Loading...
HomeMy WebLinkAboutPlans 2WT-ROS Project Number: T1 AS SHOWN AB MEK 1/7/2025 23.11 SITE PLAN PROJECT INFORMATION SHEET DESCRIPTION: Scale: Date: Drawn By: Checked By: Re v i s i o n S c h e d u l e No . De s c r i p t i o n Da t e STAMP 36 4 S T O R M K I N G R D , N E W C A S T L E , C O . 8 1 6 4 7 Pr o j e c t F o r : N u t r i e n t H o l d i n g s , L L C · · · · · · · · · · · · · · · · · · · · PROJECT INFORMATION: PROJECT GENERAL CODE NOTES: SHEET INDEX: PROJECT GENERAL NOTES: VICINITY MAP: GR E E N H O U S E HE A D H O U S E KEYNOTE LEGEND KEY VALUE KEYNOTE TEXT ® ® Project Number: A1 3/16" = 1'-0" AB MEK 1/7/2025 22-11 FLOOR PLAN SHEET DESCRIPTION: Scale: Date: Drawn By: Checked By: Re v i s i o n S c h e d u l e No . De s c r i p t i o n Da t e STAMP C-GEXC-GEXC-GEX C-GEX HEATED FLOOR HYDRONIC LAYOUT PLAN EQUIPMENT PLAN CODE PLAN 91 1 5 H W Y 3 3 5 , N E W C A S T L E , C O . 8 1 6 4 7 Pr o j e c t F o r : N u t r i e n t H o l d i n g s , L L C S S C-TM C-TM C-TMC-TM C-TM C-TM C-GEX C-GEX M-ERH M-ERH M-ERH M- E R H M- E R H GR E E N H O U S E HE A D H O U S E C-TM C-TMC-TM C-TMM-ERH M-ERH M-ERH Project Number: A2 1/4" = 1'-0" AB MEK 1/7/2025 22-11 EXTERIOR ELEVATIONS SHEET DESCRIPTION: Scale: Date: Drawn By: Checked By: Re v i s i o n S c h e d u l e No . De s c r i p t i o n Da t e STAMP 91 1 5 H W Y 3 3 5 , N E W C A S T L E , C O . 8 1 6 4 7 Pr o j e c t F o r : N u t r i e n t H o l d i n g s , L L C GR E E N H O U S E HE A D H O U S E Project Number: A3 AS SHOWN AB MEK 1/7/2025 22-11 WALL SECTIONS SHEET DESCRIPTION: Scale: Date: Drawn By: Checked By: Re v i s i o n S c h e d u l e No . De s c r i p t i o n Da t e STAMP 91 1 5 H W Y 3 3 5 , N E W C A S T L E , C O . 8 1 6 4 7 Pr o j e c t F o r : N u t r i e n t H o l d i n g s , L L C 2 - TYPICAL ADA DETAIL REFERENCES ABBREVIATIONS GR E E N H O U S E HE A D H O U S E H/P ELECTRICAL LEGEND (NOT ALL SYMBOLS REQUIRED FOR THIS PROJECT) WALL MOUNTED LIGHT FIXTURE SURFACE FLUOR. LIGHT FIXTURE Aa FIXTURE DESIGNATIONS: LOWER CASE - SWITCH DESIGNATION FLUORESCENT STRIP FIXTURE WALL WASHER POLE-MOUNTED FIXTURE POST (BOLLARD) FIXTURE EMERGENCY BATTERY LIGHTS DUPLEX RECEPTACLE @ 18" UNLESS NOTED SPECIAL OUTLET AS NOTED FLUSH FLOOR DUPLEX RECEPTACLE DUPLEX RECEPTACLE HALF-SWITCHED @ 18" UNLESS NOTED TELE-POWER POLE JUNCTION BOX IN FLOOR, CEILING OR IN WALL MULTI-OUTLET PLUG STRIP JJ CIRCUIT HOMERUN CONDUIT RUN BELOW FLOOR OR GRADE LIGHT SWITCH AT 48" UNLESS NOTED 2 = 2-POLE SWITCH 3 = 3-WAY SWITCH K = KEY-OPERATED SWITCH P = SWITCH WITH PILOT LIGHT MAGNETIC MOTOR STARTER DISCONNECT SWITCH SWITCHBOARD, MOTOR CONTROL CENTER OR DISTRIBUTION BOARD GROUND PHOTOELECTRIC CELL THERMOSTAT AT 60" UNLESS NOTED CIRCUIT BREAKER MOTOR OUTLET FOOD SERVICE EQUIPMENT T PC M ATS ABBREVIATIONS AC AFF - ABOVE FINISHED FLOOR - ABOVE FINISHED GRADE - ALUMINUM - DESIGNATIONDESIG. EM EWC GND - GROUND FAULT INTERRUPTER - NOT FUSED NIC - NOT IN CONTRACT - NIGHT LIGHT - NOT TO SCALE - UNDERGROUND WP XFMR +18" OF DEVICE AFF OR AFG FIRE ALARM SYSTEM FIRE ALARM ANNUNCIATOR PANEL COMBINATION HORN/STROBE OR SPEAKER/STROBE H I PHOTOELECTRIC SMOKE DETECTOR DUCT DETECTORR SPRINKLER SYSTEM FLOW SWITCH STROBE SMOKE/FIRE DAMPER CONNECTION REMOTE INDICATOR LIGHT COMMUNICATION SYSTEM SPEAKER IN CEILING OR WALL VOLUME CONTROL AT 60" UNLESS NOTED MICROPHONE OUTLET IN FLOOR BOX OR WALLM CALL-IN SWITCH PROGRAM BELL INTERCOM CLOCK I S S B A AMPLIFIER TELEVISION OUTLET CONTACT DOOR SWITCH IN JAMB OR HINGEDC INTRUSION MOTION DETECTOR AS SPECIFIED, CORRIDOR/ROOMP C OR R K DISTRIBUTION EQUIPMENT SYMBOLS DISCONNECT SWITCH CIRCUIT BREAKER TRANSFORMER METER - COPPER EMP STEP LIGHT POP-UP RECEPTACLE HEAT/PHOTOELECTRIC SMOKE DETECTOR RECESSED OR SURFACE DOWNLIGHT RECESSED FLUOR. LIGHT FIXTURE Aa UPPER CASE - FIXTURE TYPE SHADING ON FIXTURE INDICATES EMERG. BATTERY BACKUP TRACK LIGHT AS NOTED OR SCHEDULED CEILING OR WALL MOUNTED EXIT LIGHT DOUBLE DUPLEX RECEPTACLE @ 18" UNLESS NOTED J COMPUTER/TELEPHONE OUTLET IN FLOOR OR WALL CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING TELEPHONE BACKBOARD CONDUIT STUB-UP - CAP & MARK SUBSCRIPTS: 4 = 4-WAY SWITCH TO = THERMAL OVERLOAD SWITCH DIMMER SWITCH W/ WATTAGE PANELBOARD OR LOAD CENTER, FLUSH OR SURFACE MOUNTED TRANSFORMER PUSHBUTTON CONTROL STATION TIME SWITCH DIVISION 15 EQUIPMENT AUTOMATIC TRANSFER SWITCH D TS T - ABOVE COUNTER AFG AL - EMERGENCY - ELECTRIC WATER COOLER - GROUND GFI NF NL NTS UG - WEATHER PROOF - TRANSFORMER - MOUNTING HEIGHT TO CENTERLINE FIRE ALARM CONTROL PANEL ANN FIRE ALARM PULL STATION ALARM HORN OR SPEAKER THERMAL HEAT DETECTOR SMOKE/IONIZATION DETECTOR P S SPRINKLER SYSTEM TAMPER SWITCH F D M C V SECURITY SYSTEM KEY-OPERATED ACCESS SWITCH SURVEILLANCE CAMERA FUSES CURRENT TRANSFORMER M CU - ENERGY MANAGEMENT PANEL FACP M = MOTION-OPERATED SWITCH equipment, etc. furnish by mechanical - refer to both electrical and and mechanical drawing for scope and work and additinal infor- Fire alarm system will be by others. Coordinate connections to the exit signs and lamps as specified and as shown on drawings. Complete branch circuit wiring required for the connection of Complete feeder(s) installation as required for new and/or including new panelboards, new conduits, new wires, new wiring Complete wiring system for new lighting and power as shown, as indicated on drawing and as specified, as necessary to complete the 2. 4. 6. Provide grounding and bonding Facilities. hood & duct detection ELECTRICAL SPECIFICATIONS drawings. and power system. b. items: Contractor shall submit shop drawings for engineer review and approval. insulation, sized per NEC Table 310.15(B)(16) stranded in sizes #8 and larger, solid in sizes #10 and smaller. Wiring shall be #12, stranded min. than #1, use THW or XHHW. Use type THHN for wires entering or passing Lighting fixtures. Shop drawing submittal shall include: through fluorescent lighting fixtures. B. 13. A. B. to start of any work. Test of entire system and work. REGULATIONS AND CODES: CONTRACT SHALL BE COMPATIBLE FOR SAID ALARM EQUIPMENT USED AT THE SITE, AND BE BOTH CFM AND U.L. LISTED FOR SAME. CONTRACTOR SHALL SUBMIT UNIT PRICES ON F.A. EQUIPMENT AND DEVICES FIRE ALARM LIFE SAFETY DRAWING TO THE AUTHORITY HAVING JURISDICTION FOR REVIEW AND APPROVAL. DRAWINGS HAVE BEEN DEVELOPED FOR BIDDING AND PRICING PURPOSES 4. WHEN PERMITTED BY THE AUTHORITY HAVING JURISDICTION, COORDINATE WITH engineer. Cabling shall be in the wall, above the ceiling or where exposed, Care must be taken to ensure cables are not kinked, bent beyond limit, length of the run. Splices and bridge taps with cabling are strictly prohibited. Cabling shall be free from tension at both ends, as well as through out the I. All wiring shall be protected from moving mechanical or physical contacts. cable runs exceeding 90 meters and provide solution to meet the 90 meter the case of "hard" drywall ceilings, adequate support shall be accomplished G. All cable above the ceiling must be tied and properly supported with F. Provide plenum rated cable when required by article NEC 300-22. fluorescent fixtures or heat generating devices. Wiring is to be run in cable tray and conduit where specified. requirement. where reasonably possible. patch panel location, and each wall/floor faceplate that has wiring installed. jacks, match faceplates to power, color coded for voice and data, match to C. The terminations at the station locations must be Category 6, T568B (AT&T) B. Data cable will be colored blue. Voice cable will be colored white. 500 Mhz or better category 6, 4 pair UTP as applicable. Acceptable D. Wall mounted patch panels will be provided. cable. Outlets will be securely held in place. B. Cat 6 Wiring Requirements 6. C. Fire Life Safety Scope of Work & General Conditions PROVIDE PLENUM RATED CABLE WHEN REQUIRED BY ARTICLE NEC 300-22. required by NEC. SUPPORT A. Provide GFI type receptacles at kitchens, bathrooms, garages, exterior etc. as required by code. E.electrical apparatus as shown on single line diagram and Complete connection of HVAC/Plumbing motor(s), water heater(s), Complete provision, installation and connection of lighting fixtures, emergency lighting and exit signs to existing emergency stand devices, new control devices, etc. for a complete lighting and contract. Electrical work shall include, but not limited to, these major SCOPE: Furnish all materials and labor required to execute this work 3. 5. Complete all electrical demolition as required. mation. A. 1. by power system. a. A. CONDUCTOR SIZES AND TYPES: Use only copper wire, 600 volt In sizes #1 and smaller, use types TW, THHN or THW. In sizes larger MC cable permitted per local codes. Panelboard(s). CONDUIT AND WIRE: 2. 1. and contractor shall have written approvals from building owner prior Core drilling and patching of existing building structure required for Operating, Maintenance and identification instructions manuals, if electrical work. Core drilling shall follow Building Standard procedures PERMITS AND FEES: Obtain and pay for all necessary permits, inspec- tions, examinations and fees or charges necessary for execution and and to the requirements of Federal, State or other City agencies Conform to the prevailing edition and amendments thereto of the SHOP DRAWINGS AND SUBMITTAL: having jurisdiction. completion of electrical work. 12. 11. A. 7. 9. 8. 10. any. THE NEW FIRE LIFE SAFETY EQUIPMENT REQUIRED FOR THIS CONTRACT SHALL BE BY THE SAME MANUFACTURER. ALL FIRE LIFE SAFETY SYSTEM COMPONENT, EQUIPMENT, DEVICES, ETC. LESS WIRING PROVIDED IN THIS PRIOR TO BID, CONTRACTOR SHALL VERIFY NEW FIRE LIFE SAFETY INSTALLATION AND INCLUDE ALL LABOR AND MATERIAL REQUIRED FOR A COMPLETE AND OPERABLE LIFE SAFETY AND SMOKE CONTROL SUPPLY & INSTALL NEW EQUIPMENT AND MODIFICATIONS TO EXISTING FIRE ALARM PROVIDE ALL COSTS FOR LABOR, DESIGN, ENGINEERING, SYSTEM TO PROVIDE A COMPLETE FIRE ALARM SYSTEM TO MEET LOCAL CODES. ALL NEW FIRE ALARM EQUIPMENT, DEVICES, WIRING, ETC. REQUIRED AND WHICH ARE INSTALLED FOR THE FACILITY SHALL MEET LATEST EDITION OF THE NFPA FIRE LIFE SAFETY CODES AND SHALL MEET ALL CITY AND STATE FIRE MARSHALL REQUIREMENTS. THE FIRE ALARM SYSTEM SCOPE OF WORK SHALL INCLUDE, BUT NOT NECESSARILY BE LIMITED TO THE FOLLOWING: CALCULATIONS, SHOP DRAWING, ETC. INCLUDING SUBMISSION OF FINAL PROVIDE ALL COSTS FOR LABOR, MATERIAL, INSTALLATION, CONNECTION AND EXECUTION OF FIRE LIFE SAFETY ALARM EQUIPMENT, DEVICES, CONDUIT/WIRING SYSTEM, ETC. AS REQUIRED DUE TO THE CONSTRUCTION OF THIS FACILITY. IN THEIR BID. SYSTEM(S). 3. 2. B. A. 1. ALARM DEVICE LOCATIONS & QUANTITIES PRIOR TO FINAL ROUGHIN. WITH THE AUTHORITY HAVING JURISDICTION TO DETERMINE FINAL FIRE AND ARE DIAGRAMMATIC ONLY. THE CONTRACTOR SHALL WALK THROUGH PAINTER TO FINISH THE CEILING MOUNTED SMOKE DETECTORS TO MATCH RESPECTIVE CEILINGS. REFER TO MANUFACTURER'S INSTRUCTIONS REGARDING ADDITIONAL FINISHES TO THE SPECIFIC PRODUCT. 5. N. All cabling shall be bundled and properly secured and terminated. warranty period shall begin at the point of system acceptance or beneficial system during this warranty period at no additional cost to the owner. The free of defects of workmanship or products and will inspect and repair the from the date of project completion. The contractor warrants the system to be O. The warranty set forth for this system shall consist of a full three (3) years use, whichever comes later. Coordinate numbering scheme with owner. enclosed within cable trays, raceways or conduit, as specified. M. No exposed wiring will be accepted unless approved in writing by the including NEC, EIA/TIA 568,569 and 606, and federal, state and local codes. familiar and install in accordance with all applicable codes and standards, L. All cable hangers shall be no more than 48" apart. Contractor shall be Cables are to be kept a minimum of 6" from power lines, electric motors, K. Cable bends shall be no less than eight times the cable diameter or 1.00". termination. No more than .5 inches of exposed untwisted pairs shall be the extent in which each twisted pair is unraveled at the point of its physical J. All connections of twisted wiring shall be made in such a way as to minimize H. Route cables so as not to exceed 90 meters in length. Bidder will identify any independent hangers. Cable "draped" across ceiling tiles is unacceptable. In overloaded, over-cinched, crushed, improperly untwisted, etc. present at these locations. E. All cables will be labeled with self-laminating labels at each cable end, at each modular RJ-45, 8 pin, 8 conductor, Hubbell, Leviton, or lucent or equivalent manufacturers include: Berk-Tek, Belden, Lucent or equivalent. A. The cabling for voice and data must be continuous, home run, non-spliced, A. General Requirements 14. decora style. Finish per owner or architect. Convenience receptacles will be 20 amp, commercial grade Light switches will be 20 amp, commercial grade,B. ELECTRICAL DEVICES A. decora style. Finish per owner or architect. Provide decora style, finish per owner or architect. Dimming switches will be a minimum of 600w or as noted.C. 15. Support all electrical equipment independent of accessible ceilings as All mounting heights will conform to ADA guidelines. Typical receptacleD. heights will be +18"AFF and switch heights will be +46"AFF unless noted otherwise. 