HomeMy WebLinkAboutEngineer's OWTS Design Plan129 Cnlrus Lnrue CeReoNonm, CO A1623 970.309.5259 cARLA.oSTBERG@GMAI L.coM Ht.:I,'r.l( : (:( ):\stl :t,'t.ttY(; January 1,2022 Benjamin and Erica Coon c/o Brad Jordan bradiordanarchitecture@omail.com Project No. C1682 subsurface lnvestigation and onsite wastewater Treatment system Design 4-Bedroom Residence + 1 Future Bedroom Lot 3, Rapids on the Colorado Garfield County, Colorado Benjamin and Erica, CBO lnc. performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 2.329-acre property is tocated outside of New Caifle, in an area where OWTSs are necessary. Legal Description: Section:4 Township: 6 Range: 91 Subdivision: RAPIDS ON THE COLORADO Lot:3 Parcel lD: 2181-043-07-003 SITE CONDITIONS The property is currently undeveloped. A 4-bedroom residence and detached garageiworkshop with plumbing are proposed. A future bedroom is contemplated. The property will be served potable water from a community water system. The water line will enter theproperty from the east. The water line will not come within 2S-feet of any OWTS component. The Colorado River is located approximately 128'to the northwest of the proposed STA. The proposed soil treatment area (STA) location has an approximate 2% slope to the northwest. The proposed area vegetated with native grasses. There should be no traffic or staging of material over the future STA site to avoid compaction of soilsprior to construction of the STA. SUBSURFACE The subsurface was investigated on November 15,2021 by observing three soil profile test pit excavations (Test Pits) that were excavated prior to our arrival at the property. A visual and tactile soil analysis was completed by Carla Ostberg.l The materials encountered in Test Pit #1 mnsisted of light brown loam to 4.o-feet, underlain by light brown loam with increasing cobbles to a maximum depth explored of 8.0-feet. No bedrock or groundwlter was t Carla Ostberg holds a Certificate of Attendance and Examination from the CPOW Visual and Tactile Evaluation of Soils Training. Page2 encountered. Test Pit #1 was excavated the area of the proposed residence. The materials encountered in Test Pit #2 consisted of light brown loam to 6.0-feet, underlain by light brownloam with increasing cobbles to a maximum depth exflored of 8.g-feet. No bedrock or groundwater wasencountered. The materials encountered in Test Pit #3 consisted of light brown loam to 6.0-feet, underlain by light brownloam with increasing cobbles to a maximum depth explored of 8.g-feet. No bediock or groundwater wasencountered. Test Pits #2 and #3 were excavated in the area of the_ proposed STA. With increasing cobbles beginningat approximately 6-feet below grade, the proposed infiltrative area will remain shallow, with installa'tion a[approximately 2-feet below grade. A sample of the soils was taken from Test Pit #2 at3-teel below grade. The soil structure grade wasmoderate. The soil formed a ball and a ribbon approximately 1-inch in length before breaki-ng. Soilstructure shape was blocky and consistence was friable to fiim. Soil textuie was both gritty ind smooth. 