HomeMy WebLinkAboutManual JHVAC Load Calculations for Brad Jordan Residence 587 Elk Springs Drive Garfiled County, Co RHVAC REETpENTIAL HVAC LoLpe N N d' Prepared By: M. Dunne MDA Design Consulting, LLC 5001 N Blazingstar Trail Gasfle Rock, Co- 80109 888-903-6255 Wednesday, May 21,2O25 Rhvac is an ACCA approved Manual J, D and S computer program. Calculations are performed perACCA ManualJ 8th Edition, Version 2.50, and ACCA ManualD. Rhvac - Resldential & Llght Commercial HVAG Loads MDA Desiqn Consultins, LLC G Ellte Software Development, lnc. Designed By: Project Date: Client Name: Client Address: Client City: Company Name: Company Representative: Company Address: Company City: Company Phone: Company E-Mail Address: Company Website: MDA 5-20-25 Brad Jordarr Residerrtu 587 Elk Springs Drive Garfiled County, Co MDA Design Consulting, LLC M. Dunne 5001 N Blazingstar Trail Castle Rock, Co.80109 888-903-6255 mdu nne@mdadesignconsulti ng.com MDA Design Consulting.com Reference City: Building Orientation: Daily Temperature Range Latitude: Elevation: Altitude Factor: 40 6500 0.786 Garfield County, Co Front door faces North High Degrees ft. Outdoor Outdoor Outdoor Dry Bulb Wet Bulb Rel.Hum-2 -3 nla98 65 19Yo lndoor Rel.Hum nla 50% lndoor Grains Dry Bulb Difference Winter: .Summer:70 70 rr/a -5 Building Supply CFM:z, tot CFM Per Square ft.:0.725 * 604 **Square ft. of Room Area: 3,817 Square ft. per Ton: Volume (ff): 34,353 " Based on area of rooms being heated or cooled (whichever governs system) rather than entire floor area. "j Based on area of rooms being cooled, Total Heating Required lncluding Ventilation Air: TotalSensible Gain: Total Latent Gain: Total Cooling Required lncluding Ventilation Air: 67,954 Btuh 48,731 Btuh 10,702 Btuh 59,433 Btuh 67.954 MBH 82 o/o 18 o/o 4.95 Tons (Based On Sensible + Latent) Rhvac is an ACCA approved Manual J, D and S computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2.50, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\,..\Rifle-Garfie ... 5-20-25.110 Wednesday, May 21, 2025, 9:42 PM Rhvac - Residential & LlghtCommercial HVAC Loads MDA Design Consulting, LLC Castle Rock. CO 80109 * Ellte $oftware Development, lnc, Paoe 3 Load Preview Report Scope Net Ton ft., ffor Area Sen Gain Lat Gain Net Gain Sen Loss sys Htg CFM sys clg CFM sys Act CFM Buildinq Svstem'1 Misc. Supplv Zone I 1-Main Fl-Foyer 2-Main FFqreat Rm 5-Main FFPantrv 6-Main Fl-Laundrv Rm 7-Main Fl-Mud Rm 8-Main FFPowder Rm 9-Main Fl-Bedrm 1 -of{ice 10-Main Fl-closet interior 11-Main FFmstr Bedrm 12-Main Fl-mstr Balhrm 13-Main Fl-Garaqe Svstem 2 Misc. Supplv Zone 2 3-Main Fl-Dininq Rm 4-Main Fl-Kitchen 1 4-Lower Level-entertainment Rm 1S-Lower Level Guest Master Bdrm lGlower Level Bath #1 17-Lower Level Closet '18-Lower Level Storaqe-mech Rm 1 g-Lower Level Bath *i2 2O-Lower Level Closet 21-Lower Level Bedrm #2 4.95 2.53 48,731 25,534 0 25,534 2,755 4,801 620 1,747 924 1,'t 16 3,993 616 5,566 3,396 o 23,197 0 23,197 4,702 3,093 6,281 3,729 788 407 503 447 438 2,809 10,702 4,836 3,000 1,836 't92 779 -5 -2'l -8 -13 372 0 365 175 0 5,866 3,000 2,866 788 554 773 384 4 -2 -5 4 4 386 59,433 30,370 3,000 27,370 2,47 5,580 620 1,747 924 1,116 4,365 616 5,931 3,571 0 29,063 3.000 26,063 