16. At fire rated wall space electrical boxes at opposite sides of the wall no less than 24" horizontal distance. ELECTRICAL BOXES A. When phone, TV & power receptacles are shown on plan next to each other. Locate respective receptacles next to each other on site with no more B. than 1" seperating cover plates. ACCEPTABLE FIRE ALARM SYSTEM MANUFACTURERS ARE SIMPLEX, NOTIFIER, SILENT KNIGHT & FIRELITE. FIRE ALARM SYSTEMS MUST HAVE PARTS AND SERVICE AVAILABLE WITHIN 24 HOURS. 7. 8. Drawing Index SHEET DESCRIPTION E-001 ELECTRICAL SPECIFICATIONS, LEGEND & DRAWING INDEX E-101 ELECTRICAL PLANS E-601 POWER DISTRIBUTION RISER DIAGRAM AND SCHEDULES H/P ELECTRICAL LEGEND (NOT ALL SYMBOLS REQUIRED FOR THIS PROJECT) WALL MOUNTED LIGHT FIXTURE SURFACE FLUOR. LIGHT FIXTURE Aa FIXTURE DESIGNATIONS: LOWER CASE - SWITCH DESIGNATION FLUORESCENT STRIP FIXTURE WALL WASHER POLE-MOUNTED FIXTURE POST (BOLLARD) FIXTURE EMERGENCY BATTERY LIGHTS DUPLEX RECEPTACLE @ 18" UNLESS NOTED SPECIAL OUTLET AS NOTED FLUSH FLOOR DUPLEX RECEPTACLE DUPLEX RECEPTACLE HALF-SWITCHED @ 18" UNLESS NOTED TELE-POWER POLE JUNCTION BOX IN FLOOR, CEILING OR IN WALL MULTI-OUTLET PLUG STRIP JJ CIRCUIT HOMERUN CONDUIT RUN BELOW FLOOR OR GRADE LIGHT SWITCH AT 48" UNLESS NOTED 2 = 2-POLE SWITCH 3 = 3-WAY SWITCH K = KEY-OPERATED SWITCH P = SWITCH WITH PILOT LIGHT MAGNETIC MOTOR STARTER DISCONNECT SWITCH SWITCHBOARD, MOTOR CONTROL CENTER OR DISTRIBUTION BOARD GROUND PHOTOELECTRIC CELL THERMOSTAT AT 60" UNLESS NOTED CIRCUIT BREAKER MOTOR OUTLET FOOD SERVICE EQUIPMENT T PC M ATS ABBREVIATIONS AC AFF - ABOVE FINISHED FLOOR - ABOVE FINISHED GRADE - ALUMINUM - DESIGNATIONDESIG. EM EWC GND - GROUND FAULT INTERRUPTER - NOT FUSED NIC - NOT IN CONTRACT - NIGHT LIGHT - NOT TO SCALE - UNDERGROUND WP XFMR +18" OF DEVICE AFF OR AFG FIRE ALARM SYSTEM FIRE ALARM ANNUNCIATOR PANEL COMBINATION HORN/STROBE OR SPEAKER/STROBE H I PHOTOELECTRIC SMOKE DETECTOR DUCT DETECTORR SPRINKLER SYSTEM FLOW SWITCH STROBE SMOKE/FIRE DAMPER CONNECTION REMOTE INDICATOR LIGHT COMMUNICATION SYSTEM SPEAKER IN CEILING OR WALL VOLUME CONTROL AT 60" UNLESS NOTED MICROPHONE OUTLET IN FLOOR BOX OR WALLM CALL-IN SWITCH PROGRAM BELL INTERCOM CLOCK I S S B A AMPLIFIER TELEVISION OUTLET CONTACT DOOR SWITCH IN JAMB OR HINGEDC INTRUSION MOTION DETECTOR AS SPECIFIED, CORRIDOR/ROOMP C OR R K DISTRIBUTION EQUIPMENT SYMBOLS DISCONNECT SWITCH CIRCUIT BREAKER TRANSFORMER METER - COPPER EMP STEP LIGHT POP-UP RECEPTACLE HEAT/PHOTOELECTRIC SMOKE DETECTOR RECESSED OR SURFACE DOWNLIGHT RECESSED FLUOR. LIGHT FIXTURE Aa UPPER CASE - FIXTURE TYPE SHADING ON FIXTURE INDICATES EMERG. BATTERY BACKUP TRACK LIGHT AS NOTED OR SCHEDULED CEILING OR WALL MOUNTED EXIT LIGHT DOUBLE DUPLEX RECEPTACLE @ 18" UNLESS NOTED J COMPUTER/TELEPHONE OUTLET IN FLOOR OR WALL CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING TELEPHONE BACKBOARD CONDUIT STUB-UP - CAP & MARK SUBSCRIPTS: 4 = 4-WAY SWITCH TO = THERMAL OVERLOAD SWITCH DIMMER SWITCH W/ WATTAGE PANELBOARD OR LOAD CENTER, FLUSH OR SURFACE MOUNTED TRANSFORMER PUSHBUTTON CONTROL STATION TIME SWITCH DIVISION 15 EQUIPMENT AUTOMATIC TRANSFER SWITCH D TS T - ABOVE COUNTER AFG AL - EMERGENCY - ELECTRIC WATER COOLER - GROUND GFI NF NL NTS UG - WEATHER PROOF - TRANSFORMER - MOUNTING HEIGHT TO CENTERLINE FIRE ALARM CONTROL PANEL ANN FIRE ALARM PULL STATION ALARM HORN OR SPEAKER THERMAL HEAT DETECTOR SMOKE/IONIZATION DETECTOR P S SPRINKLER SYSTEM TAMPER SWITCH F D M C V SECURITY SYSTEM KEY-OPERATED ACCESS SWITCH SURVEILLANCE CAMERA FUSES CURRENT TRANSFORMER M CU - ENERGY MANAGEMENT PANEL FACP M = MOTION-OPERATED SWITCH equipment, etc. furnish by mechanical - refer to both electrical and and mechanical drawing for scope and work and additinal infor- Fire alarm system will be by others. Coordinate connections to the exit signs and lamps as specified and as shown on drawings. Complete branch circuit wiring required for the connection of Complete feeder(s) installation as required for new and/or including new panelboards, new conduits, new wires, new wiring Complete wiring system for new lighting and power as shown, as indicated on drawing and as specified, as necessary to complete the 2. 4. 6. Provide grounding and bonding Facilities. hood & duct detection ELECTRICAL SPECIFICATIONS drawings. and power system. b. items: Contractor shall submit shop drawings for engineer review and approval. insulation, sized per NEC Table 310.15(B)(16) stranded in sizes #8 and larger, solid in sizes #10 and smaller. Wiring shall be #12, stranded min. than #1, use THW or XHHW. Use type THHN for wires entering or passing Lighting fixtures. Shop drawing submittal shall include: through fluorescent lighting fixtures. B. 13. A. B. to start of any work. Test of entire system and work. REGULATIONS AND CODES: CONTRACT SHALL BE COMPATIBLE FOR SAID ALARM EQUIPMENT USED AT THE SITE, AND BE BOTH CFM AND U.L. LISTED FOR SAME. CONTRACTOR SHALL SUBMIT UNIT PRICES ON F.A. EQUIPMENT AND DEVICES FIRE ALARM LIFE SAFETY DRAWING TO THE AUTHORITY HAVING JURISDICTION FOR REVIEW AND APPROVAL. DRAWINGS HAVE BEEN DEVELOPED FOR BIDDING AND PRICING PURPOSES 4. WHEN PERMITTED BY THE AUTHORITY HAVING JURISDICTION, COORDINATE WITH engineer. Cabling shall be in the wall, above the ceiling or where exposed, Care must be taken to ensure cables are not kinked, bent beyond limit, length of the run. Splices and bridge taps with cabling are strictly prohibited. Cabling shall be free from tension at both ends, as well as through out the I. All wiring shall be protected from moving mechanical or physical contacts. cable runs exceeding 90 meters and provide solution to meet the 90 meter the case of "hard" drywall ceilings, adequate support shall be accomplished G. All cable above the ceiling must be tied and properly supported with F. Provide plenum rated cable when required by article NEC 300-22. fluorescent fixtures or heat generating devices. Wiring is to be run in cable tray and conduit where specified. requirement. where reasonably possible. patch panel location, and each wall/floor faceplate that has wiring installed. jacks, match faceplates to power, color coded for voice and data, match to C. The terminations at the station locations must be Category 6, T568B (AT&T) B. Data cable will be colored blue. Voice cable will be colored white. 500 Mhz or better category 6, 4 pair UTP as applicable. Acceptable D. Wall mounted patch panels will be provided. cable. Outlets will be securely held in place. B. Cat 6 Wiring Requirements 6. C. Fire Life Safety Scope of Work & General Conditions PROVIDE PLENUM RATED CABLE WHEN REQUIRED BY ARTICLE NEC 300-22. required by NEC. SUPPORT A. Provide GFI type receptacles at kitchens, bathrooms, garages, exterior etc. as required by code. E.electrical apparatus as shown on single line diagram and Complete connection of HVAC/Plumbing motor(s), water heater(s), Complete provision, installation and connection of lighting fixtures, emergency lighting and exit signs to existing emergency stand devices, new control devices, etc. for a complete lighting and contract. Electrical work shall include, but not limited to, these major SCOPE: Furnish all materials and labor required to execute this work 3. 5. Complete all electrical demolition as required. mation. A. 1. by power system. a. A. CONDUCTOR SIZES AND TYPES: Use only copper wire, 600 volt In sizes #1 and smaller, use types TW, THHN or THW. In sizes larger MC cable permitted per local codes. Panelboard(s). CONDUIT AND WIRE: 2. 1. and contractor shall have written approvals from building owner prior Core drilling and patching of existing building structure required for Operating, Maintenance and identification instructions manuals, if electrical work. Core drilling shall follow Building Standard procedures Applicable codes: National Electric Code (2018) PERMITS AND FEES: Obtain and pay for all necessary permits, inspec- tions, examinations and fees or charges necessary for execution and and to the requirements of Federal, State or other City agencies Garfield County Electrical Code, pertinent NFPA publications Conform to the prevailing edition and amendments thereto of the SHOP DRAWINGS AND SUBMITTAL: having jurisdiction. completion of electrical work. 12. 11. A. 7. 9. 8. 10. any. THE NEW FIRE LIFE SAFETY EQUIPMENT REQUIRED FOR THIS CONTRACT SHALL BE BY THE SAME MANUFACTURER. ALL FIRE LIFE SAFETY SYSTEM COMPONENT, EQUIPMENT, DEVICES, ETC. LESS WIRING PROVIDED IN THIS PRIOR TO BID, CONTRACTOR SHALL VERIFY NEW FIRE LIFE SAFETY INSTALLATION AND INCLUDE ALL LABOR AND MATERIAL REQUIRED FOR A COMPLETE AND OPERABLE LIFE SAFETY AND SMOKE CONTROL SUPPLY & INSTALL NEW EQUIPMENT AND MODIFICATIONS TO EXISTING FIRE ALARM PROVIDE ALL COSTS FOR LABOR, DESIGN, ENGINEERING, SYSTEM TO PROVIDE A COMPLETE FIRE ALARM SYSTEM TO MEET LOCAL CODES. ALL NEW FIRE ALARM EQUIPMENT, DEVICES, WIRING, ETC. REQUIRED AND WHICH ARE INSTALLED FOR THE FACILITY SHALL MEET LATEST EDITION OF THE NFPA FIRE LIFE SAFETY CODES AND SHALL MEET ALL CITY AND STATE FIRE MARSHALL REQUIREMENTS. THE FIRE ALARM SYSTEM SCOPE OF WORK SHALL INCLUDE, BUT NOT NECESSARILY BE LIMITED TO THE FOLLOWING: CALCULATIONS, SHOP DRAWING, ETC. INCLUDING SUBMISSION OF FINAL PROVIDE ALL COSTS FOR LABOR, MATERIAL, INSTALLATION, CONNECTION AND EXECUTION OF FIRE LIFE SAFETY ALARM EQUIPMENT, DEVICES, CONDUIT/WIRING SYSTEM, ETC. AS REQUIRED DUE TO THE CONSTRUCTION OF THIS FACILITY. IN THEIR BID. SYSTEM(S). 3. 2. B. A. 1. ALARM DEVICE LOCATIONS & QUANTITIES PRIOR TO FINAL ROUGHIN. WITH THE AUTHORITY HAVING JURISDICTION TO DETERMINE FINAL FIRE AND ARE DIAGRAMMATIC ONLY. THE CONTRACTOR SHALL WALK THROUGH PAINTER TO FINISH THE CEILING MOUNTED SMOKE DETECTORS TO MATCH RESPECTIVE CEILINGS. REFER TO MANUFACTURER'S INSTRUCTIONS REGARDING ADDITIONAL FINISHES TO THE SPECIFIC PRODUCT. 5. N. All cabling shall be bundled and properly secured and terminated. warranty period shall begin at the point of system acceptance or beneficial system during this warranty period at no additional cost to the owner. The free of defects of workmanship or products and will inspect and repair the from the date of project completion. The contractor warrants the system to be O. The warranty set forth for this system shall consist of a full three (3) years use, whichever comes later. Coordinate numbering scheme with owner. enclosed within cable trays, raceways or conduit, as specified. M. No exposed wiring will be accepted unless approved in writing by the including NEC, EIA/TIA 568,569 and 606, and federal, state and local codes. familiar and install in accordance with all applicable codes and standards, L. All cable hangers shall be no more than 48" apart. Contractor shall be Cables are to be kept a minimum of 6" from power lines, electric motors, K. Cable bends shall be no less than eight times the cable diameter or 1.00". termination. No more than .5 inches of exposed untwisted pairs shall be the extent in which each twisted pair is unraveled at the point of its physical J. All connections of twisted wiring shall be made in such a way as to minimize H. Route cables so as not to exceed 90 meters in length. Bidder will identify any independent hangers. Cable "draped" across ceiling tiles is unacceptable. In overloaded, over-cinched, crushed, improperly untwisted, etc. present at these locations. E. All cables will be labeled with self-laminating labels at each cable end, at each modular RJ-45, 8 pin, 8 conductor, Hubbell, Leviton, or lucent or equivalent manufacturers include: Berk-Tek, Belden, Lucent or equivalent. A. The cabling for voice and data must be continuous, home run, non-spliced, A. General Requirements 14. decora style. Finish per owner or architect. Convenience receptacles will be 20 amp, commercial grade Light switches will be 20 amp, commercial grade,B. ELECTRICAL DEVICES A. decora style. Finish per owner or architect. Provide decora style, finish per owner or architect. Dimming switches will be a minimum of 600w or as noted.C. 15. Support all electrical equipment independent of accessible ceilings as All mounting heights will conform to ADA guidelines. Typical receptacleD. heights will be +18"AFF and switch heights will be +46"AFF unless noted otherwise. 