9IA lling is based on Soil Type 2, Loam with moderate structure grade. A long term acceptance rate LLTAR) of 0.6 gallons per square foot will be used to design thi owTs in aicordance GarfieldCou nty On -Site Wastewater Treatment System Reg ulation's. View Test Pit #1 , cobbles begin at 4' Test Pit #1 Page 3 Test Pit #2,begin at 2' View of and Backfill Pit #3 Page 4 Test Pit #3 View of property a Backfill Looking toward the Colorado River Sieved sample Ribbon approximately 1-inch in length Page 5 DESIGN SPECIFICATIONS Design Calculations: AverageDesignFlow=T5GPDx2people/bedroomx3Bedrooms+T5GPDl4tnBedroom)=525GPD+ future bedroom 150 GPD = 675 GPD LTAR = 0.6 GPD/SF 675 GPD / 0.6 GPD/SF x 1.0 (pressure dosed beds) x 0.7 (chambers) = 766 t- The new OWTS design is based on 4-bedrooms and possible future bedroom. An average daily wastewater flow of 675 GPD will be used. For the purposes of this OWTS design, Benchmark Elevation has been established as Finished Floor of the Main House 100' (5503.5'). The Finished Floor elevation of the Garage/ Workshop with plumbing is 99'. CBO lnc. should be notified of any discrepancies or problems with grade elevations of proposed components during installation of the OWTS. *Elevations are based upon standard OWTS installation practices. Component elevations may change during installation due to site conditions. The 4-inch diameter SDR-35 sewer lines exiting the residence and garage must have double-sweep clean outs and a minimum2o/o grade to the septic tank. The sewer line from the garage should tie into the sewer line from the main house with a wye fitting prior to entering the septic tank. The system installation will include a 2000-gallon, two-compartment concrete septic tank with an Orenco@ Biotube Pump Vault and an Orenco@ PF3005 pump in the second compartment of the septic tank. The floats should be set to dose approximately 80 gallons each pump cycle, allowing approximately 2 gallons of drain back after each pump cycle. A pump curve is enclosed. The control panel for the pump must be located within line of sight of the septic tank. We recommend Valley Precast out of Buena Vista be contracted for start-up of the pumping system. A 1.S-inch diameter Schedule 40 pump line must be installed from the pump to an Orenco@ automatic distributing valve (ADV), model 6402. This pump line must have a minimum 1o/o grade for proper drain back into the tank after each pump cycle. The ADV must be placed a high point in the system in an insulated riser with access from grade. Screened rock must be placed below the ADV to support the ADV and to assure the clear pipes existing the ADV remain visible for future inspection and maintenance. OWTS Gomponent Minimum Elevation Primary Tank lnlet lnvert Approximate horizontal distance 55' / min. 2% fall I min. 13.75" fall Automatic Distributing Valve Approximate horizontal distance 15'/ min. 1% rise for drain back / min. 1.875" rise lnfiltrative Surface Approximate horizontal distance to furthest bed 16' / min. 1o/o'fall I min. 2" fall Dose Range Max = 171 gal. (675 GPD x25o/o + 2 qallons drain back) Min. 62 gal. (15 gal x 4) + 2 gat drain back Dose Setting 80 gallons/dose 2 gallons drain back (15' I 1.5" diameter oumo line) Float Separation 2000 gallon 2-compartmet Valley Precast concrete septic tank 6" on/off float separation Pump Criteria 31.4 gallons per minute (GPM)22.8 feet total dynamic head ffDH) Page 6 Effluent will be pressure dosed through 1.5-inch diameter pipes to two beds, each with 2 rows of 17'Quick 4' Standard Plus Low Profile lnfiltrator@ chambers, for a total of 68 