5,490 3,647 7,Oil 4.113 788 407 503 447 438 3,195 67,954 48,499 1,497 934 2,167 1.135 2,167 1.13s 604 3,817 625 2,410 2,410 294 340 60 100 40 50 182 90 270 156 a28 48,499 4,1't8 5,587 886 2,286 731 1,343 4,204 841 5,833 3,609 19,061 1,135 't22 213 28 78 41 50 178 27 247 151 0 1,031 1,03'l 209 138 279 166 35 18 22 20 19 125 19,455 934 1,135 79 122 108 213 17 28 44 78 14 41 26 50 81 178 16 27 112 247 70 151 367 0 562 1,0312-42 581 1,407 1.407 180 238 u0 195 50 30 .119 50 25 180 19,455 4,095 3,193 4,206 3,244 396 261 614 396 363 2,687 562 118 92 122 94 11 I 18 1',| 10 78 1,031 209 138 275 166 35 18 22 20 19 125 C:\ ...\Rifle-Garfie ... 5-2O-25,r1O Wednesday, May 21, 2025, 9:42 PM Rhvac - Residential & Light Gommercial HVAG Loads MDA Desiqn Consultino. LLC Elite Sofhrarc Development, lnc^ Total Buildin Loads Component fuea Sen Lat Sen Total 4A-5f-o' Glazing-Double pane low-e (e = 0.20 or less), operable window, e=0.05 on surface 2, insulated fiberglass frame, outdoor insect screen with 50% coverage, nredium color blinds at 45" with 75% coverage, U-value 0.27, SHGC 0.31 4A-5f-o: Glazing-Double pane low-e (e = 0.20 or less), operable window, e=0.05 on surface 2, insulated fiberglass frame, U-value 0.27, SHGC 0.31 111: Door-Wood - Panel With Metal Storm, U-value 0.36 11D: Door-Wood - Solid Core, U-value 0-39 12F-6sw: Wall-Frame, R-21 insulation in 2 x 6 stud cavity, R-6 board insulation, siding finish, wood studs, U-value 0.048 12F-6sw: Part-Frame, R-21 insulation in 2 x 6 stud cavity, R-6 board insulation, siding finish, wood studs, U- value 0.048 ceiling-attic fl : Partition Roof/Ceiling (STD=1 0, WTD=30F Under Attic with lnsulation on Attic Floor (also use for Knee Walls and Partition Ceilings), Custom, My first examnle r:r rsfnm ronf I l-vahre. 0 27 19D1-2Scsr-v: Floor-Over enclosed crawl space, R-19 insulation on exposed walls, spray foam insulation, sealed crawl space, rudiarrt, R-25 ulosed cell 2 lb. spray foam, 4 inches in 2 x 10 joist cavity, vinyl covering, U-value 0.043 '1 9D1-2Scsr-c: Floor-Over enclosed crawl space, R-1 9 insulation on exposed walls, spray foam insulation, sealed crawlspace, radiant, R-25 closed cell2 lb. spray foam, 4 inches in 2 x 10 joist cavity, carpet covering, U-value 0.043 CustomFloor3-c: Partition Floor (STD=O, WTD=30FSlab on grade, Custom, My third example custom floor, carpet covering, U-value 0.05 19D1-27osr-c: Floor-Over enclosed crawl space, R-19 insulation on exposed walls, spray foam insulation, sealed crawl space, radiant, R-27 open cell l12lb. spray foam, 7 inches in 2 x 10 joist cavity, carpet covering, U-value 0.04 'l9D-19sr-c: Floor-Over enclosed crawl space, R-19 insulation on exposed walls, sealed crawl space, rpdia4t,8-19 bla!:rket, carpqt qqlering, Urvalue 0.053 Subtotals for structure: People: Equipment: Lighting: Duciwork: lnfiltration: Winter CFM:212, Summer CFM: 109 Ventilation: Winter CFM: 0, Summer CFM: 0 498 9,680 0 8,121 8,121 176 3,421 0 4,s01 4,501 18 184 2363 467 5,167 8,166 0 0 0 220 0 1,673 220 0 1,673 950 1,128 0 433 433 2828 22,907 0 5,400 5,400 294 762 828 340 649 365 0 105 105 947 0 273 273 1,242 0 0 0 413 0 119 119 856 0 246 246 54,759 0 4,800 '161 21,091 5,520 2,777 16,709 0 2,634 0 0 48,731 21,491 10,320 2,938 16,709 0 2,375 0 6,000 59,433 24 4900 1 3, 0 195 0 0 0 -259 0 6,000 10,702 Supply Misc. Gain: Total Building Load Totals:67,954 Total Building Supply GFM: 2,167 CFM Per Square ft.: Square ft. of Room Area: 3,817 Square ft. Per Ton: Volume (ft3): 34,353 " Based on area of rooms being heated or cooled (whichever governs system) rather than entire floor area. 0.725 * 604 ** C:\ ...