16. At fire rated wall space electrical boxes at opposite sides of the wall no less than 24" horizontal distance. ELECTRICAL BOXES A. When phone, TV & power receptacles are shown on plan next to each other. Locate respective receptacles next to each other on site with no more B. than 1" seperating cover plates. ACCEPTABLE FIRE ALARM SYSTEM MANUFACTURERS ARE SIMPLEX, NOTIFIER, SILENT KNIGHT & FIRELITE. FIRE ALARM SYSTEMS MUST HAVE PARTS AND SERVICE AVAILABLE WITHIN 24 HOURS. 7. 8. E-001 Electrical Specifications Drawing Index Design Criteria & Legend DATEMARK DESCRIPTION SHEET TITLE OF 3 CHK'D BY: DRAWN BY: PROJECT NUMBER: Nu t r i e n t F a r m s G r e e n h o u s e H e a d h o u s e 33 3 N u t r i e n t F a r m s R o a d Ne w C a s t l e , C O 8 1 6 4 7 mh BE 240402-01 SEAL SD 08/05/24 SCHEMATIC DESIGN PO BOX 5774 783 Second Street EAGLE, CO 81631 970.390.7673 www.bremaengr.com DD 08/26/24 PERMIT DOCUMENTS CD 12/04/24 PERMIT DOCUMENTS2 CD 12/12/24 PERMIT DOCUMENTS3 CD 01/07/25 PERMIT DOCUMENTS4 Electrical Plan 1/4" = 1'-0"NORTH ERV 1 XF SWITCH MAIN DISC PANEL MDP CT-METER wp/gfic wp/gficwp/gficwp/gfic wp/gfic gfic gfic gficgficgfic PANEL A SP 1 UH 1 UH 10thru M-ERHM-ERHM-ERH C-TM C-TMC-TM C-TM B 1 P 1 ET 1 P 2 WH 1 P 3 P 4 P 5 P 6-12 B 2EF 1 FC 1 FC 2 E-101 Electrical l Plan DATEMARK DESCRIPTION SHEET TITLE OF 3 CHK'D BY: DRAWN BY: PROJECT NUMBER: Nu t r i e n t F a r m s G r e e n h o u s e H e a d h o u s e 33 3 N u t r i e n t F a r m s R o a d Ne w C a s t l e , C O 8 1 6 4 7 mh BE 240402-01 SEAL SD 08/05/24 SCHEMATIC DESIGN PO BOX 5774 783 Second Street EAGLE, CO 81631 970.390.7673 www.bremaengr.com DD 08/26/24 PERMIT DOCUMENTS CD 12/04/24 PERMIT DOCUMENTS2 CD 12/12/24 PERMIT DOCUMENTS3 CD 01/07/25 PERMIT DOCUMENTS4 M UTILITY XMFR 120 / 240 3Ø 4W 1000A 3P SWITCHBOARD "MDA" FOOD TRUCK FUTURE RES PANEL APANEL GP Electrical Power Distribution Riser Diagram NO SCALE 400A 3P (2)4#250M (3)CM 1#6AWG G. IN 4" C PANEL GP2 2#6 ,AWG, 1#6 AWG G. IN 1" C 60A 2P XFER 208-277/480 100A 2P 200A 2P TRANSFER SWITCH GEN-SET CT/METER 1000A FOOD TRUCK 100A 2P 100A 2P 100A 3P 100A 3P 200A 3P 1000A 3P 1000A 3P 1000A 3#1/0 AWG 1#6AWG G. IN 2" C (4)-4#250MCM 1#6AWG G. IN 4" C (4)-4#250MCM 1#6AWG G. IN 4" C (4)-4#250MCM 1#6AWG G. IN 4" C 3#1/0 AWG 1#6AWG G. IN 2" C 3#1/0 AWG 1#6AWG G. IN 2" C GROUND PER NEC E-601 Electrical Riser Diagram and Schedules DATEMARK DESCRIPTION SHEET TITLE OF 3 CHK'D BY: DRAWN BY: PROJECT NUMBER: Nu t r i e n t F a r m s G r e e n h o u s e H e a d h o u s e 33 3 N u t r i e n t F a r m s R o a d Ne w C a s t l e , C O 8 1 6 4 7 mh BE 240402-01 SEAL SD 08/05/24 SCHEMATIC DESIGN PO BOX 5774 783 Second Street EAGLE, CO 81631 970.390.7673 www.bremaengr.com DD 08/26/24 PERMIT DOCUMENTS CD 12/04/24 PERMIT DOCUMENTS2 CD 12/12/24 PERMIT DOCUMENTS3 CD 01/07/25 PERMIT DOCUMENTS4 T DOMESTIC HOT WATER PIPE UP CW PIPE DOWN VENT NEW ABOVE CEILING OR BELOW GRADE PIPE END CAP POINT OF NEW CONNECTION EXISTING TRANSFER AIR OR GRILLE EXHAUST AIR OUTDOOR AIR INTAKE CUBIC FEET PER MINUTE OA EX (E) T CFM UP THROUGH ROOFUTR POWER SWITCH MOTOR OPERATED DAMPERMOD THERMOSTAT SUPPLY DUCT SECTION RETURN OR EXHAUST SECTION SUPPLY DUCT TURN DOWN RETURN/EXHAUST DUCT TURN DOWN SUPPLY CFM / NECK SIZENECK SIZE CFM-S NECK SIZE CFM-R NECK SIZE CFM-OA NECK SIZE CFM-EX U DOOR UNDERCUT CFM ROUND DUCT SECTION ROUND DUCT TURN DOWN Mechanical Legend RETURN CFM / NECK SIZE OUTSIDE AIR CFM / NECK SIZE EXHAUST CFM / NECK SIZE Mechanical Specifications General These drawings are intended to provide the general scope of work and materials of the project. Mechanical Contractor (MC) shall provide the management, labor, equipment and accoutrements for a safe, functioning and complete system. Tendering of a proposal shall be confirmation the contractor has made a thorough analysis of the job site, existing conditions and construction documents to deliver the described mechanical design and system. Change orders and modifications submitted by the contractor shall not be honored without the express written approval by the owner, architect, general contractor (GC or prime) and/or engineer of record. Codes and Standards Contractor to obtain all necessary testing results, certificates of permit and inspection(s). The heating, ventilating, and air conditioning systems shall be installed and tested in accordance with the following codes, standards and permitting requirements under the authority having jurisdiction. Where there are conflicts between the codes, the strictest interpretation shall apply. 1.Local ordinances as interpreted by the authority having jurisdiction in the Garfield County Building Department and the state of Colorado. 2.2015 International Mechanical Code (IMC). 3.2015 International Building Code (IBC). 4.2018 International Energy Conservation Code (IECC). 5.2015 International Fuel Gas Code (IFGC). 6.2015 International Plumbing Code (IPC). Warranty, Materials and Workmanship Manufacturer trade names and catalog numbers stated herein are intended to indicate the quality of equipment or materials desired. All manufacturers not specifically listed or scheduled require prior review before installation. All materials and equipment shall be of the highest quality and performance. If a modification to the specified equipment is desired, the contractor shall provide a written request to the engineer of record for review and six (6) copies of submittals describing make, model and all the necessary metrics for adequate review. The installation shall perform according to the code and design intent, and be free of any defects for a period of one year upon acceptance by the owner. Contractor shall have current licensing and necessary general and liability insurance, applicable to the jurisdiction of installation. All materials and equipment shall be installed in a neat and workmanlike manner by competent specialists of each trade to meet the described and specified standards and intent of the design. It is the responsibility of the contractor to verify the desired mechanical equipment and accoutrements meet any and all spatial constraints, working clearances, accessibility and the design intent of the project. Do not scale drawings - it is up to the contractor to verify all constraints in the field before completing any work. Coordinate the mechanical installation with engineer, architect, fire suppression, plumbing, electrical, civil, structural, interior and other applicable elements prior to installation. Contractor to complete all functional performance testing according to, but not limited to, and specified by the sequence of operations, backup modes, alarms, power on/off, economizer, sensor control, hydronic/airside test and balance, chemistry and manufacturer installation instructions. If testing procedure fails, fix and repeat the test at no additional cost to the owner. All areas requiring cutting and patching shall be coordinated with the owner, architect, project superintendent and/or general contractor. Locate any utilities prior to excavating. X-ray concrete walls and/or slabs prior to coring. Coordinate all roof and exterior wall penetrations with the appropriate trades. Any penetrations through a fire wall or partition shall maintain the integrity of the fire rating - verify fire rating with architect. Any material used to prevent fire or products of combustion from penetrating a fire wall or partition shall be UL listed and meet the minimum fire rating as prescribed by the architect. Any roof penetrations shall prevent any outdoor elements from entering the roof assembly and/or building. All equipment installed under this contract shall follow the respective manufacturer installation, maintenance and operation instructions. Provide adequate clearances and access panels for inspection, service, maintenance and the removal of equipment and accessories - not limited to appliances, control devices, heat exchangers, valves, actuators, compressors, burners, and blower assemblies. Provide at least a level 30” deep and wide working space in front of all these devices. Offset piping, ductwork and appurtenances as necessary to avoid beams, columns and structural members - get consent from a structural engineer before penetrating any structural member. Contractor to provide carbon monoxide detectors in any room with natural gas burning appliances. Provide detectors per local code and authority having jurisdiction. Cleanup The contractor shall leave the workspace and equipment in an orderly and unsoiled condition during and upon completion of work. Contractor is responsible for removing own debris, trash, and remaining material. Electrical Motors, starters, overloads, sensors, relays, solenoid valves, transformers and variable frequency drives shall be provided by MC unless otherwise indicated on plans. Electrical contractor to provide necessary high voltage wiring, disconnects, and conduit unless provided with the packaged mechanical equipment. Contractor to coordinate and verify all voltage and phase requirements to the specified motor and equipment with utility services, GC and EC. Provide phase loss protection and soft start motors. No equipment, materials, piping or ductwork shall be installed above or below electrical switchgear, electrical panels and within any elevator shaft unless approved for that application. Equipment Identification All ductwork, piping and equipment shall have a professional legible identification delineating make, model, flow direction, and the metrics necessary for service, maintenance and identification. Any painting or customization shall not inhibit reading the label. Provide duct, pipe and valve markers as necessary. Low Pressure Ductwork Low pressure ductwork shall comply and be fabricated according to current SMACNA Duct Construction Standards - Metal and Flexible, and chapter 6 of the IMC. Low pressure ducts shall be sized at 0.08” of water column loss per 100 feet lengths unless otherwise specified. Any rectangular ductwork with aspect ratios greater than a 3:1 shall have reinforcement, cross breaking or beading to limit deflection, sagging, bellowing, sound transmission, leakage and vibration. Drawing ductwork sizes represent the outside to outside dimensions and include allowance for any insulation. All ductwork transverse joints, seams and connections shall be sealed by UL 181B listed tapes, gaskets, liquid sealants or other approved closure system. Type I ducts shall be constructed of 16 gauge welded black steel. Provide cleanouts every 20' and at any change of direction - grease duct reservoirs shall be a minimum 12” wide and 1” deep. Clothes dryer ductwork shall be aluminum and not penetrated by screws and fasteners-provide cleanouts and access panels at all vertical risers, UL listed backdraft damper and termination without screening as required by code. Maximum ductwork length shall not exceed 35' where every elbow has an equivalent length of 5' or install per manufacturer recommendations. Dryer booster fans shall be UL 705 listed and installed per manufacturer installation instructions. Provide make-up air for any dryer exhaust volume over 200 cubic feet per minute. Where dryer ductwork leaves the room, contractor shall provide permanent wall mounted nameplate specifying the final duct length to termination, and the number of elbows. Provide means to prevent outdoor air flow leakage into building supply and exhausts upon equipment shutdown. All rectangular ductwork 90 degree changes of direction shall have single bladed turning vanes or be a long radius elbow. Provide UL listed and labeled fire and/or smoke dampers at any fire rated assembly. Verify fire ratings with architect and/or general contractor. Insulation shall not conceal access panels, fire dampers, fire damper operation and other openings into ductwork. Provide UL listed and labeled filters as required on return/intakes into air handling units. Fitting, grille, register, louver and termination pressure drops shall not exceed 0.10” water column loss unless otherwise specified. Ductwork, linings, insulation, vibration isolators and connectors installed outdoors or in locations where they may suffer damage shall be protected from the exposure elements. Underground ductwork shall be protected from corrosion and deterioration and be approved for underground installation or encased in a minimum of 2 inches of concrete. In air handlers with supply air of 2,000 to 18,000 cfm