 B47 0.0000002690 -0.00035905 0.2435 12.05 0.09 25 1.0000 50 B29 0.0000001110 -0.00014900 0.0920 4.40 -0.02 25 0.6000 50 flow = (A x FP3) + (B x FP2) + (C x FP) + D +((G - RP) x F)