\Rifl+.Garfie ... 5-20-25l10 Wednesday, May 21,2025,9:42 PM ** Based on area of rooms being cooled Total Heating Requ ired lnclud ing Ventilation Air: TotalSensible Gain: Total Latent Gain: Total Cooling Required lncluding Ventilation Air: 67,954 Btuh 48,731 Btuh 10,702 Btuh 59,433 Btuh 67.954 MBH 82 o/o 18 Yo 4.95 Tons (Based On Sensible + Latent) Rhvac is an ACCA approved Manual J, D and S computer program. Calculations are performed perACCA ManualJ 8th Edition, Version 2.50, and ACCA ManualD. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturefs performance data at your design conditions. Cl ...\Rifle-Garfie ... _5-20-25.11 0 Wednesday, May 21, 2O25, 9:42 PM 1 - Main Level Gooling: Outdoor Dry Bulb: OutdoorWet Bulb: lndoor Dry Bulb: Indoor RH: Supply Airflow: 8E 65 70 50 1,220 Sensible Gain: Latent Gain: TotalGain: Load SHR: Entering Dry Bulb: Entering Wet Bulb: 25.534 4.836 30.370 0.84 72 60 Heating: Outdoor Dry Bulb: lndoor Dry Bulb: lndoor RH: -2 70 30 Sensible Loss: Entering Dry Bulb: Supply Airflow: 48.499 70.0 934 This system's equipmentwas selected in accordancewith ACCA Manual S. Cooling: Model Type: Air Source Heat Pump-VRF, Outdoor Model: LMU420HHV, lndoor Model: (2) 6MBH,(3) 4MBH Nominal Capacity: 42.000, Manufacturer: LG lnterpolation Results: Sensible Capacity: Latent Gapacity: TotalCapacity: 27.OOO 15_000 42.OOO Load 25.5U 4.836 30.370 Percent of Load 1060/o 31Oo/o 138o/o Heating: Model Type: Air Source Heat Pump-VRF, Model: LMU420HHW, Nominal Capacity: 55.000, Manufucturer: LG Results: PercentLoad ofload Heating Capacity: 55.000 48.499 1'l3o/o C:\ ...\Rifle-Garfie ... 5-20-25.110 Wednesday, May 21, 2025, 9:42 PM Rhvac - Resldential & Ught Commercial HVAG Loads MDA Design Consulting, tLC Castle Rock, CO 8O1OS * Ellte Software Development, lnc. Paqe 7 S 2 - Lower Level Gooling: Outdoor Dry Bulb: Outdoor Wet Bulb: lndoor Dry Bulb: lndoor RH: Supply Airflow: 88 65 70 50 1,220 Sensible Gain: Latent Gain: TotalGain: Load SHR: Entering Dry Bulb: Entering Wet Bulb 23.197 s.866 29.063 0.80 72 60 Heating: Outdoor Dry Bulb: lndoor Dry Bulb: lndoor RH: -2 70 30 Sensible Loss: Entering Dry Bulb: Supply Airflow: 19.455 70.0 562 This system's equipment was selected in accordance with ACCA Manual S. Cooling: Model Type: Air Source Heat Pump-VRF, Outdoor Model: LMU3OOHHV, lndoor Model: 07MBH,(3) 4MBH,(1) 6 MBH Nominal Capacity: 30.000, Manufacturer: LG lnterpolation Results: Sensible Capacity: Latent Capacity: TotalCapacity: 27.OOO 3.000 30.000 Load 23.197 5.866 29,063 Percent of Load 1160/o 51% 1O3o/o Heating: ModelType:Air Source Heat Pump-VRF, Model: LMU3000HHW, NominalCapacity:40.000, Manufacturer: LG Results: PercentLoad ofload Heating Capacity: 40.000 19.455 206% C:\ ...\Rifle-Garfie ... 