provide smoke detector in return air stream. Any air flow greater than 18,000 CFM shall also require a smoke sensor on the supply side of the blower. Ductwork and Plenum Insulation and Sealing Lining insulation shall not impede the operation of fire dampers. Insulation shall inhibit growth of bacteria, mold and fungus, and limit potential health hazards. All supply and return air ducts and plenums shall be insulated to a minimum of R6 where located in unconditioned spaces. Outside the building ducts shall be insulated to a minimum of R8. Outdoor insulation shall be protected from the elements with a UV and weather resistant barrier. Any supply or return duct within the envelope must be separated from the outdoors, unconditioned or exempt spaces by minimum R12 insulation. Exhaust and intake air ducts in conditioned areas that may condense shall be wrapped to R6 with a vapor barrier to prevent condensation. Supply and return rectangular ductwork shall be lined, and round ductwork shall be wrapped or sleeved for sound attenuation in areas of sensitivity. Plastic piping, wire sheath, duct insulation, coverings, linings and adhesives shall have a flame spread index not more than 25 and smoke-developed index not more than 50 and conform to ASTM E 84 or UL 723. Mechanical Hydronic Piping Pipe material, connectors, valves, fittings, expansion and vibration controls shall be approved and rated for the operating temperature and pressure of the hydronic system, and conform to the standards listed in Table 1202.4 of the IMC or an approved equivalent. Piping shall be sized for no more than 3.5' of head loss per 100 feet of pipe and a maximum velocity of 4 feet per second. Provide corrosion protection when joining piping of different materials. Where copper is utilized, any piping 2-1/2” and smaller shall be type “L” and soldered or brazed. Joining surfaces shall be cleaned, and fluxed prior to completing the joint. Any copper piping 3” or larger shall be silver soldered. Iron pipe shall be schedule 40 black steel flanged, grooved, pressed, flared, welded or by other approved means and material. Provide fluxes and solder compatible to material, and approved for application. Valves shall not have a Cv rating with a pressure loss greater than 1 psi. Provide isolation valves on both the supply and return side of any boiler, pressure vessel, heat exchanger, pump, and pressure reducing device. Above grade domestic water piping shall be drawn tube type “L” wrought copper and approved fittings. Domestic water piping and fittings shall comply with NSF 372 and shall have a weighted average lead content of lead of 0.25% or less. All domestic water valves shall be compatible with the installed piping and fittings and meet NSF 61 in all potable supply drinking water-this includes all ball, gate, butterfly, globe, plug, prv, backflow prevention, check and solenoid valves. Waste piping shall be cast iron only - no plastic waste piping will be acceptable unless under written approval by the engineer of record. Mechanical Pipe Insulation Pipe insulation shall be required on any heating and cooling piping and shall conform to section C403.2.10 and thickness and thermal conductivity in Table C403.2.1 of the IECC and 1204.1 of the IMC. Pipe insulation shall have a smoke developed length of 50 or less and a flame spread rating of 25 or less. Outdoor pipe insulation exposed to weather shall be protected from damage due to sunlight moisture, equipment maintenance, wind and shielded from solar radiation. Adhesive tapes shall not be permitted. Any underground piping shall be type K and insulated to the appropriate thickness to size and temperature and protected from corrosion and degradation with no fittings. Direction changes shall be accomplished with long radius elbows. Provide thermal expansion joints for piping lengths greater than 50.' Refrigerant Piping Refrigerant piping shall not: obstruct normal equipment operations, be located in any elevator, dumbwaiter or shaft that has openings into living quarters, or to means of egress. Refrigerant piping shall be Type ACR copper or an approved equivalent, conform to ASTM B 280, listed in chapter 11 of the IMC, assembled in accordance with ASTM B 88, and appropriate for the particular application. Brazing linesets shall be completed, while nitrogen is flowing in the refrigerant piping. Provide insulated linesets per manufacturer specifications and installation manuals. Provide accumulator and insulation per the IECC and IMC. On conventional refrigerant systems with a condenser, provide fan speed control and a sight glass upstream of TXV valve as close to evaporator as possible. On a compressor changeout, provide filter drier, pressure testing and lineset cleaning/flushing as necessary to remove all contamination and ensure integrity of linesets. MC shall be responsible for final refrigerant piping sizing, as per the equipment manufacturer installation and field sizing requirements. Refrigerant circuit access ports shall be fitted with locking type resistant caps or secured to prevent unauthorized access. Underground piping shall be sleeved and insulated per manufacturer recommendations. Linesets shall be cleaned, flushed and vacuum/pressure tested, holding the vacuum for at least four hours prior to releasing refrigerant into the piping and equipment - refrigerant lines shall be installed per manufacturer recommended procedures. All refrigerant piping shall be supported per ANSI requirements. If the condenser is installed 19' or more feet higher than the evaporator, oil traps shall be provided on the vapor suction line at every 10' of additional height gain. Utilize inverted traps where the condenser is lower than the evaporator. Traps shall be installed at the bottom of all vertical risers on refrigerant vapor suction lines. Horizontal suction lines shall be level or sloped back toward the compressor. Install refrigerant lines per manufacturer installation instructions and specifications. Natural Gas Piping Natural gas piping shall be schedule 40 black iron or galvanized and in accordance to NFPA 58, ASME B36.10, 10M, ASTM A53/A53M, and/or ASTM A106. Corrugated stainless steel tubing shall be listed in accordance with ANSI LC1/CSA 6.26. Black or wrought iron sizes up to 4” may be threaded. Any iron gas piping larger than 4” shall be welded. Gas piping shall be rated for the demand and pressure application, tested and hold pressure (at 1.5 times the working pressure but not less than 3psi) at least 24 hours, and be inspected by the authority having jurisdiction prior to meter connection. Pipe sizing has been determined for black iron use at 2psi with a 1psi pressure drop up to the sub-meters. Piping downstream of the sub-meters have been sized for 14” wc pressure with a 0.5 inch wc drop. Any other utilized piping materials and sizing methods shall be verified by the contractor to meet the listed demand and pressure drops with the engineer of record. Any gas piping that is underground must be rated for the application, protected from corrosion and physical damage. Contractor to install underground piping according to the specifications of the utility company. Any gas piping encased under buildings or in concrete shall be sleeved, and provided with access and protection from damage and corrosion. Gas service piping shall not penetrate building foundation walls at any point below grade. Any subgrade piping shall be located at least 12” below grade. Any exposed piping shall be protected from corrosion, structurally supported, and any penetration shall be sealed from the outdoors. Natural gas piping on roofs shall be elevated at least 3.5 inches. Contractor shall use anodeless risers and provide protection from physical damage upon routing out of the ground into the building unless black or galvanized steel is used indoors. Provide shield plates where piping has been routed in wall framing. Appliances shall be connected to the gas piping system with ANSI 121.75/CSA6.27 connectors. Contractor shall provide a shutoff valve within 6 feet of the appliance being served, and the floor. Gas relief piping and serving gas regulators to the outdoors shall be aluminum. Equipment, Drain Pans, Hangers and Supports Adequate structural support shall be provided and according to IMC requirements - vibration isolators, neoprene pads and insulation saddles shall be required to support any piping, equipment and ductwork from structure without noise propagation and damage to integrity and operation. Contractor to provide temporary heat, outdoor pads, drain pans, sensors, water detectors, alarms, drains and any other appurtenance necessary for a functional mechanical system. Where damage to any building components could occur as a result of overflow from the equipment condensate or drain removal system, provide either of the following four alternatives. Provide an auxiliary 1-1/2” deep drain pan three inches larger than the equipment and drain. Provide a separate overflow drain connected to the drain pan at a point higher than the primary drain, provided with the equipment. An auxiliary drain pan without a drain equipped with a water detection device conforming to UL 508 that will shut off equipment prior to overflow. Provide a water level detection device conforming to UL 508 that will shut off the equipment served in the event the primary drain is blocked. Air Intakes, Venting and Exhaust Contractor to provide venting and combustion air intake to the outdoors with manufacturer approved materials, and according to the appliance manufacturer installation instructions. Size, elbows and length shall be determined by manufacturer installation guidelines and/or engineer. Any variation in routing and sizing shall be approved by the engineer of record. Any heating water boiler application that utilizes manufacturer approved plastic PVC venting, shall use at least 10' of actual length of CPVC out of the boiler before continuing with PVC to the termination. Contractor to use only materials, glue and primer that is appropriate and compatible to match the piping material(s) and application(s). Intake openings shall be located at least 10' away from any property line or contaminant, or with at least 25' of vertical separation. Intakes shall be located not less than 3' below contaminant sources located within 10' of the source. Exhaust shall be discharged outdoors at a point where it will not cause a nuisance or reintroduce the exhaust air back into the building, and not directed onto walkways. For environmental exhaust, maintain at least 3' between any exhaust termination and openings into the building, and property lines. Maintain at least 10' between any mechanical intake and any environmental exhaust. Explosive or flammable vapor, fumes or dust exhaust shall be 30 feet from the property line, combustible walls, and operable openings into buildings which are in the direction of discharge; 10 feet from openings into the building; and 6 feet from exterior walls and roofs. Product conveying outlets shall be 10' away from property lines, operable openings and above grade. Product exhaust shall be at least 3 feet from exterior walls and roofs. Fireplace appliance vent terminations shall not be within 12” of any door swing - door stops and closers cannot be used to meet clearance requirements. Exhaust and outdoor air intake terminations shall be protected from the outdoors with corrosion, animal and weather resistant 1/4” to 1/2” screening. It is recommended to use 1/2” screening for exhaust terminations in heating dominant environments such as climate zones 6 and 7. Exhaust and outdoor air intake openings shall be at least 12” above grade or the highest snow level, and exhaust shall not be within 10 feet of any opening into any adjacent building. Heating and Chilled Water System Any hydronic closed system boiler, chiller and piping shall be filled with 30% propylene glycol and 70% water with inhibitors compatible to the equipment, heat exchanger(s) and piping materials-when all piping is within the conditioned envelope. Any outdoor hydronic closed system boiler, chiller and piping shall be filled with 50% propylene glycol and 50% water with sufficiently compatible inhibitors. Contractor to provide the appropriate freeze protection and corrosion inhibitor to match the service, installed working materials and maintain manufacturer recommended water chemistry balance. All new and retrofitted heating and chilled water systems shall be cleaned and flushed with 2-3% solution of tri-sodium phosphate and water, or manufacturer recommended cleaner, and flushed again with clean