chambers and 816 square feet of infiltrative area. There must be at least 6-feet of undisturbed soil between each bed. Efflueni will be pressure dosed to 1.S-inch diameter laterals, which must be hung with zip ties from the underside of the chambers. Laterals will have 5/32-inch diameter orifices facing up, with the exception of the first and last holes facing down for drainage. Orenco@ Orifice Shields may be placed under each downward-facing orifice. The orifices must be placed 3-feet on center. Each lateral must end in a g0 degree ell facing -up with a ball valve for flushing. Valves may be placed in a valve box, accessible from grade, for accesl. ' lnspection ports must be placed at the beginning and end of each trench. Ports may Oe cut to grade and covered with a valve box for access. COMPONENT SPECIFICATIONS The component manufacturers are typical of applications used by contractors and engineers in this area GBO lnc. must approve alternative components prior to instatlation of the OWTS. Requests must be submitted, in writing, to our office for approval prior to installation. Gomponent technical data sheets are available upon request. Construction must be according to Garfield County On-Site Wastewater Treatment System Regulations, theowrs Permit provided by Garfield county Building Department, and this design. INSTALLATION CONTRACTOR CBO lnc. expects that the installer be experienced and qualified to perform the scope of work oulined in this design. The installer must review this design thoroughly and coordinate with our office in advance of installation. Any additional conditions in this design or county permit must be completed and documented prior to final approval of the OWTS installation. Communication between the installer and this office is expected throughout the installation. INSTALLATION OBSERVATIONS CBO lnc. must view the OWTS during construction. The OWTS observation should be performed before backfill, afier placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. CBO lnc. should be notified 48 hours in advance to observe the installation. COMPONENT MANUFACTURER MODEL NO.COMMENTS Septic Tank Valley Precast Item # 2000T-2CP-HH 2-compartment concrete reptic tank with high read pump Pump Orenco@ PF300511%HP 120 Volt Biotube ProPak Pumo Packaoe Orencoc)BPP3ODD dose Tank Risers and Lids Orenco@ Double-walled PVC Risers and -ids (24" diameter) Orenco@ v64024 1.5" lnlet and Outlets an Orenco@ Double-walled PVC Risers and Lids (30" diameter) Orenco@ Ol'150 1.5 inch diameter (84 total) (Jrenco(D 1.5" diameter (2) 45" or 90" long sweep only (4 total) Chambers lnfiltrator@ 68'Quick 4' Low Profile chambers Page 7 ln an effort to improve the accuracy of the record drawing, we request that the installer provide asketch of the installation, including path of the sewer lines, water line installation (ii applicable), septic tank location, STA location, and measurements from building corners or another fixed gbjects on the property. This sketch is most easily provided on Sheet W2.0 of the OWTS DesignPacket' Photographs of the installation and final cover are also requested to supplement our installation documentation. REVEGETATION REQU IREMENTS An adequate layer of go_o! l_uality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of nativre grais seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and