5-20-25.110 Wednesday, May 21, 2025, 9:42 PM Rhvac - Residential & Light Gommercial HVAG Loads MDA Design Consultinq, LLC s Elite So'fhrarc Development, lnc- S 1 Room Load Htg Min Htg Run Duct Run Duct cls clg Lat Min clg Act sysRoomArea Sens Sens ---Zone 1--- 1 Main Fl-Foyer 2 Main Fl-great Rm5 Main Fl-Pantry 6 Main Fl-Laundry Rm 7 Main Fl-Mud RnrI Main Fl-Powder Rm 9 Main Fl-Bedrrn 1- office 10 Main Fl- closet_interior 11 Main Fl-mstr Bedrm 12 Main Fl-mstr Bathrm 13 Main Fl-Garage Misc Supply Gain System 1 total 294 340 60 100 182 90 270 .l5A 828 4,118 5,597 886 2,286 4,204 841 5,833 ? Ano 19,061 79 108 17 44 81 16 112 7n 367 1E1 0 4 E.lrut 2-O 2-O 1-0 1-0 122 213 28 78 122 213 28 78 0 0 0 0 0 0 0 0 0 al 0 2,755 4,801 620 1.747 924 1,1 16 3,993 616 5,566 ? aoA 0 -B -13 372 0 365 17tr 0 3,000 4,836 0 192 779 -5 -21 40 50 731 1,343 14 26 1-0 1-0 41 50 41 50 178 178 27 27 247 247 2-O 1-0 3-0 2-O 0-0 0 2,410 48,499 934 25,534 1,135 1,135 Cooling Sensible/Latent Sensible Latent Total Net Required: Actual: 2.53 3.50 84% I 16% 760/" I 24V" 25,534 32,000 4,836 10,000 30,370 42,000 Model: lndoor Model: Brand: Description: Efficiency: Sound: Capacity: Adjusted Capacity: Sensible Capacity: Adjusted Sensible Capacity: Latent Capacity: Adjusted Latent Capacity: Heating System Heating System LMU42OHHW LG vrf split heat pump system 0 30 55,000 Btuh nla nla nla nla nla Cooling System Cooling System LMU42OHHV (2) 6MBH,(3) 4MBH LG Air cooled vrf heat pump with mated indoor units 20 SEER 30 42,000 Btuh 42,000 Btuh 32,000 Btuh 27,000 Btuh 10,000 Btuh 15,000 Btuh This system's equipment was selected in accordance with ACCA Manual S. ManualS equipment sizing data: SOI)B:98F, SOWB:65F, WODB:-2F, SIDB: 70F, SIRH:50%, WIDB:70F, Sen. gain 25,534 Btuh, Lat. gain;4,836 Btuh, Sen. loss:48,499 Btuh, Entering clg. coilDB: 70F, Entering clg. coilWB: 57.4F, Entering htg. coil DB: 70F, Clg. coil TD: 26F, Htg. coil TD: 60F, Req. clg. airflow: 1135 Cl-M, Req. htg. airflow: 934 CFM C:\ ...\Rifle-Garfie ... 5-20-25-11O Wednesday, May 21, 2025, 9:42 PM Rhvac - Residential & Llght Commercial HVAC Loads MDA Design Consulting, LLC * Elite So,fhrare Development, lnc. 2 Room Htg Min Htg Run Duct Run Duct clg CIg Lat Min cls Act sysRoomArea Sens Sens F ---Zone2-- 3 Main Fl-Dining Rm 4 Main Fl-Kitchen 14 Lower Level- entertainment Rm 15 Lower Level Guest Master Bdrm 16 Lower Level Bath #1 17 Lower LevelCloset 18 Lower Level Storage-mech Rm 19 Lower Level Bath #2 20 Lower LevelCloset 180 238 340 4,095 3,193 4,206 118 92 122 2-O 2-O 3-0 2-O 0 0 0 0 4,702 3,093 6,281 788 554 773 209 138 279 209 138 279 195 3,244 94 3,729 788 407 503 447 384 166 166 50 396 11 1-0 0 0 0 0 0 0 4 -2 -5 4 4 386 35 35 30 119 261 614 8 1-0 1-0 18 22 18 2218 50 396 11 1-0 20 20 21 Lower Level Bedrm #2 25 180 363 2,687 10 78 1-0 2-O 438 2,809 19 125 19 125 Misc Supply Qain System 2 total 1,407 19,455 562 0 3,000 23,157 5,866 1,031 1,031 Net Required: Actual: 2.42 2.50 BOY' I 2OYo 73Yo I 27o/o 23,197 22,000 5,866 8,000 29,063 30,000 Model: lndoor Model Brand: Description: Heating System Heating System LMU3OOOHHW Cooling System Cooling System LMU3OOHHV 07MBH,(3) 4MBH,(1) 6 MBH LG Air cooled vrf heat pump with mated indoor units 20 SEER 30 30,000 Btuh 30,000 Btuh 22,000 Btuh 27,000 Btuh 8,000 Btuh 3,000 Btuh LG vrf split heat pump system Efficiency: Sound: Capacity: Adjusted Capacity: Sensible Capacity: Adjusted Sensible Capacity: Latent Capacity: Adjusted Latent Gapacity: 0 30 40,000 Btuh nla nla nla nla nla This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODB: 9BF, SOWB:65F, WODB: -2F, SIDB: 70F, SIRH: 50%, WIDB: 70F, Sen. gain 23,197 Btuh, Lat. gain: 5,866 Btuh, Sen. loss: 19,455 Btuh, Entering clg. coil DB: 70F, Entering clg. coilWB: 57.4F, Entering htg. coil DB: 70F, Clg. coilTD:26F, Htg. coilTD:40F, Req. clg. airflow: 1031 CFM, Req. htg. airflow: 562 CFM Cooling Tons Sensible/Latent Snlit Sensible Btuh Latent Btuh Total Btuh C:\ ...\Rifle-Garfie ... 5-20-25l'10 Wednesday, May 21,2025,9:42 PM ,- '._/ -_- /4CCF\" Form RPER 1.OI 8 Mar 10AaMSCMdM County, Town, Municipality, Jurisdiction Header lnformation Gontractor Mechanical License # Building Plan #Sys.1 Home Address (Street or Lot#, Block, Subdivision) Rifle-Garfield Gounty, Co REQUIRED ATTACHMENTS1 Manual Jl Form (and supporting worksheets): YesE or MJIAE Form2 (and supporiing worksheeto): Yes! OEM performance data (heating, cooling, blower):Ynsl8 Manual D Friction Rate Worksheet: Yes[ Duct distribution system sketcfr: yesfl AfiACHED uon ruoE runfl ruoE r.roE Residential Plans Examiner Review Form n (Loads, Equifor HVAC S ment, Ducts)tem Desi HVAC LOAD CALCULATION rRC M 1401.3) fresign Conclitions Winter Design Gonditions Outdoor temperature lndoor temperaiure Totral heat loss tiummer Design Conditions Outdoor temperature lndoor temperature Grains difference Sensihle heat gain Latent heat gain Total heat gain Ruilding Construction I nformation Building Orientation (Front door faces) North, Easl, West, South, Northeast, Nodhwest, Southeast, Soulhwest Number of bedrooms 2 Conditioned floor area lZl I fl Sq ft4P'49.9 Btu/h 98 "F OF -5 AGr@S0 %Rh 2 5?4 F F Number of occupants Windows Eave overhang depth 4 Blinds Roof Ft Btu/h Btu/h Btu/h <- 4836 htterlral shade Blinds, dEpes, etc Eave Depth Window 30370 Number of skylights 0 H\/AC EQI-IIPME\IT SELECTIONI (IRC N41401.3) Heating Equipment fiata Equipment type Air Source Heat Pump-VRF Fume, Heat pump, Bciler, elq. Model LMU42OHHV Heating output capacity 55OOO Cooling Equipment Fratei Equipment type Air Source Heat Pump-VRF Air Condilions, Heat pump, etc Model LMU42OHHV Blower Data Heatins cFM 1 1 00 CFM coorins cFM 1 200 cFM Heat pumps - €pacity at winlq dosign ould@rmditions Auxiliary heat output capacity Sensible cooling capacity Latent cooling capacity Total cooling capacity Btu/h 15000 Btu/h 42OOO Btu/h Btu/h Btu/h HVAC DUCT D|STRIBUT|ON SYSTEM DEStcN (lRC M1601.1) Design airflow CFM External Static Pressure (ESP) IWC Component Pressure Losses (CPL) IWC lra r^AYarilarurG Jrcrrc rressure [ADF, lYYv ASP=ESP-CPL Longest supply duct: Longest return duct: Total Effec{ive Length gEL} Friciion Raiel F iction Faale = (ASP r 100); TEL Duct Materials Used (circle) Trunk Duct: Duct board, Flex, Sheet metal, Lined sheet metal, Other (specify) Branch Duct: Ducl board, Flex, Sheet metal, Lined sheet meta!, Other (spcciiy) Ft Ft Ft lVVtr ldeclare the load calcr tlation eqrripmerrt selection, arrd duct system design,,vere rigorously por-formcd baccd on thc brrilcling plan listecl irls rnade on thesa forrrs will be cLr verificationabove. I r"tnderstarrd