water prior to filling, and starting system. Verify cleaning, water, fill requirements and chemical balance with manufacturer. Contractor shall test a sample of the working fluid 8 weeks after the installation has been operating and adjust water chemistry as necessary to meet the manufacturer recommended working fluid quality. Contractor shall provide means to test water chemistry, balance water flow and fill requirements, wye strainer, expansion tank, dirt/magnetic separator, and air separator on all hydronic closed piping systems. Radiant In floor radiant tubing shall be a nominal 5/8” diameter cross linked polyethylene with an oxygen barrier manufactured under the Engle method. A minimum R10 insulation shall be installed under the heated slab extending horizontally from the exterior wall of the building envelope for 4 feet. Tubing loop lengths shall be equivalent as measured from the manifold. Manifolds shall have balancing valves. Air pressure test 25% above specified fill pressure before filling and contractor shall verify there are no leaks within system, before charging - if leaks are found, repair and repeat the process. Upon filling, contractor shall purge all piping, equipment, tubing and manifolds of all air - install air vents at high points as necessary to remove the air, in accessible locations. Snowmelt Snowmelt tubing shall be a nominal 3/4” diameter cross linked polyethylene with an oxygen barrier manufactured under the Engle method. Installed tubing shall be insulated below and at all sides by at least R10 insulation. Tubing loop lengths shall be equivalent as measured from the manifold. Manifolds shall have balancing valves and boiler drains for filling. Air pressure test 25% above specified fill pressure before filling and contractor shall verify no leaks within system before filling - if leaks are found, repair and repeat the process. Upon filling, contractor shall purge all piping, equipment, tubing and manifolds of all air - install air vents at high points as necessary to remove the air, in accessible locations. Snow and ice melting systems shall include controls capable of shutting off the system when the surface temperature is above 38 degrees Fahrenheit and no precipitation is falling and automatic or manual control that will allow shutoff when the outdoor temperature is above 38 degrees. Hydronic and Airside Balancing Any chemistry, water and airside flows shall be tested and recorded by a third party licensed laboratory or test and balance contractor under NEBB, AABC guidelines. Provide (6) copies of report to the mechanical engineer of record for review. Balance contractor to provide the necessary adjustments to motors, belts, sheaves, balancing valves, quadrants and pumps to meet the specified flow rates, within a 10% deviation. MC to provide all necessary fill, pressure and temperature ports, balancing valves, dampers, and other measuring access points and devices to complete the required balancing. Upon completion of any balance, valve/quadrant/damper position shall be visibly and permanently marked and labeled, and all final positions of all balancing cocks, valves, and operators shall be marked with a center punch. Boiler Safeties, NFPA 85, ASME, CSD-1, Outdoor Setback and Emergency Power Off Switch (EPO) & Colorado Boiler Inspection Any service and domestic type water heater of either instantaneous or storage type used for heating or combined heating and storage of hot water for domestic or sanitary purposes or for space heating where the heating input is greater than 200kBTU/hr, the potable water temperature exceeds 210 degrees Fahrenheit, or the nominal capacity of the vessel exceeds 120 gallons shall require an inspection by the Colorado State Boiler Inspector. Any boiler with more than 12.5 million BTU/hr input shall have two emergency exits, two EPO's, and abide by NFPA 85. A manually operated remote shutdown switch, an emergency power off switch, shall be installed at each boiler room entrance and conform to UL 353. This emergency switch or circuit breaker must disconnect all power to the burner controls per CSD-1 and CE-110(a) while pumping continues to run. A boiler that supplies heat to the building shall have an outdoor setback control algorithm to lower and raise the boiler supply water temperature based on increasing outdoor temperatures. Any commercial heating water boiler installation(s) shall adhere to all applicable operational safety requirements mandated by ASME CSD-1, IMC and local code amendments. When a full flow pumping and/or common pump(s) serving multiple boilers piping strategy is utilized, the boiler(s) shall be independently and minimally protected with a low water fuel cutoff control device. When an individually dedicated pump and boiler is hydronically separated from system loop and system pumping, under a forced flow or injection piping arrangement, the boiler shall be minimally protected by an independently controlled flow or temperature sensing device which shall terminate fuel and burner operation, and prevent overheating under an inadequate flow condition. Any forced flow potable water heaters require an EPO, and any domestic water heater shall employ a high limit fuel shutoff when water temperatures reach 210 degrees. All residential boilers require at least a low water fuel cutoff, flow sensing and/or temperature sensing device for boiler protection when overheating. Contractor will verify proposed boiler already employs this minimum safety strategy (low water fuel cutoff, flow or temperature sensing devices) or contractor shall provide it. This applies to any one to two single-family dwelling three stories or less, even if boiler input is less than 400kBTU/hr. Under a fuel cutoff scenario, pumping shall continue. Potable water heaters are exempt. ASME potable supply Water Heaters, Storage Tanks, Expansion Tanks and Hot Water Recirculation Systems Pressure relief valve (PRV) shall be installed vertically and according to manufacturer installation instructions. Any boiler heating system with PRV setting greater than 30psi shall require an ASME expansion tank. Any potable supply water heater with storage, storage tank and sidearm heated by steam or other indirect means when the heating input is greater than 200kBTU/hr, the potable water temperature exceeds 210degrees or the vessel contains more than 120 gallons shall be ASME constructed. Water heaters and storage tanks shall require a 1-1/2” deep and 2” equipment overlap where leakage may cause damage. Provide at least a 3/4” indirect drain line to nearest receptor and/or water leakage detection device. Where a storage water heater is supplied with cold water that passes through a check valve, pressure reducing valve or backflow preventer, a thermal expansion tank shall QUADRANT OR BALANCE DAMPER IN DUCT V CW HW S RETURN GRILLE OR EXHAUST SUPPLY GRILLE POUNDS PER SQUARE INCHPSI INCHES WATER COLUMN"WC FEET ABOVE SEA LEVEL'ASL SUPPLY AIR RETURN AIRR S CHILLED WATER RETURN CHILLED WATER SUPPLY HEATING WATER RETURN HEATING WATER SUPPLY MEDIUM PRESSURE NATURAL GAS - 2 PSI SNOWMELT RETURN GAS HWS HWR CWS CWR SMS SMR G MG SNOWMELT SUPPLY AQUASTAT PRESSURE - TEMP PORT PRESSURE REDUCING VALVE TWO WAY CONTROL VALVE WYE STRAINER CHECK VALVE THREE WAY CONTROL VALVE BALL VALVE THERMOMETER AIR VENT DIFFERENTIAL BYPASS VALVE PRESSURE RELIEF VALVE FLOW SWITCH PIPE UNION P FS A FOUR WAY CONTROL VALVE Design Criteria 39.5° NORTH, 107.5° WEST, 5619'ASL, CLIMATE ZONE 5B WINTER DESIGN TEMPERATURE / SETPOINT -5° / 70°F R19+R11LS=R30roof, R13+R7.5ci=R20.5wallabovegrade, R5belowheated slab & R15 to 36" thermal break, R2.4door, U0.38fixedwin, U0.45operablewin 2018 IECC + 2015 ICodes ENVELOPE: Qpeakheat = 36kBTU/hr Boiler AHRI Thermal Efficiency: 96.2% Qpeakhoth2o: 318 GPH @ 100° temperature increase be connected to the water heater cold water supply pipe downstream of these devices and upstream of the tank. Tank shall be sized in accordance with the manufacturer instructions and such that the pressure in the water distribution system shall not exceed 80 pounds per square inch or the setting of the ASSE 1003 PRV or CSA B356 PRV with strainer system, pressure relief setting and maximum allowable working pressure requirements of the served equipment. In a hot water recirculation system, circulation pumps and/or heat trace shall automatically turn off when there is no demand. Condensate Pumps, Drain Piping and Discharge Piping with a PRV Provide trapped and vented condensate piping to nearest waste line receptacle. Piping may be Type M hard drawn copper with soldered joints, schedule 40 PVC with solvent fused joints or other approved material. Where condensate discharge may be acidic from any boiler, furnace, makeup air unit, air handler, unit heater, or other, condensate shall be piped through a manufacturer approved neutralization kit and prevent downstream pipe corrosion, degradation and failure for all high efficiency equipment (greater than 90%). Discharge piping from a pressure relief valve shall terminate not more than 6” above or not less than twice the discharge pipe diameter above the drain receptor or flood rim level. Condensate drain lines shall be configured to permit the cleaning of blockages without being cut. Condensate pumps located in uninhabitable areas shall be interlocked to shut off equipment when pump fails. Thermostats Contractor to provide a seven day programmable thermostat as located on plan at 52” above the floor finish. The thermostat shall provide readings in Fahrenheit and have a range from at least 55 to 85 degrees. Thermostat shall have a deadband of at least five degrees and the capability of switching from heating to cooling automatically, not allow simultaneous heating and cooling, have setback capabilities, allow manual operation for up to 2 hours, and have a 10 hour backup power supply. Where a zone has a separate heating and a separate cooling system, a limit switch, mechanical stop or direct digital control system shall prevent the heating set point from exceeding the cooling set point and to maintain the 5 degree deadband. Final Job Closeout, Operations and Maintenance Manuals The contractor shall provide all construction documents, as-builts, equipment operations and maintenance manuals upon completion of work, to the owner or agent within 90 days of obtaining the certificate of occupancy. The manual shall be entitled "Operations and Maintenance Manual", with the contact information of project manager, job name, completion date, with year of completion. The manual shall include, as a minimum: Maintenance instructions for all equipment, including but not limited to, schedule, servicing, lubrication, belt and filter requirements. Equipment suppliers names, addresses, and telephone numbers. Equipment catalog submittals, cut sheets and ratings tables. Part numbers for all replaceable parts. As built drawings. Air and/or water systems balance report as specified. Working fluid chemistry reports. Control diagram or drawing and operation sequences. Startup and all functional performance testing reports. Commissioning report completed by the design professional to ensure operations are as intended by the design team, basis of design and owner project requirements. Inspection reports including rough in, final and certificate of occupancy by the authority(ies) having jurisdiction. A permanent detailed list of all design criteria including but not limited to: building heat loss; gain; thermal conductivity R values for any roof, wall, window, door, and slab assemblies; water heating load; equipment capacities and efficiency; and any other relevant loads and metrics of the project shall be located at the electrical panel. Valve tagging chart as herein/before specified. Guarantee and warranty letter for at least a one year period, from the time of acceptance. M-001 Mechanical Specifications Design Criteria & Legend DATEMARK DESCRIPTION SHEET TITLE OF 5 CHK'D BY: DRAWN BY: PROJECT NUMBER: Nu t r i e n t F a r m s G r e e n h o u s e H e a d h o u s e 33 3 N u t r i e n t F a r m s R o a d Ne w C a s t l e , C O 8 1 6 4 7 BW BE 240402-01 SEAL SD 08/05/24 SCHEMATIC DESIGN PO BOX 5774 783 Second Street EAGLE, CO 81631 970.390.7673 www.bremaengr.com DD 08/26/24 PERMIT DOCUMENTS CD 12/04/24 PERMIT DOCUMENTS2 CD 12/12/24 PERMIT DOCUMENTS3 CD 01/07/25 PERMIT DOCUMENTS4 WT-ROS Mechanical Site Plan 1" = 10'NORTH SZ 1 1745 SQFT SZ 2 400 SQFT SZ 3 235 SQFT SZ 4 160 SQFT SZ 5 500 SQFT General Notes 1.PROVIDE ACCESS TO ALL CONTROLS, VALVES & FILTERS AS NECESSARY. INSTALL PER MANUFACTURER INSTALLATION GUIDE - VCIF. 2.DO NOT PENETRATE ANY CONCRETE AND STRUCTURAL MEMBER WITHOUT CONSULTING A STRUCTURAL ENGINEER AND RECEIVING WRITTEN APPROVAL FOR SIZE AND LOCATION. REFERENCE SPECIFICATIONS FOR ADDITIONAL CORING, CUTTING & OTHER REQUIREMENTS. 