fompetes well wit6 successional species. No trees or shrubs, or any vegetation requiring regular inigation shatibe placed overthe STA' Until vegetation is reestablished, erosion and sediment control measires shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing theproperty' The property owner is responsible for maintaining service contracts for manufactured inits, alternating STAs, and any other components needing maintenance. Geo-fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials should be placed on the backfilled STA. Machines with tracks (not wheels) should be used during construction of the STA for better weight distribution. Livestock should not graze on the STA. plumbin! fixtures should be checked to ensure thit no additional water is being discharg6U to OWTS. For example, I running toilet or leaky faucet can discharge hundreds of gallons of waler a daylnd harm a STA. lf an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. lf the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed. The homeowner should pump the septic tank every two yearc, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non-biodegrada-ble mate1als should not be placed into the OWTS. Grease should not be placed in household drains. toading from a water softenershould not be discharged into the OWTS. No hazardous wastes should Oe OirdcteO into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES lf design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk offreezing. The pump shall have an audible and visual alarm notification in the event of excessively high- water conditions and shall be connected to a control breaker separate from the high-water alarm breakerand from any other control system circuits. The pump system shall have a switCh so the pump can be manually operated. Excavation equipment must not drive in the excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing graOe. Backfill over the STA must be uniform and granular with no material greater than minus 3-inch. Page 8 LIMITS: The design is based on information submitted. lf soil conditions encountered are different from conditions described in report, CBO lnc. should be notified. All OWTS construction must be according to the countyregulations. Requirements not specified in this report must follow applicable county relulations. The contractor should have documented and demonstrated knowledge of the requirementianJregulations ofthe county in which they are working. Licensing of Systems bontractors may be required-by countyregulation. Please call with questions. Sincerely, CBO lnc.Reviewed By (auta }xfu"/rE t Carla Ostberg, MPH, REHS Romeo A. Baylosis, PE T-27-2022 l at*388U' Pump Selection for a Pressurized System - Singte Famity Residence Project Coon Residence Parameters 1.25 15 40 1.50 6402 J 40 1.50 2 3 40 1.50 4 68 40 1.50 5132 3 5 None 0 Galculations 100 300Discharge Assembly Size Transport Length Before Valve Transporl Pipe Class Transport Line Size Distribuling Valve Model Transport Length After Valve Transport Pipe Class Transport Pipe Size Max Elevation Lift Manifold Length Manifold Pipe Class Manifold Pipe Size Number of Laterals per Cell Lateral Length Lateral Pipe Class Lateral Pipe Size Orifice Size Orifice Spacing Residual Head Flow Meter 'Add-on' Friction Losses feet inches inches inches feet inches inches feet