the Contractor's Printed Name Contractor's Signature Date Reserved for use by CoLtn Town. Mur-iicipality, or ALrthority havinq lurisdictiortlTheAHJhave the discretion to accepl Required Attrachments printed fiom approved ACCA software vendors, see list on pag€ 2 u6od for load calculatlon, then verity residence meets requirements, see Abridged Edllion Ctiecttist of instructions. on page 13 of inslruclions.' lf abidged version o[ Manual J ls Form generated by ACCA-approved Manual J Eighlh Edition version 2 Elite software Rhvac program. ,t=. /4CCF\. Form RPER 1.01 8 Mar 10 ATTACHED ruoI uoE &MiECffiffid!ffi County, Town, Municipality, Jurisdiction Header lnformation Contractor Mechanical License # Building Plan #Sys.2 Home Address (Streel or Lot#, Block, Subdivision) Rifle-Garfield County, Co REQUIRED ATTACHMENTS1 ManualJl Form(andsupportingworksheets): YesE or MJIAE Formz (and supporting worksheets): yesL OEM performance data (heating, cooling, blower):YesEl Manual D Friction Rate Worksheet: yesfl Duct distribution system sketct: yesE ruoE noE r'roE Residential Plans Examiner Review Form for HVAC S stem Desi n utLoadsE ment Ducts HVAC LOAD CALCULATTON (rRC M 1401.3) Design Conditions Winter Design Conditions Outdoor temperature lndoor temperature Total heat loss Summer Design Conditions Outdoor temperature lndoor temperafure Grains difference Sensible heat gain Latent heat gain Total heatgain 1 9455 "F OF Btu/h ? Ruilding Construction lnformation Building Orientation (Front door faces)1 North, East, West, South, Northeast, Northwest, Southeast, Southwest Number of bedrooms 2 Conditioned floor area I {fl/ Sq Ft 98 70 -5 AGr@50 %Rh ??197 Number of occupants Windows Eave overhang depth Ft lntemal shade Blinds, dEpes, etc Blinds Number of skylights 0 OF OF Roof <- 5866 Btulh Btu/h Btulh Eave Depth Window 2906.3 HVAC EQUIPMENT SELECTTON (rRC N/1401.3) Heating Equipment Data Equipment type Air Source Heat Pump-VRF Fumace. Heat pump, Boiler, etc. Model LMU3000HHW Heating output capacity 4OOOO Conling Eqr tipment l-tata Equipment type Air Source Heat Pump-VRF AirCondilioner, Heat pump, elc Model LMU3OOHHV Blower Data Heating cFM 600 CFM coolins cFM 1000 CFM Heat pumps - @pacity at winter design outdmr @ditions Auxiliary heat output capacity Sensible cooling capacity Latent cooling capacity Total cooling capacity Btu/h Btu/h 27000 Btu/h Btu/h Btu/h Snnn 30000 HVAC DUCT DTSTRTBUTTON SYSTEM DESIGN (lRC M1601 .1) Design airflow CFM External Static Pressure (ESP)lwc Component Pressure Losses (CPL) IWC Available Static Pressure (ASP) IWC ASP=ESP-CPL Longestsupplyduct: _ Ft Longest return duct: _ Ft Total Effective Length (TELI _ Ft Friction Rate: IWC Duct Materials Used (circle) Trunk Duct Duct board, Flex, Sheet metal, Lined sheet metal, Other (specifY) Branch Duct: Duct board, Flex, Sheet metal, Lined sheet metal, Other (specifY) tr'"tion 3219 = (ASP x 100) r TEL I declare the load calculation, equipment selection, and duct system design rvere rigorously performed based on the building plan listed above I urrrderstand the clairns rrade on to review and verification Contractofs Printed Name Contractor's Signature Date Reserved for use by County. Town. Municipality. or ALithority having