3.UPON DEMOLITION, IF THE EXISTING REVELATIONS WARRANT RE-ROUTING OR ADAPTING TO THE CONDITIONS CONSULT OWNER REP & ENGINEER TO FINALIZE PRACTICAL SOLUTION. 4.MC TO PROVIDE SOFT STARTERS. EC TO PROVIDE THE NEW EQUIPMENT WHIPS, DISCONNECTS, BREAKERS, WIRING AND CONDUIT FROM NEAREST ELECTRICAL PANEL. PC SHALL PROVIDE GRAVITY CONDENSATE DRAINS TO NEAREST SANITARY RECEPTACLE OR FLOOR SINK. WALK IN FREEZER AND REFRIGERATOR SHALL INDIRECTLY DRAIN TO NEAREST FLOOR SINK. ANY REVERSE OSMOSIS (RO) WATER SHALL DRAIN TO THE RO DRYWELL - SEE SITE PLAN FOR LOCATION. VCIF. 5.COORDINATE EQUIPMENT LOCATIONS & PIPE ROUTING WITH STRUCTURAL MEMBERS, LIGHTS, COLUMNS & OTHER TRADES. DUCTWORK AND PIPING SHALL BE ROUTED AS CLOSE TO STRUCTURE AS POSSIBLE. VCIF. 6.VERIFY AND COORDINATE SNOWMELT ZONE INSTALLATION SEQUENCE WITH OWNER AND ARCHITECT PRIOR TO PURCHASING MATERIALS. SM S SM R MANIFOLD BOX SZ-1 MANIFOLD BOX SZ2&3 MANIFOLD BOX SZ-4 MANIFOLD BOX SZ-5 1 1 2 Plan Notes PROVIDE SNOWMELT MOISTURE & TEMPERATURE SENSOR & SOCKET AND ROUTE CONTROL WIRE UNDERGROUND IN RATED CONDUIT BACK TO BOILER CONTROLLER. VCIF. INSULATED 2" SMS/R BACK TO BOILER - SEE MECHANICAL PLAN FOR CONTINUATION. INSULATED 1-1/2" SMS/R TO SNOWMELT MANIFOLD 1 - REFERENCE SNOMELT SCHEDULE FOR ADDITIONAL INSTALLATION INFORMATION. VCIF. INSULATED 1-1/4" SMS/R TO SNOWMELT MANIFOLD SERVING SZ-2 & 3 - REFERENCE SNOWMELT SCHEDULE FOR ADDITIONAL INSTALLATION INFORMATION. VCIF. INSULATED 1" SMS/R TO EACH SNOWMELT MANIFOLD 5 - REFERENCE SNOWMELT SCHEDULE FOR ADDITIONAL INSTALLATION INFORMATION.. VCIF. INSULATED 3/4" SMS/R TO SNOWMELT MANIFOLD 4 - REFERENCE SNOWMELT SCHEDULE FOR ADDITIONAL INSTALLATION INFORMATION. VCIF. 3 4 5 2 3 6 4 5 6 M-100 Mechanical Site Plan DATEMARK DESCRIPTION SHEET TITLE OF 5 CHK'D BY: DRAWN BY: PROJECT NUMBER: Nu t r i e n t F a r m s G r e e n h o u s e H e a d h o u s e 33 3 N u t r i e n t F a r m s R o a d Ne w C a s t l e , C O 8 1 6 4 7 BW BE 240402-01 SEAL SD 08/05/24 SCHEMATIC DESIGN PO BOX 5774 783 Second Street EAGLE, CO 81631 970.390.7673 www.bremaengr.com DD 08/26/24 PERMIT DOCUMENTS CD 12/04/24 PERMIT DOCUMENTS2 CD 12/12/24 PERMIT DOCUMENTS3 CD 01/07/25 PERMIT DOCUMENTS4 Mechanical Plan 1/4" = 1'-0"NORTH B 1 P 1 ET 1 P 2 WH 1 568 SQFT RZ 4622 SQFT RZ 3 411 SQFT RZ 2 139 SQFT RZ 1 T TTT ERV 1 EF 1 4"Ø SMS HWS SMR HWRHWS HWR SMS SMR General Notes 1.PROVIDE ACCESS TO ALL CONTROLS, VALVES & FILTERS AS NECESSARY. INSTALL PER MANUFACTURER INSTALLATION GUIDE - VCIF. 2.DO NOT PENETRATE ANY CONCRETE AND STRUCTURAL MEMBER WITHOUT CONSULTING A STRUCTURAL ENGINEER AND RECEIVING WRITTEN APPROVAL FOR SIZE AND LOCATION. REFERENCE SPECIFICATIONS FOR ADDITIONAL CORING, CUTTING & OTHER REQUIREMENTS. 3.UPON DEMOLITION, IF THE EXISTING REVELATIONS WARRANT RE-ROUTING OR ADAPTING TO THE CONDITIONS CONSULT OWNER REP & ENGINEER TO FINALIZE PRACTICAL SOLUTION. 4.MC TO PROVIDE SOFT STARTERS. EC TO PROVIDE THE NEW EQUIPMENT WHIPS, DISCONNECTS, BREAKERS, WIRING AND CONDUIT FROM NEAREST ELECTRICAL PANEL. PC SHALL PROVIDE GRAVITY CONDENSATE DRAINS TO NEAREST SANITARY RECEPTACLE OR FLOOR SINK. WALK IN FREEZER AND REFRIGERATOR SHALL INDIRECTLY DRAIN TO NEAREST FLOOR SINK. ANY REVERSE OSMOSIS (RO) WATER SHALL DRAIN TO THE RO DRYWELL - SEE SITE PLAN FOR LOCATION. VCIF. 5.COORDINATE EQUIPMENT LOCATIONS & PIPE ROUTING WITH STRUCTURAL MEMBERS, LIGHTS, COLUMNS & OTHER TRADES. DUCTWORK AND PIPING SHALL BE ROUTED AS CLOSE TO STRUCTURE AS POSSIBLE. VCIF. 6.ALL DUCTWORK DIMENSIONS ARE OUT TO OUT - DUCT INSULATION SHALL BE WRAP. 7.SOME OBJECTS SHOWN OFFSET FOR CLARITY. VCIF. 8.CEILING TO BE LAY-IN TILE. COORDINATE ABOVE CEILING EQUIPMENT, FAN COILS, PIPING, & CONTROLLERS WITH STRUCTURE, LIGHTING, GRID/TILES, AND OTHER TRADES. PROVIDE ACCESS AND REQUIRED SERVICE CLEARANCES ACCORDING TO INSTALLATION DOCS AND SPECIFICATIONS. VCIF. 1 2 Plan Notes PROVIDE UNDERGROUND 2" INSULATED SMS/R TO SNOWMELT MANIFOLDS. REFERENCE MECHANICAL SITE PLAN FOR CONTINUATION. SEE SCHEDULE AND PIPING DIAGRAM FOR ADDITIONAL INSTALLATION INSTRUCTIONS. VCIF. PROVIDE UNDERGROUND 1" INSULATED SMS/R TO SNOWMELT MANIFOLD 5. REFERENCE SITE PLAN FOR CONTINUATION. SEE SCHEDULE AND PIPING DIAGRAM FOR ADDITIONAL INSTALLATION GUIDANCE. VCIF. PROVIDE UNDERGROUND 3/4" INSULATED SMS/R TO SNOWMELT MANIFOLD 4. REFERENCE SITE PLAN FOR CONTINUATION. SEE SCHEDULE AND PIPING DIAGRAM FOR ADDITIONAL INSTALLATION INFORMATION. VCIF. PROVIDE INSULATED 3/4" HWS/R TO EACH RADIANT MANIFOLD. SEE SCHEDULE AND PIPING DIAGRAM FOR ADDITIONAL INSTALLATION INFORMATION. VCIF. EF-1 & DUCTWORK TO BE INSTALLED ABOVE LAY-IN CEILING - REFERENCE ARCHITECTURAL RCP's. PROVIDE 4"Ø BACKDRAFT DAMPERED EXHAUST TERMINATION. MAINTAIN AT LEAST 10' TO ANY MECHANICAL AIR INTAKE. VCIF. ERV-1 & DUCTWORK TO BE INSTALLED ABOVE LAY-IN CEILING - REFERECNE ARCHITECTURAL RCP's. PROVIDE MANUFACTURER EXHAUST & INTAKE TERMINATION KIT. REFERENCE SCHEDULE FOR ADDITIONAL INSTALLATION INSTRUCTIONS. VCIF. PROVIDE 4" CONCRETE PAD, REQUIRED SERVICE CLEARANCES, MANUFACTURER APPROVED 6"Ø STAINLESS STEEL EX & INSULATED 6"Ø SEALED OA B-VENT UTR, CONDENSATE NEUTRALIZATION KIT AND IW TO NEAREST DRAIN - INSTALL PER MANUFACTURER INSTALLATION MANUAL & SEE SPECIFICATIONS FOR ADDITIONAL INSTALLATION INFORMATION. VCIF. PROVIDE 3/4" UNDERCUT DOORS TO ALLOW FOR RETURN AIR BACK TO FC-1. 3 4 5 6 7 1 2 3 4 44 1"2"1-1/4" 5 6 6 5 P 3 P 4 P 5 7 M-ERHM-ERHM-ERH C-TM C-TMC-TM C-TM P 6-12 B 2 7 REQUIRED CLEARANCES 8"Ø8"Ø8"Ø 4"Ø MOD 12x1012x10 A200-S 24x24 L 50-OA 12x12 A200-S 24x24A200-S 24x24 B550-R 24x24 4"Ø MOD 12x10 B 550-R 24x24 12x10 8"Ø A200-S 24x24 A200-S 24x24 12x6 4"Ø A50-S 24x24 4"Ø A50-S 24x24 6"Ø A100-S 24x24 8 8 8 8 L 50-OA 12x12 FC 1 HWS HWR 3/4"HWS HWR 3/4" FC 2 T T M-101 Mechanical Plan DATEMARK DESCRIPTION SHEET TITLE OF 5 CHK'D BY: DRAWN BY: PROJECT NUMBER: Nu t r i e n t F a r m s G r e e n h o u s e H e a d h o u s e 33 3 N u t r i e n t F a r m s R o a d Ne w C a s t l e , C O 8 1 6 4 7 BW BE 240402-01 SEAL SD 08/05/24 SCHEMATIC DESIGN PO BOX 5774 783 Second Street EAGLE, CO 81631 970.390.7673 www.bremaengr.com DD 08/26/24 PERMIT DOCUMENTS CD 12/04/24 PERMIT DOCUMENTS2 CD 12/12/24 PERMIT DOCUMENTS3 CD 01/07/25 PERMIT DOCUMENTS4 General Sequence of Operation: Boiler The operation of the Boilers B1&2 shall operate in a lead lag mode according to lead controller, and associated injection loop pumps, P1&2, shall be enabled by the controller on a call from any zone valve, aquastat, or slab sensor and fire to maintain temperature via the water supply sensors. Upon completion of a heating water call, pumps P1&2 shall remain energized for 30 seconds (adj.) after boiler fire halts. Provide an outdoor temperature sensor, and utilize the boiler outdoor reset schedule to adjust supply temperatures seasonally. Domestic Hot Water Production Boilers B1&2 shall provide 160°F (adj.) HWS to WH-1. WH-1 shall provide tempered domestic hot water to the fixtures. Upon a call for heat from the aquastat, P1and/or2, and P-3 shall energize until domestic hot water reaches 140°F (adj). Provide thermostatic mixing valve/anti scald device to deliver no more than 105°F (adj) to HW fixtures. UH1-10, FC1-2 Each of the ten unit heaters and fan coils shall provide heating for the existing greenhouse or comfort zone. On a call for heat from the unit or wall mounted mounted thermostat, the associated zone valve shall open, and the zone pump and fan shall energize. Unit shall operate until setpoint (adj) has been met. Radiant Upon a heating demand call from any radiant heating thermostat, the respective zone valve(s) end switch(es) shall send a demand to the boiler controller. B1and/or2, P1and/or2 & P-4 shall energize, and the three way shall mix the supply and return to deliver 130°F HWS to each comfort zone. Snowmelt Upon a heating demand call from the outdoor temperature and moisture sensor, B1and/or2, P1and/or2 and P-5 shall energize, and the three way valve shall mix with the return water to deliver 130°F HWS to the snowmelt tubing. Boiler Piping Diagram NO SCALE AUTO AIR VENT AIR SEPARATOR GF 1 ET 1 A P P 4 TO RADIANT ZONES P 5 TO SM ZONES HW S 1 3 0 ° F HW R 1 0 5 ° F HW S 1 3 0 ° F HW R 1 0 5 ° F 4" HW S 1 6 0 ° F 1-1/2"1-1/2" 4" 1-1/4" 1-1/4" P 3 2"2" HWS 160° F HWR 130° F SPIROTHERM VSR400 1 1/4" 1" General Mechanical Notes: 1.INSTALL PER MANUFACTURER SPECIFICATIONS, THE APPLICABLE 2018 INTERNATIONAL CONSERVATION CODES, THE AUTHORITY HAVING JURISDICTION, COMMON SENSE AND WITH CONSIDERATION TO ANY FORCE MAJEURE. 2.NEW BOILERS AND PIPING SHALL BE FILLED WITH 50% PROPYLENE GLYCOL AND WATER WITH CORRECT INHIBITORS. FLUSH AND FILL AS NECESSARY TO ENSURE WATER QUALITY REQUIRED BY BOILER MANUFACTURER. PROVIDE ISOLATION & BOILER DRAINS TO SERVICE / FLUSH / DRAIN / FILL SYSTEM, EACH PIECE AND TAKE OFF, WITHOUT DRAINING THE ENTIRE SYSTEM. SEE SPECIFICATIONS FOR ADDITIONAL INSTALLATION REQUIREMENTS. 3.PROVIDE BOILER DRAINS, ISOLATION VALVES, TESTING PORTS AND ALL APPURTENANCES NECESSARY TO TEST AND BALANCE, SERVICE AND REPAIR. SEE SPECIFICATIONS FOR FURTHER INSTALLATION REQUIREMENTS. P B 1 WH 1 4" 4" 3" MAX 4 PIPE Ø's OR HYDRAULIC SEPARATOR 3" P 6 HW S 1 6 0 ° F HW R 1 3 0 ° F 1"1" P 7 HW S 1 6 0 ° F P 10 HW S 1 6 0 ° F P 11 HW S 1 6 0 ° F 3/4"3/4" NOTE: SEE ARCHITECTURAL PLANS FOR FINAL UH LOCATIONS P B 2 3" 3" P 1 P 2 1"1" 1"1" TO FC-1 P 12 HW S 1 6 0 ° F 3/4"3/4" TO FC-2 HW R 1 3 0 ° F HW R 1 3 0 ° F HW R 1 3 0 ° F HW R 1 3 0 ° F UH 2 T UH 1 T UH 4 T UH 3 T 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" P 8 HW S 1 6 0 ° F HW R 1 3 0 ° F 1"1" P 9 HW S 1 6 0 ° F 1"1" HW R 1 3 0 ° F UH 6 T UH 5 T UH 8 T UH 7 T 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" UH 10 T UH 9 T 3/4" 3/4" 3/4" 3/4" 4" 4" MAX 4 PIPE Ø's 4"4" PROVIDE TAKEOFFS FOR FUTURE HEATING SYSTEM 4"4" S PROVIDE SENSOR WELL FOR FUTURE S HW R 1 3 0 ° F GF 1 ET 1 B 1 WH 1 B 2 AS 1 P 3 P 4 P 12 South Mechanical Room Elevation 1/4" = 1'-0" 202.8000 508.8000 M-201 Mechanical Piping Plan & Sequence of Operations DATEMARK DESCRIPTION SHEET TITLE OF 5 CHK'D BY: DRAWN BY: PROJECT NUMBER: Nu t r i e n t F a r m s G r e e n h o u s e H e a d h o u s e 33 3 N u t r i e n t F a r m s R o a d Ne w C a s t l e , C O 8 1 6 4 7 BW BE 240402-01 SEAL SD 08/05/24 SCHEMATIC DESIGN PO BOX 5774 783 Second Street EAGLE, CO 81631 970.390.7673 www.bremaengr.com DD 08/26/24 PERMIT DOCUMENTS CD 12/04/24 PERMIT DOCUMENTS2 CD 12/12/24 PERMIT DOCUMENTS3 CD 01/07/25 PERMIT DOCUMENTS4 M-601 Mechanical Schedules DATEMARK DESCRIPTION SHEET TITLE OF 5 CHK'D BY: DRAWN BY: PROJECT NUMBER: Nu t r i e n t F a r m s G r e e n h o u s e H e a d h o u s e 33 3 N u t r i e n t F a r m s R o a d Ne w C a s t l e , C O 8 1 6 4 7 BW BE 240402-01 SEAL SD 08/05/24 SCHEMATIC DESIGN PO BOX 5774 783 Second Street EAGLE, CO 81631 970.390.7673 www.bremaengr.com DD 08/26/24 PERMIT DOCUMENTS CD 12/04/24 PERMIT DOCUMENTS2 CD 12/12/24 PERMIT DOCUMENTS3 CD 01/07/25 PERMIT DOCUMENTS4 Plumbing Specifications General These drawings are intended to provide the general scope of work and materials of the project. Plumbing Contractor (PC) shall provide the management, labor, equipment and accoutrements for a safe, functioning and complete system. Tendering of a proposal shall be confirmation the contractor has made a thorough analysis of the job site, existing conditions and construction documents to deliver the described mechanical design and system. Change orders and modifications submitted by the contractor shall not be honored without the express written approval by the owner, architect, general contractor (GC or prime) and/or engineer of record. Codes and Standards Contractor to obtain all necessary certificates of permit and inspections. The plumbing system, piping, waste, domestic water, natural gas and vent shall be installed in accordance with the following codes, standards and permitting requirements under the authority having jurisdiction. Where there are conflicts between the codes, the strictest interpretation shall apply. 1.Local ordinances as interpreted by the Town of Garfield County Department. 2.2015 International Plumbing Code (IPC). 3.2015 International Building Code (IBC). 4.2018 International Energy Conservation Code (IECC). 