Attached please find the corrections you requested as individual sheets for slip-sheeting.
Corrections to address prior to issuing a building permit:
1 This building appears to serve the Art Center and is being reviewed as an S-1 occupancy in
Type V Construction.
Please see new sheet G-02 with Occupancy and Use shown, clouded.
2 The new addition did not provide a dimension to the north property line. The new addition
scales approximately 37' to the north property line. When a structure is within 50' of a
property line, a stamped survey is to be submitted showing the improvements. (Amendment
to IBC 107.2.5)
Please see sheets AS-03 and AS-04 where the property line is shown, dimension and the area
clouded.
3 The solar array is shown at 15.6 KW. The County Land Use Code requires an Administrative
Review process for systems 1sKW to 500KW. Either schedule a Pre-App with Planning
Department or reduce the solar array to under 1sKW. (LUDC Table 3-403)
Please see A-115 and A-202 where we reduced the size of the array to 14.4 kW, clouded.
4 The remodeled restroom is to be accessible. Please provide adequate detailto verify
compliance. The lavatory is not to be in the water closet clearances, a 5' diameter circle in
the clear is required, grab bars, a righthand flush toilet model, knee and toe clearance on
the lavatory, reach requirements for accessories within the restroom. (ANSI 4117.1)
Please see A-111 with accessible bathroom plan and new interior elevations, clouded.
5 The sidewalk/landing outside the heated addition is shown at 36" depth. Landings outside
doors are to be 44" in depth. Please change the drawings accordingly. (lBC 1010.1 .6)
Please see A-111, clouded.
6 Please provide exit signs at the egress doors. (lBC 1013)
Please see E-01 and E-02, clouded.
7 Please provide the R-10 slab edge insulation detailforthe new heated addition. (Table
c402j.3)
Please see A-304 with R-10 insulation shown around perimeter foundation wall, clouded.
1
8 Please provide the insulation value for the new interior wall separating the Cold Storage
from the Pedestaland Hanging Shop. (Table C4021.3)
Please see drawing 7, sheetA40l, clouded.
9 Please provide the soils report that is referenced in the structural notes.
There is not a current soils report. The note is lncorrect. Lucy Hunter, PE has agreed to an open
hole inspection process,