lurisdiction 1 The AHJ shall have the discretion to accept Requlred Attachments printed ftom approved ACCA software vendors. see list on page 2 of instructions., lf abridged version ot Manual J is used for load calculation, lhen veriry residence meets requiremenls, see Abridged Edition Checklist on page 13 of instruciions. Form generated by AccA-approved Manual J Eighth Edition Version 2 El;te Software Rhvac program. /+-. /4CCF\" Form RPER 1.01 8 Mar 10 ATTACHED vesEl NoI At()]ffii4MNotM Contractor County, Town, Municipality, Jurisdiction Header lnformation Mechanical License # Building Plan # REQUIRED ATTACHMENTS1 Manual J1 Form (and supporting worksheets): or MJlAE Formr (and supportng worksheets): OEM performance data (heating, cnolinc, hlower): Yesn vesE Yes! tr tr Sys. 1 Manual D Friction Rate Worksheet: No No No NoDuct distribution system sketch:YesE Home Address (Street or Lot#, Block, Subdivision) Rifle-Garfield County, Co Residential Plans Examiner Review Form for HVAC S Estem Desi n Loads UI ment, Ducts HVAC LOAD CALCULATION UMC 1 106 1) Iresign Conditions Winter Design Gonditions Outdoor temperature lndoor temperafure Total heat loss Summer Deslgn Condltlons Outdoor temperature lndoor temperature 2"F 7n "F Btu/h 98 "F 70 "F Grains rtifference -5 A Gr @ 50 % Rh sensibleheatgain 255}{. Btu/h Latent heat gain Total heat gain 4R36 Btu/h 3n37O Btu/h Rr rilding COnsfrtrction InfOrmatinn Building Orientation (Front door faces)I North, East, West, South, Northeast, Northwest, Southeast, Southwesl Number of bedrooms 2 )2t{ fl sq Ft Roof Ft Conrlitioned flnnr arca Number of occupants Windows Eave overhang depth lnternal shade Blinds, dmpes, elc Blinds Number of skylights 0 Eave Depth Window HVAC EOUIPMENT SELECTION Heating Fquif'menf Dala Equipmenttype Air Source Heat Pump-VRF Fumae, Heat pump, Boiler, elc. Model LMU42OHHV Model Heating output capacity OnO Btu/h Coolin$ Fq uipment [rata Equipment type Air Source Air Condiliffi, Heat pump, etc Sensible cooling capacity Latent cooling capacity Total cooling capacity Blower Data Heatins cFM 1 1 00 CFM cooring cFM 1 200 cFM Pump-VRF LMU42OHHV HBat pumps - €paclty at wintsr design outd@r Mditions Auxiliary heat output capacity Btn/h 27OOO Btu/h 1 SOO0 Btuih 4 OOO Btu/h HVAU UUCT DtSTRtBUTION SYSTEM DEStcN (UMC 601.2 Design airflow External Static Pressure (ESP) Component Pressure Losses (CPL) Arrailqlrla Glatia Oraaar.ra rAaDrrErJu.E l^sry ASP=ESP-CPL CFM lwc twc llAr/^ Longestsupplyduct: _ Ft Longest return duct: -- Ft Total Effective Length fIEL) Ft E-iJ:^- d^.-, llltr/^rrr9lr9l! n4lEr luu\, tn"*n 6119 = (ASP x 100) + TEL Duct Materials Used (circle) Trunk Duct Duct board, Flex, Sheet metal, Lined sheet metal, Other (specify) Branch Duct: Duct board, Flex, Sheet metal, Lined sheet metal Other (soecitu) I declare tlre load calculaliurr. equiptrrerrl selection, arrd ducl syslem clesiqn rvere rigorolsly performed baseci on the herildinq plan listed above und the clair-ns nrade on these forrns wi h Cl t,.) f FViF\^' and verifiCatiorr Contractor's Printed Name Contractor's Signature Date Reserved lor use by CoLrrrty. Town, Mrrnrcipalily or ALrthority havi ng jurlsdiction I The AHJ shall have the dlscrelion to trom approved ACCA softlvare2 lf