5.2015 International Fuel Gas Code (IFGC). Warranty, Materials and Workmanship Manufacturer trade names and catalog numbers stated herein are intended to indicate the quality of equipment or materials desired. All manufacturers not specifically listed or scheduled require prior review before installation. All materials and equipment shall be of the highest quality and performance. If a modification to the specified materials or equipment is desired, the contractor shall provide a written request to the engineer of record for review and six (6) copies of submittals describing make, model and all the necessary metrics for adequate review. The installation shall perform according to the code and design intent, and be free of any defects for a period of one year upon acceptance by the owner. Contractor shall have current licensing and all necessary general and liability insurance applicable to the area of installation. All materials, piping and equipment shall be installed in a neat and workmanlike manner by competent specialists of each trade to meet the described and specified standards. It is the responsibility of the contractor to verify the desired piping, equipment and accoutrements meet any and all spatial constraints, working clearances, accessibility and the design intent of the project. Do not scale drawings - it is up to the contractor to verify all constraints in the field before completing any work. Coordinate the plumbing installation with architect, fire suppression, electrical, civil, structural, interiors and other applicable elements prior to installation. Any piping, insulation, sheathing, hangers or other materials installed in a plenum shall have a flame spread index not more than 25, a smoke-developed index not more than 50, and conform to ASTM E 84 or UL 723. Medical gas piping may never be located in any plenum. Contractor to complete all functional performance testing according to, but not limited to, and specified by the sequence of operations, backup modes, alarms, power on/off, economizer, hydronic/airside test and balance, and manufacturer installation instructions. If testing procedure fails, fix and repeat the test at no additional cost to the owner. All areas requiring cutting and patching shall be coordinated with the project superintendent and/or general contractor. Locate any utilities prior to excavating. X-ray concrete walls and/or slabs prior to coring. Coordinate all roof and exterior wall penetrations with the appropriate trades. Any penetrations through a fire wall or partition shall maintain the integrity of the fire rating - verify fire rating with architect. Any material used to prevent fire or products of combustion from penetrating a fire wall or partition shall be UL listed and meet the minimum fire rating as prescribed by the architect. Any roof penetrations shall prevent any outdoor elements from entering the roof assembly and/or building. All equipment installed under this contract shall follow the respective manufacturer installation, maintenance and operation instructions. Provide adequate clearances and access panels for inspection, service, maintenance and the removal of equipment and accessories - including but not limited to appliances, control devices, heat exchangers, valves, actuators, compressors, burners, and blower assemblies. Provide at least a level 30” deep and wide working space in front of all these devices. Offset piping, and equipment as necessary to avoid beams, columns and structural members - verify with the structural engineer before penetrating any structural member. Contractor to provide carbon monoxide detectors in any room with natural gas burning appliances. Provide detectors per local code and authority having jurisdiction. Cleanup The contractor shall leave the workspace and equipment in an orderly and unsoiled condition during and upon completion of work. Contractor is responsible for removing own debris, trash, and remaining material. Electrical Motors, starters, overloads, sensors, relays, solenoid valves, transformers and variable frequency drives shall be provided by PC unless otherwise indicated on plans. Electrical contractor to provide necessary high voltage wiring, disconnects, and conduit unless provided with the packaged plumbing equipment. Contractor to coordinate and verify all voltage and phase requirements to the specified motor and equipment with GC and EC. Provide phase loss protection and soft start motors. No piping or ductwork shall be installed above or below electrical switchgear, electrical panels and within any elevator shaft. Piping & Insulation New or repaired potable water systems shall be purged of deleterious matter and disinfected prior to utilization in accordance to section 610.1 of the IPC. Pipe material, connectors, valves, fittings, expansion and vibration controls shall be approved and rated for the operating temperature and pressure of the system, and conform to the standards listed in sections 605 and 702, Table 605.3 and 702.1 of the IPC or an approved equivalent. Provide double check back flow protection on cold water supply service and back flow preventers where there is any chance of cross contamination to the domestic supply water. Piping shall be sized for no more than 3.5' of head loss per 100 feet of pipe and a maximum velocity of 4 feet per second. Above grade domestic water piping shall be drawn tube type “L” wrought copper and approved fittings. Domestic water piping and fittings shall comply with NSF 372 and shall have a weighted average lead content of lead of 0.25% or less. Any underground piping shall be insulated type “K” to the appropriate thickness and protected from corrosion and degradation with no fittings. Direction changes shall be accomplished with long radius elbows. All domestic hot and cold water piping shall be insulated according to IECC Table C403.2.1. Provide thermostatic mixing valves and anti-scald protection for domestic hot water supply that conforms to ASSE 1070, foot baths, pedicure baths and shampoo sinks so they shall deliver no more than 110 degrees Fahrenheit water. In localities having a winter design temperature of 32° Fahrenheit or less, water, soil or waste pipe, and waste receptors, shall not be installed outside, in exterior walls, in attics, crawlspaces or other areas of freezing conditions unless adequate protection from freezing is implemented. Water service piping shall be installed 6” below frost level specified by the local authority jurisdiction. Provide non-lead solder compatible to material, fittings and valves, and approved for the particular application. All valves shall be compatible with the installed piping and fittings and meet NSF 61 in all potable supply drinking water-this includes all ball, gate, butterfly, globe, plug, prv, backflow prevention, check and solenoid valves. Valves shall not have a Cv rating with a pressure loss greater than 2 psi. Provide isolation valves on both the sides of any major piece of plumbing equipment that shall require service and maintenance. Above ground waste piping shall conform to ASTM A 888. Any below grade waste may be standard weight cast iron and/or schedule 40 PVC with solvent fused joints. Vent shall be PVC schedule 40 with solvent fused joints. ASME potable supply Water Heaters, Storage Tanks, Expansion Tanks and Hot Water Recirculation Systems Pressure relief valve (PRV) shall be installed vertically and according to manufacturer installation instructions. Any boiler heating system with PRV setting greater than 30psi shall require an ASME expansion tank. Any potable supply water heater with storage, storage tank and sidearm heated by steam or other indirect means when the heating input is greater than 200kBTU/hr, the potable water temperature exceeds 210degrees or the vessel contains more than 120 gallons shall be ASME constructed. Water heaters and storage tanks shall require a pan 1-1/2” deep and 2” equipment overlap where leakage may cause damage. Provide at least a 3/4” indirect drain line to nearest receptor and/or water leakage detection device. Where a storage water heater is supplied with cold water that passes through a check valve, pressure reducing valve or backflow preventer, a thermal expansion tank shall be connected to the water heater cold water supply pipe downstream of these devices. Tank shall be sized in accordance with the manufacturer instructions and such that the pressure in the water distribution system shall not exceed 150 pounds per square inch or the setting of the ASSE 1003 PRV or CSA B356 PRV with strainer system, pressure relief setting. In a hot water recirculation system, circulation pumps and/or heat trace shall automatically turn off when there is no demand. Equipment Identification All piping and equipment shall have a professional legible identification delineating make, model, flow direction, and the metrics necessary for service, maintenance and identification. Any painting or customization shall not inhibit reading the label. Provide pipe and valve markers as necessary. Clothes Washers and Dishwashers, Food Waste Disposers, Water Closets, Urinals and Whirlpool Tubs Domestic water supply to any dishwasher or clothes washer shall be protected against backflow by an ASME 112.1.2 or 112.1.3 approved air gap integral to the machine or a backflow preventer. Domestic food waste disposers shall conform to ASSE 1008 and UL 430. Water closets shall not exceed 1.6, and urinals shall not exceed 1 gallon(s) per flush. Dual flushing toilets shall comply with ASME 112.19.14. Whirlpool bathtubs shall be UL 1795 listed. Condensate Drain Piping and Discharge Piping with a PRV Provide trapped and vented condensate piping to nearest waste line receptacle. Piping may be schedule 40 PVC with solvent fused joints or other approved material. Where condensate discharge may be acidic from any boiler, furnace, makeup air unit, air handler, unit heater, or other, condensate shall be piped through a manufacturer approved neutralization kit and prevent downstream pipe corrosion, degradation and failure for all high efficiency equipment (greater than 90%). Discharge piping from a pressure relief valve shall be copper and terminate not more than 6” above or not less than twice the discharge pipe diameter above the drain receptor or flood rim level. Condensate drain lines shall be configured to permit the cleaning of blockages without being cut. Condensate pumps located in uninhabitable areas shall be interlocked to shut off equipment when pump fails. Food Handling Equipment and Fixtures Commercial equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap. Each well of multiple-compartment sink shall discharge independently to a waste receptor. Natural Gas Piping Natural gas piping shall be schedule 40 black iron or galvanized and in accordance to NFPA 58, ASME B36.10, 10M, ASTM A53/A53M, and/or ASTM A106. Corrugated stainless steel tubing shall be listed in accordance with ANSI LC1/CSA 6.26. Black or wrought iron sizes up to 4” may be threaded. Any iron gas piping larger than 4” shall be welded. Gas piping shall be rated for the demand and pressure application, tested and hold pressure (at 1.5 times the working pressure but not less than 3psi) at least 24 hours, and be inspected by the authority having jurisdiction prior to meter connection. Pipe sizing has been determined for black iron use at 2psi with a 1psi pressure drop up to the sub-meters. Piping downstream of the sub-meters have been sized for 14” wc pressure with a 0.5 inch wc drop. Any other utilized piping materials and sizing methods shall be verified by the contractor to meet the listed demand and pressure drops with the engineer of record. Any gas piping that is underground must be rated for the application, protected from corrosion and physical damage. Contractor to install underground piping according to the specifications of the utility company. Any gas piping encased under buildings or in concrete shall be sleeved, and provided with access and protection from damage and corrosion. Gas service piping shall not penetrate building foundation walls at any point below grade. Any subgrade piping shall be located at least 12” below grade. Any exposed piping shall be protected from corrosion, structurally supported, and any penetration shall be sealed from the outdoors. Natural gas piping on roofs shall be elevated at least 3.5 inches. Contractor shall use anodeless risers and provide protection from physical damage upon routing out of the ground into the building unless black or galvanized steel is used indoors. Provide shield plates where piping has been routed in wall framing. Appliances shall be connected to the gas piping system with ANSI 121.75/CSA6.27 connectors. Contractor shall provide a shutoff valve within 6 feet of the appliance being served, and the floor. Gas relief piping and serving gas regulators to the outdoors shall be