feet inches feet inches feet feet feet 250 150 50 PumpData 5 10 15 20 25 Net Discharge (Spm) 30 35 40 200oolr IoF tt(!o .9 E G o 6 oF Minimum Flow Rate per Orifice 0.68 NumberofOrificesperZone 46 Total Flow Rate per Zone 31.4 Number of Laterals per Zone 2 % Flow Differential 1st/Last Orifice 3.5 Transport Velocity Before Valve 4.9 Transport VelocityAfter Valve 4.9 Frictional Head Losses gpm gpm fps fps Loss through Discharge Loss in Transport Before Valve Loss through Valve Loss in Transport after Valve Loss in Manifold Loss in Laterals Loss through Flowmet€r 'Add-on' Friction Losses Pipe Volumes 6.9 0.9 7.4 0.2 0.0 0.4 0.0 0.0 00 feet feet feet feet feet feet f€et feet Vol of Transport Line Before Valve Vol of Transport Line After Valve Vol of Manifold Vol of Laterals per Zone Total Vol Before Valve Total Vol After Valve |quirements 31.4 22.8 1.6 0.3 0.3 14.4 1.6 15.0 gals gals gals gals gals gals PF3005 High Head Effluent Pump 30 GPM, 1/2HP 11 5/230V 16 6OHz, 200Y 36 6OHz PF3007 High Head Eflluent Pump 30 GPM,3/4HP 230V 10 60H2, 200/460V 30 60Hz PF3010 High Head Effluent Pump 30 GPM, 1HP 230V 1O 6OHz,2OO|46OV 30 6OHz PF3015 High Head Effluent Pump 30 GPM, 1-1l2HP 230V 1O 60H2,20012301460V 3O 60Hz gpm SYSTEMSn 'l I j \? System Curve: - Pump Curve: * Pump Optimal Range:- Operating Point: O o Design Point: feet N tf--ErEr-_l SCALE: 1 = 50'=O' DMWINGS MUST BE USED IN CONJUNCTION WTH DESIGN LETTER DATED O 1 IO1 12022 t .t .f,ot 2 t LINE I i RESIDENCE .> I I t(tc 6f THE LOCATION OF PROPOSED Ii,IPROVEMENTS SHOWN ARE NOT THE RESULT OF A PROPERTY SURVEY. THE LOCATIONS ARE APPROXIMATE. lT lS THE HOMEO\,r,NERS DUTYTO ENSURE ALL CONSTRUCTION AND IMPROVEMENT LOCATIONS ARE ACCURATE. PROPERTY LINES AND SEIBACK OISTANCES SHOULD BE CONFIRMED PRIOR TO EXCAVATION, SCALED FOR PRINTING ON 1,I'X 17" PAPER. .trot 2 SI w1 .0 CBO lnc. 129 Cains Lane Carbondale, Colorado 81 623 Phone 970.309.5259 €da.ostberg@gmail.com ltz.0 ( I Ff, .s\9 .$ .s +$ lE STA TP3 SEPTIC TANK 2 TP1 Y Sc la Coon Residence Lot 3, Rapids on the Colorado Garfi eld County, Colorado ProjectNumber: C1682 Designed by: CBO Dalei 0110112022 by: RB DD Reviewed Drawn by:Sheet 1 0F 4 PROFILE CHAMBER BEDS CONNECTED WITH A LEVEL MANIFOLD. EACH BEO HAS 2 ROWS OF 17 'QUICK 4' CHAMBERS FOR A TOTAL OF 68 CHAMBERS AND 816 SQUARE FEET, 1,5'DIA SCH.4O SUSPENDED LATERALS WITH 5/32' DIA ORIFICES, 3'O.C FACING UP. FIRST AND LAST ORIFICES FACING DOWN FOR DRAINAGE COVERED WITH AN ORIFICE SHIELD. 2OOO.GALLON 2.COMPARTMENT SEPTIC TANK WITH AN ORENCO PUMP PACKAGE IN THE SECOND COMPARTMENT RISERS AND LIDS TO GRADE / /t rwo (2) Low 1.5" DIA SCH-40 PUMP LINE, 1.5" DIA SCH4O PVC DISTRIBUTION LINE TO EACH BED 1.5" DIA SCH.4O LEVEL MANIFOLD (MIN 1% DRAIN BACK TO TANK)/t AOV MODEL 6402 AT HIGH POINT, ACCESSIBLE AT GRADElt TP3 6' rP2+ ,I.BEDROOM RESIDENCE FF 100' (5503.5) CBO lnc. 129 Cains Lane Carbondale, Colo€do 81 623 Phone 970.309.5219 carla.ctb€rg@gmail.com Coon Residence Lot 3, Rapids on the Colorado Garfield County, Cdorado Project Number: C1682 Date: 0110112022 by: CBO by: RB DD Designed Reviewed Drawn by: TP.I 87 FLUSHING VALVE AT END OF EACH LATEML INSPECTION PORT AT CORNER OF EACH BED LINE o t 03s .01 A(2 DRIVEWAY 4" DIA SDR-35 SEWER PIPE WTH CLEANOUT MIN 2% FALL TO TANK. SEWER LINES CONNECTED WITH WYE FITTING BEFORE ENTERING SEPTIC TANK\-\ / ..N/? w2.0 N i-----ffia@ffir----l