abridged version of Manual J is used for load calculation, then residence meets requiremenls, see vendors, see list on page 2 Abddged Edition Checklist of instructions. on page 13 of instructlons. Form generated by AccA-approved Manual J Eighth Edition Version 2 Elite Sonware Rhvac program. A. /4CCF\. Form RPER 1.01 8 Mar ,l0 ATTACHED uo!I DI E ehknE@WcdM County, Town, Municipality, Jurisdiction Header Information Contractor Mechanical License # Building Plan #Sys.2 Home Address (Street or Lot#, Block, Subdivision) Rifle-Garfield County, Go REQUIRED ATTACHMENTSI Manual J'l Form (and supporting worksheets): VesE or MJ1AE Formz (and supporting worksheets): Yes! OEM performance data (heating, cooling, blower):YesEl Manual D Friction Rate Worksheet: Yeslj Duct distribution system sketc*t: yes! No No No No Residential Plans Examiner Review Form for HVAC S ment, Ductstem Desi UInLoadsE HVAC LOAD CALCULATION (UMC 1106 1 l-tesign Conditions Winter Design Gonditions Outdoor temperature lndoor temperature Total heat loss Summer Design Gonditions Outdoor temperature lndoor temperafure Grains difference Sensible heat gain Latent heat gain Total heat gain 98 70 -5 AGr@50 %Rh 2"197 Btu/h 5866 Btu/h 29063 Btu/h Br dlding Constructinn lnformation Building Orientation (Front door faces)1 North, East, West, South, Northeast, Northwest, Southeast, Southwest Numberofbedrooms 2 Conditionedfloorarea {{fl/ Sq Ft Number of occupants Vllindows Eave overhang depth Roof Ft Blinds 2 7A oF 19455 Btu/h "F OF "F lntemal shade Blinds, dEpes, etc Eave Depth Window Number of skylights 0 HVAC EQUIPMENT SELECTION Heafing Equipment Data Equipment type Air Source Heat Fumace, Heat pump, Boiler, etc. Model LMU3000HHW Heatins output capacity 4OOOO Btu/h Heat pumps - Epacity at winter design outdmr @rditions Auxiliary heat output capacity Btu/h Conling trquipment frata Pumo-VRF Equipment type Air Source Heat Pumo-VRF Air Conditioner, Heat PumP, etc Model Blower Data Healing CFM 600 cFM LMU3OOHHV coolins cFM 1000 CFM nnn Btu/h Btu/h 30000 eturt Sensible cooling capacitY Latent cooling capacity Total cooling capacitY HVAC DUCT DISTRIBUTION SYSTEM DESIGN (UMC 601.2) Design airflow _ CFM External Static Pressure (ESP) IWC Component Pressure Losses (CPL) IWC Available Static Pressure (ASP) ASP=ESP-CPL twc Longest supply duct: Longest return ducl: Total Effec{ive Length (TEL} Friction Rate: Fr'ction Rate = (ASP x 100) + TEL Duct Materials Used (circle) Trunk Duct Duct board, Flex, Sheet meial, Lined sheet metal, Other (sPecifY) Branch Duct: Duct board, Flex, Sheet metal, Lined sheet metal, Other (sPecifY) Ft _Ft _Ft twc I declare the load calculation. equipment selection. arrd ducl system design rvere rigorously per{ormed based on the building plan listed these forrrs will be s revien, and verificationabove. I understand the clait.trs Contracto/s Printed Name Contractor's Signature Date Reservecl for use by County Town, Municipality, or Authority having lurisdiction ' The AHJ shall have the discretion vendors, see list on page 2 Abridged Edition Checklist of instructions. on page 13 of instructions.' lf abridged version of Manual J is Form generated by AccA-approved Manual J Eighth Edition Version 2 Elite Soflware Rhvac program.