aluminum. Equipment, Hangers and Supports Adequate structural support shall be provided and according to IPC requirements - vibration isolators, neoprene pads and insulation saddles shall be required to support any piping, equipment and ductwork from structure without noise propagation and damage to integrity and operation. Contractor to provide temporary heat, outdoor pads, drain pans, sensors, water detectors, alarms, drains and any other appurtenance necessary for a functional mechanical system. The new building heating and/or cooling equipment shall not be used as temporary heat during construction. Where damage to any building components could occur as a result of overflow from the equipment condensate or drain removal system, provide either of the following four alternatives. Provide an auxiliary 1-1/2” deep drain pan three inches larger than the equipment and drain. Provide a separate overflow drain connected to the drain pan at a point higher than the primary drain, provided with the equipment. An auxiliary drain pan without a drain equipped with a water detection device conforming to UL 508 that will shut off equipment prior to overflow. Provide a water level detection device conforming to UL 508 that will shut off the equipment served in the event the primary drain is blocked. Air Intakes, Venting and Exhaust Contractor to provide venting and combustion air intake to the outdoors with manufacturer approved materials. Size, elbows and length shall be determined by manufacturer installation guidelines and/or engineer. Any variation in routing and sizing shall be approved by the engineer of record. Any heating water boiler application that utilizes manufacturer approved plastic venting, shall use at least 10' of actual length of CPVC out of the boiler. Contractor to use only glue and primer that is appropriate to match the material application. Intake openings shall be located at least 10' away from any property line or contaminant, or with at least 25' of vertical separation. Intakes shall be located not less than 3' below contaminant sources located within 10' of the source. Exhaust shall be discharged outdoors at a point where it will not cause a nuisance or reintroduce the exhaust air back into the building, and not directed onto walkways. For environmental exhaust, maintain at least 3' between any exhaust termination and openings into the building, and property lines. Maintain at least 10' between any mechanical intake and any environmental exhaust. Product conveying outlets shall be 10' away from property lines, operable openings and above grade. Product exhaust shall be at least 3 feet from exterior walls and roofs. Combustion appliance vent terminations shall not be within 12” of any door swing - door stops and closers cannot be used to meet clearance requirements. Outdoor air intake terminations shall be protected from the outdoors with corrosion, animal and weather resistant 1/4” to 1/2” screening. Direct vent terminations from condensing appliances shall be at least 12” above grade or highest snow level, and shall not be within 10 feet of any opening into any adjacent building. Final Job Closeout, Operations and Maintenance Manuals The contractor shall provide all construction documents, as-builts, applicable certifications, equipment operations and maintenance manuals upon completion of work, to the owner or agent within 90 days of obtaining the certificate of occupancy. The manual shall be entitled "Operations and Maintenance Manual", with the contact information of project manager, job name and year of completion. The manual shall include, as a minimum: Maintenance instructions for all equipment, including but not limited to, servicing, lubrication, and filter requirements. Equipment suppliers names, addresses, and telephone numbers. Equipment catalog submittals, cut sheets and ratings tables. Part numbers for all replaceable parts. As built drawings. Control diagram or drawing and operation sequences. Startup, and all functional performance testing reports. Commissioning report completed by the design professional to ensure operations are as intended by the design team and owner project requirements. Inspection reports including rough in, final and certificate of occupancy by the authority(ies) having jurisdiction. A detailed list of all design criteria including but not limited to: building heat loss; gain; thermal conductivity R values for any roof, wall, window, door, and slab assemblies; water heating load; equipment capacities and efficiency; and any other relevant loads and metrics of the project shall be located at the electrical panel. Valve tagging chart as hereinbefore specified. Guarantee and warranty letter. PIPE UP PIPE DOWN PIPE TAKEOFF (BOTTOM OF MAIN) PIPE TAKEOFF (TOP OF MAIN) PIPE END CAP PIPE UNION FLEXIBLE PIPE CONNECTION PIPE EXPANSION JOINT POINT OF NEW CONNECTION LOW CAPACITY AIR VENT PLUG VALVE CHECK VALVE BALL VALVE FLOWSET ACCUSETTER BALANCING VALVE BUTTERFLY VALVE PRESSURE REDUCING VALVE STRAINER W/ BLOWDOWN VALVE PRESSURE / TEMP. TAP (PETE'S PLUG) COMBINATION PRESSURE / TEMP. GAUGE 2-WAY CONTROL VALVE 3-WAY CONTROL VALVE 4-WAY CONTROL VALVE DIFFERENTIAL BYPASS (ANGLED / STRAIGHT) THERMOMETER Plumbing Legend HIGH CAPACITY AIR VENT WATER TEMPERATURE SENSOR Note: All symbols on this legend may not be used on this project. OIL WASTE INDIRECT WASTE WASTE ABOVE GRADE DOMESTIC HOT WATER RECIRC. DOMESTIC HOT WATER DOMESTIC COLD WATER MEDIUM PRESSURE NATURAL GAS 2PSI GREASE WASTE WASTE BELOW GRADE NATURAL GAS 10-14" WCG MG VENT THROUGH ROOF CLEAN OUT TO GRADE FLOOR CLEAN OUT WALL CLEAN OUT CLEAN OUT NEW EXISTING WCO FCO COTG (E) (N) VTR IW VENT CONDENSATE DRAIN UP THROUGH ROOFUTR VERIFY CONDITIONS IN FIELDVCIF DOMESTIC HOT WATER RECIRCULATIONHWC GW V W W CO HOSE BIB / DRAIN OW C CUBIC FEET PER HOURCFH FEET PER SECONDFPS SANITARY STORMSS OVERFLOW ROOF DRAINO NITROUS OXIDE PIPINGN20 OXYGEN PIPINGO2 VACUUM PIPINGVAC COMPRESSED AIR PIPINGCA GATE VALVE P-001 Plumbing Specifications Schedules & Legend DATEMARK DESCRIPTION SHEET TITLE OF 2 CHK'D BY: DRAWN BY: PROJECT NUMBER: Nu t r i e n t F a r m s G r e e n h o u s e H e a d h o u s e 33 3 N u t r i e n t F a r m s R o a d Ne w C a s t l e , C O 8 1 6 4 7 BW BE 240402-01 SEAL SD 08/05/24 SCHEMATIC DESIGN PO BOX 5774 783 Second Street EAGLE, CO 81631 970.390.7673 www.bremaengr.com DD 08/26/24 PERMIT DOCUMENTS CD 12/04/24 PERMIT DOCUMENTS2 CD 12/12/24 PERMIT DOCUMENTS3 Plumbing Plan 1/4" = 1'-0"NORTH WH 1 1.112" W, 112" V, 12" CW & 12" HW TO LV-1. 2.3" W, 2" V & 12" CW TO WC-1. 3.3" W & 2" V TO FLOOR SINK. 4.2" W, 1-1/2" V, 3/4" CW TO URINAL. 5.3" W & 2" V TO FD-1. 6.PROVIDE FLUSHING IW FROM RO SYSTEM TO FLOOR SINK AS REQUIRED. 4" RO WASTE FROM FLOOR SINK TO NORTH DRYWELL ONLY. INSTALL PER MANUFACTURER INSTALLATION INSTRUCTIONS AND SEE SITE PLAN FOR LOCATION & VCIF. 7.4" W OUT OF THE BUILDING TO SEPTIC FIELD. VERIFY INVERT ELEVATIONS IN FIELD. SEE SITE PLAN AND SEPTIC DRAWINGS FOR FURTHER INFORMATION. VCIF. 8.2" POTABLE CW FROM CISTERN. SEE SITE PLAN FOR FINAL LOCATION. MAINTAIN 5' HORIZONTALLY TO ANY WASTE LINE PER IPC 302. COORDINATE FINAL PIPING LOCATIONS BETWEEN PLUMBING AND ELECTRICAL CONTRACTOR. VCIF. 9.1-1/4" POTABLE RO CW FROM RO SYSTEM AND/OR CISTERN. SEE SITE PLAN FOR FINAL LOCATION. MAINTAIN 5' HORIZONTALLY TO ANY WASTE LINE AND PER IPC 302. COORDINATE FINAL PIPING LOCATIONS BETWEEN PLUMBING AND ELECTRICAL CONTRACTORS. VCIF. 10.4" RO W SHALL DRAIN TO NORTH DRYWELL ONLY. VERIFY INVERT ELEVATIONS AND SEE SITE PLAN FOR FINAL LOCATION. VCIF. MAINTAIN MINIMUM 5' HORIZONTALLY BETWEEN ANY W AND DOMESTIC CW OR RO CW PIPING - PROVIDE REQUIRED CLEARANCES PER IPC 302 AND NEC. COORDINATE FINAL PIPING LOCATIONS BETWEEN PLUMBING AND ELECTRICAL CONTRACTOR. 11.3/4" IW CONDENSATE FROM EACH REFRIGERATOR OR FREEZER TO NEAREST FLOOR SINK. REFERENCE INSTALLATION MANUAL FOR EACH APPLIANCE FOR INDIVIDUAL REQUIREMENTS. VCIF. 12.1" CW & HW TO EACH TRIPLE SINK & & ROOT WASH FAUCET. INDEPENDENT 1-1/2" IW FROM EACH SINK TO DRAIN TO NEAREST FLOOR SINK. VCIF. 13.UNDERGROUND SIZE 46 2 PSI LP FROM STORAGE TANKS TO BOILER & REGULATE AS REQUIRED TO THE 11' WC FOR THE BOILER - PROVIDE 2 PSI TO 11" WC REGULATOR AND THEN MAINTAIN AT LEAST 10' OF STRAIGHT 11" WC SIZE 46 CSST AND PROVIDE NECK DOWN TO 1-1/4" CONNECTION AS CLOSE TO BOILER AS POSSIBLE. SEE SITE PLAN FOR FINAL TANK LOCATION. REFERENCE PROPANE SCHEDULE, BOILER INSTALLATION MANUAL AND SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. VCIF. Plumbing Notes: SYMBOL USED FOR NOTE DESIGNATION General Plumbing Notes: 1.PC TO PROVIDE CLEANOUTS AND ACCESS AT EACH CHANGE OF DIRECTION FOR W, STORM & OVERFLOW PIPING. 2.SOME PIPING, EQUIPMENT AND DUCTWORK SHOWN OFFSET FOR CLARITY. OFFSET PIPING AS REQUIRED TO ROUTE AROUND STRUCTURAL MEMBERS - ANY STRUCTURAL MEMBER PENETRATION SHALL BE APPROVED BY STRUCTURAL ENGINEER. COORDINATE ANY CONFLICTS WITH ARCHITECT AND OTHER TRADES. 3.PROVIDE FREEZE PROTECTION TO ALL PIPING SUBJECT TO EXPOSURE TO THE OUTDOORS. 4.POTABLE REVERSE OSMOSIS (RO) WATER SHALL BE DRAINED TO NORTH DRYWELL ONLY, AND SHALL NOT BE DRAINED TO THE SANITARY W. - SEE SITE PLAN FOR LOCATION. VCIF. 5.MAINTAIN MINIMUM CODE REQUIRED DISTANCES BETWEEN ANY PROPANE, WASTE, WATER AND/OR CONDUIT OR ELECTRICAL WIRE. CONTACT YOUR LOCAL UTILITY SERVICE FOR EXACT REQUIREMENTS. VCIF. 1 LV-1 1 LV-1 TS-1122 WC-11 MS-1 ET 1 FS-1 5 FD-1 FD-1FD-1 FD-1 FD-1 FD-1 FD-1 FD-1 COTG COTG 3 U-1 3 FS-1 20 4"4"4"4" W WW RO W RO CW 1-1/2" CW 4" CW HW 35 5 5 5 5 55 3/4" CW 7 2" CW 1-1/4" RO CW 9 8 10 11SIZE 46 CSST 2PSI LP - SEE PLAN NOTE 13 13 13 3/4" 1/2" 1-1/4" 1/2" 3/4" 1-1/4" 1-1/2" 14.PROVIDE 1-1/4" RO CW TO FOGGING SKID - REVIEW ARCHITECTURAL DRAWINGS FOR ADDITIONAL DETAILS, AND INSTALL PER MANUFACTURER INSTALLATION INSTRUCTIONS AND SPECIFICATIONS. VCIF. 15.PROVIDE ISOLATION, CHECK VALVE, AND 1-1/2" CW TO WH-1. PROVIDE THERMOSTATIC ANTI-SCALD MIXING DEVICE DOWNSTREAM TO DELIVER NO MORE THAN 105°F (ADJ) TO THE DOMESTIC HW FIXTURES. VCIF. 16.PROVIDE 3/4" RO, 1" RO W & V TO DRINKING FOUNTAIN. INSTALL PER MANUFACTURER INSTALLATION INSTRUCTIONS. 17.PROVIDE 1" HW & CW, 1-1/4" W & 1" V, THERMOSTATIC ANTI-SCALD MIXING DEVICE TO DELIVER 60°-90°F (ADJ) TO EMERGENCY EYEWASH STATION. REFERENCE ARCHITECTURAL PLANS, AND INSTALL PER MANUFACTURER INSTALLATION INSTRUCTIONS. VCIF. 18.PROVIDE 3/4" CW & HW, 1-1/2" W & V ROUGH-INS FOR FUTURE SINK - VERIFY MAKE AND MODEL WITH ARCHITECT AND OWNER. 19.PROVIDE 3' DIAMETER 6' DEEP SUMP FOR FUTURE SUMP PUMP, SP-1, AND A 4" W APPROXIMATELY 4' ABOVE BOTTOM OF SUMP OUT EAST FOUNDATION WALL AND CAPPED FOR FUTURE. W TO EVENTUALLY BE ROUTED TO FUTURE ANAEROBIC DIGESTER. 20.PROVIDE 24x24 FLOOR SINK - VERIFY MAKE AND MODEL WITH ARCHITECT AND OWNER. PROVDE 3" W TO SUMP - COORDINATE ROUTING WITH OTHER TRADES AND VCIF. 1415 17 16 DF-1 7 6 FS-1 3 FS-1 COTG M-ERHM-ERHM-ERH C-TM C-TMC-TM C-TM LV-1 1 12FS-2 RW-1 11 11 11 11 SP 1 18 L-1 CW HW3/4" HW CW HW 3/4" 3/4" General Plumbing Notes: 1.PC TO PROVIDE CLEANOUTS AND ACCESS AT EACH CHANGE OF DIRECTION FOR W, STORM & OVERFLOW PIPING. 2.SOME PIPING, EQUIPMENT AND DUCTWORK SHOWN OFFSET FOR CLARITY. OFFSET PIPING AS REQUIRED TO ROUTE AROUND STRUCTURAL MEMBERS - ANY STRUCTURAL MEMBER PENETRATION SHALL BE APPROVED BY STRUCTURAL ENGINEER. COORDINATE ANY CONFLICTS WITH ARCHITECT AND OTHER TRADES. 3.PROVIDE FREEZE PROTECTION TO ALL PIPING SUBJECT TO EXPOSURE TO THE OUTDOORS. 4.POTABLE REVERSE OSMOSIS (RO) WATER SHALL BE DRAINED TO NORTH DRYWELL ONLY, AND SHALL NOT BE DRAINED TO THE SANITARY W. - SEE SITE PLAN FOR LOCATION. VCIF. 5.MAINTAIN MINIMUM CODE REQUIRED DISTANCES BETWEEN ANY PROPANE, WASTE, WATER AND/OR CONDUIT OR ELECTRICAL WIRE. CONTACT YOUR LOCAL UTILITY SERVICE FOR EXACT REQUIREMENTS. VCIF. 6.VERIFY ALL W INVERT ELEVATIONS PRIOR TO INSTALLATION - ENSURE ANY BUILDING W DRAIN LINES SLOPE AT LEAST 1/8" DROP PER FOOT OF RUN. VCIF. 7.CEILING TO BE LAY-IN TILES. COORDINATE ABOVE CEILING EQUIPMENT, FAN COILS, PIPING, & CONTROLLERS WITH STRUCTURE, LIGHTING, GRID/TILES, AND OTHER TRADES. PROVIDE ACCESS AND REQUIRED SERVICE CLEARANCES ACCORDING TO INSTALLATION DOCS AND SPECIFICATIONS. VCIF. 19 3/4" RO CW 3/4" RO CW COTG 5 FD-1 5 FD-1 5 FD-1 4" COTG COTG B 1 B 2 13 13 P-101 Plumbing Plan DATEMARK DESCRIPTION SHEET TITLE OF 2 CHK'D BY: DRAWN BY: PROJECT NUMBER: Nu t r i e n t F a r m s G r e e n h o u s e H e a d h o u s e 33 3 N u t r i e n t F a r m s R o a d Ne w C a s t l e , C O 8 1 6 4 7 BW BE 240402-01 SEAL SD 08/05/24 SCHEMATIC DESIGN PO BOX 5774 783 Second Street EAGLE, CO 81631 970.390.7673 www.bremaengr.com DD 08/26/24 PERMIT DOCUMENTS CD 12/04/24 PERMIT DOCUMENTS2 CD 12/12/24 PERMIT DOCUMENTS3