SGALE: 1'= 20'4" Sheet 2 0F 4 ,I.5'DIA. SCH-40 PUMP LINE FROM TANK (MIN- IYO DRAIN BACK TO PUMP CHAMBER) il02 ADV WITH ACCESS ATGME 1.5'DIA SCH.4O PVC SUSPENDED LATEMLS WTH 5A? ORIFICES FACING UP 3' O.C. FIRST AND LAST ORIFICES FACE OOWN FOR DRAINAGE AUICK4(TM) LOW PROFILE END CAPS INFILTMTOR(R) CHAMBERS, 3' X 4' LOW 6' INSPECTION PORT AT CORNER OF STA END EACH LATERAL IN A 90" SWEEPING ELL FACING UP WTH A BALL VALVE FOR FLUSHING STA TO WATER COURSE 50'124', STA TO WELL 100 STA TO HOUSE 20'55', SEPTIC TANK TO WATER COURSE 50'1U', SEPTIC TANK TO WELL 50' HOUSE TO SEPTIC TANK 5' OWTS COMPONENTS AND PHYSICAL FEATURES MINIMUM REQUIRED SETBACK APPROXIMATE PROPOSEO SETBACK DIA VALVE BOX WTH SECURED LID PVC SLIP X MALE PIPE THREAD ADAPTERWCAP ,I.5" DIA BALL VALVF 1.5'DIA PVC LONG SWEEP 90'BEND 1.$ DIA SCH-40 PVC DISTRIBUTION LINE FROM ADV 1.5'DtA SCH-40 PVC LEVEL MANIFOLD BACKFILL WTH NATIVE MATERIAL 34 CHAMBERS EACH BED 4\CHAMBER BED PLAN\rr--------rF;G FOR (MUST BE MTNUS S|NCH OR TOPSOIL 4' DIA SDR 35 PVC INSPECTION PORT AT FLUSHING ASSEMBLY INFILTMTOR(R) QU|CK4CTM) LOW PROF|LE CHAMBER, 3'X4 DIA SCH.4O PVC SUSPENDED EACH CORNER OF EXTENT OF EXCAVATION SCARIFY SURFACE 2' INSTALL DISCHARGE PIPE AND VALVE ECCENTRIC TO CENTER OF VAULT END CAP /iCHAMBER BED SECNON\5r---._anet TATEMLS WTH 582' ORIFICES FACING UP 3 O,C. FIRST AND LAST ORIFICES FACE DOWN FOR DRAINAGE. SUSPEND WTH ZIP TIES /.\ FLUSHING VAL\E DETAIL\9r--i6.ffi w3.0 CBO lnc. '129 Cains Lane Carbondale, Colorado 81 623 Phone 970.309"5259 €da.ostberg@gmail.com Goon Residence Lot 3, Rapids on the Colorado Garfi eld County, Colorado Project Number: C1682 by: by: RB DD 01t01/2022 by: CBO Sheet 3 0F 4 SMALL VALVE COVER BOX OR IRRIGATION VALVE BOX AT GMDEDESIGN 4AEDROOM RESIDENCE + 1 FUTURE BEDROOM 75 GPD x 2 PERSONS/BEDROOM x 4 BEDROON,TS = 52S GpD 75 GPD x 2 PERSONS/BEDROOM x,I BEoRooM = 150 GPD WASTEWATER FLOW = 675 cpD TANK; MIN. 15OO GALLONS USE 2OOO-GALLON, TWO-COMPARTMENT CONCRETE SEPTIC TANK WTH ORENCO PUMPING SYSTEM IN THE SECOND COMPARTMENT SOIL TREATMENT AREA (STA): LONG TERM ACCEPTANCE RATE (LTAR) = 0.6 GAU sF CALCULATED STA = Q/LTAR = 675 / 0.6 = 1 125 SF PRESSURE DOSED, BEDS = 1 i25 SF X i.0 = 1 12S SF CHAMBERS = 1.125 SF X 0.7 = 788 sF / 12 sF / CHAMBER = MIN.66 GHAMBERS TWO GMVELLESS CHAMBER BEDS 2 ROWS OF 17'QUICK 4'CHAMBERS IN EACH BED TOTAL 68 'QUICK 4' CHAMBERS SOIL PROFILE TEST Pfi NO. 1 SOIL PROFILE TEST PIT NO- 2 LIGHT BROWI\ LOAM LIGHT BROWN LOAM LIGHT BROWN LOAM WTH INCREASING PERCENTAGE OF COBBLES FINISHED GRADE 24'MtN. 3'MtN. /AIRENCH DETAIL\r-------nrrs SOIL PROFILE TEST PIT NO, 3 LIGHT BROYVN LOAM LIGHT BROWN LOAM WTH INCREASING PERCENTAGE OF COBELES 4'PVC PIPE CUTTO FIT (DlISeEc'ltoN_Pos*cH AM BER AUTOI\,IATIC DISTRIBUTING VALVE ASSEI\4BLY 1.5'DtA SCH40 PVC INLET AND OUTLETS 4" DIA SDR.35 SEWER (MrN 2olo SLOPE TO TANK, MrN. 1% TO STA) SCREENED COI\,IPACT END BASE TO SUPPORT BOX USE HOLE SAWTO CUT THRU TOP OF CAP OR THR€ADED CLEANOUT ASSEMBLY VAL\E DETAIL FINISHED GRADE HOUSE OR SA}ID FOR BEDDING 8' 0 30" DIAMETER PVC RISER FROM PUMPING SLIP.ON PVC DO NOT GLUE INSULATED TMCERwlRE 4'DIA SEWER LINE 2 4 5 6 LIGHT BROWN LOAM WTH INCREASING PERCENTAGE OF COBBLES I NO GROUNDWATER OR BEDROCK ENCOUNTERED DURING EXCAVATION TOTANK 10 LEGEND fiil r@m /.\CLEANOUT DETAIL\7ASOILS LOG\rr--ft,ft w4.0 CBO lnc. 129 Cains Lane Carbondale, ColoEdo 81 623 Phone 970.309.5259 cada.ostberg@gmail.mm Coon Residence Lot 3, Rapids on the Colorado Garfi eld Gounty, Colorado ProjectNumber: C1682 Date: 0110112022 Designed by: CBO by: RB DD Reviewed Drawn by:Sheet 4 0F 4 111t22,9..53 AM Summary Account Parcel Property Address Legal Descriptlon Acres Land SqFt Tax Area MillLevy Subdivlsion View Map Owner COON, BENJAMIN DON & BRUCKER COON, ERICA 222 BLACKHAWK DRIVE NEW CASTLE CO 81547 Land Unlt Type 1 AC TO VT 5 AC - 0520 (VACANT LAND) Square Feet 0 Actual Values Assessed Year Land Actual lmprovement Actual Total Actual Assessed Values Asressed Year Land Assessed lmprovement Assessed TotalAssessed Tax History Jbx Year Taxes Billed qPublic.net - Garfield County, CO - Property Record Card: R17O35S 6qPublic.net'" Garfield County, CO R170355 218104307003 ,NEWCASTLE,CO 81647 Section;4Township: 6 Range: 91 Subdivision: RAPIDS ON THE COLORADO Lot: 3 2.329 o T7 62.32rO RAPIDS ON THE COLORADO Click here to view the tax information for this @ Transfers 202L $825.t2 2020 $s30.40 20.2r $45,640.00 $o.oo $4s,640.00 2027 $13,240.00 $0.00 $13,240.00 20L9 $s09.12 2020 $32,s60.00 $0.00 $32,560.00 2020 $9,440.00 $o.oo $9,440.00 201A $664.24 2079 $32,s60.00 $0.00 $32,560.00 2079 $9,440.00 $o.oo $9,440.00 20t7 $56s.80 Sale Price $210,000 Sale Date 8/t2/202t 6/70/2027 70/20t2003 72/28/200r 9/8/t997 9/8/L997 9/5/L997 9/3/L997 70/74/L996 6/75/1992 tl/8/7974 77/8/L974 7t/7/7974 Reception Number 96L620 958023 639203 594733 513354 513353 s1?3s5 573352 499822 435827 265351. 265350 265246 Book - Page t316-983-987 7032-0948 7032-096t 7032-0945 o996-0665 0834-0233 0466-0207 o466-0204 0466-0029 Deed Type SPECIAL WARRANTY DEED EASEMENT Plat SPECIALWARRANTY DEED SUBDIVISION I MPROVEMENTS Plat QUITCLAIM DEED SPECIAL WARRANTY DEED RESOLUTION RESOLUTION WARRANTYDEED WARRANryDEED WARRANry DEED $o $o $o $o $o $o $o $o $o $o $o $o No data available for the following modules: Buildings, photos, Sketches. https://qpublic.schneidercorp.com/Application.aspx?ApplD=1038&LayerlD=22381&PageTypelD=4&pagelD= 9447&Q=1755240261&KeyVatue=R170355 1t2 '1,11122,9:53 AM qPublic.net - Garfield County, CO - Property Record Card: R170355 The Gadreld CountyAssessor's Office makes every e{fort to produce the most accurate information possible, No warranties, expressed or implied ar€ provided for the data horeih, its rse or interpretation. Data is subject tD constert change and its accuracy and completeness cannot be guaranteed. Developed bys)Mrr User Prlvacy Policy GDPR Prlvacy Notlce Last Data upleesli!:UzXuL!2ggg!&Version 2.3.168 https:i/qpublic.schneidercorp.com/Application.aspx?ApplD=1038&LayerlD=22381&PageTypelD=4&PagelD=9447&Q=1755240261&KeyValue=R170355 212 d G)qPuhlic.ttet"" Garfield County, CO Account Number Parcel Number Acres Land SqFt Tax Area 2019 Miil Levy R170355 218104307003 2 0 o77 62.32LO Physical Address Owner Address 0 NEWCASTLE COON, BENJAMIN DON & BRUCKER cooN, ERIcA 222BLACKHAWK DRIVE NEW CASTLE CO 81647 Overuiew s Legend i ! parcets Roads Parcel/Account Numbers Highways - Limited Access - Highway Major Road Local Road Minor Road Other Road Ramp * " Ferry Pedestrian Way Owner Name i j Lakes&Rivers - CountyBoundary Line 2019Total Actual $45,640 Last 2Sales Value Date Price B'J.647 8/72/2027 $210,000 6/to/2o2r $o Date created: llU2O22 Last Data Uploaded: I/7/2Q222:O3:53 AM Deve roned bv(;:) gS!,gFjdgl