HomeMy WebLinkAboutOWTS Design ReportMOUNTAIN CROSS
ENGINEERING, INE.
Civil and Environmental Consulting and Design
William & Catherine Kenworthy
223W. Menomonee St.
Chicago, IL 60614
June23,2025
R!:CHM:1.]
RE:Kenworthy Residence, Lot 21 Ranch at Coulter Creek,
Garfield County, CO - OWTS Report
.jtjhl {J ? J{l?5
GAI:- trtF:: l.-f,i [:'.-r i ;']
CC[i,,ilillil'r' i.ii-Vi-i i,i. ,'' '
Dear Mr. & Mrs. Kenworthy:
The purpose of this correspondence is to inform you about the onsite wastewater treatment system
(OWTS) designed for the Kenworthy Residence.
The project proposes to construct a new residence located in Garfield County, Lot2l in the Ranch
at Coulter Creek subdivision off of Saddle Drive. The main and upper floors of the residence will
be a gravity system to a conventional septic tank where a pump will pressure dose to a leach field
comprised of a sand filter bed. There is no lower/basement level proposed. If a basement is
constructed in the future, it will need a sewer ejector to pump into the OWTS. The residence will
be served from an existing community water system. The OWTS is not within a 100-year flood
plain boundary. There are practical constraints that you should be aware of when considering the
propsr design, construction, and operation.
Subsurface
The soil was determined to be R-2 with 2A' soils; rocky, silty sandy to very silty sand. This
corresponds to a long-term acceptance rate (LTAR) approximated as 0.50 gallons per day per
square foot (GPD/sq.ft.) from soil evaluations performed Kumar and Associates. Their analysis
was done in a different location than the designed location. A profile hole will need to be excavated
and an inspection performed to verify that the design location has similar soils and that that no
bedrock nor groundwater is within an 8' depth of the leaching area. A copy of the soils report is
attached.
Desisn Calculations
The residence is proposed to be 3 bedrooms with a 1 bunk room (4 beds). Using Garfield County
Table 6-1 for a S-bedroom residence, this yields 600 gallons per day (GPD) total. The design
calculations for sizing of the septic system and the leach field follow:
o Kenworthy Residence: 5 bedrooms: 600 GPD
o Based on soil evaluation and percolation tests results, LTAR: 0.50 GPD/sq.ft.
o Minimum absorption area : 600 GPD / 0.50 : 1,200 sq. ft.
o No reductions are allowed for rocky soils.
o Required septic tank volume : 1,500 gallons per Garfield County Table 9-l
o Dosing frequency:4 doses per day; dose volume : 600 GPD / 4 doses : 150 gal./dose
o Pump(s) should provide 35 gpm at25' of Total Dynamic Head
826f, Grand Avenue, Glenwood Springs, CO 81601
P: 970.945.5544 F: 970.945.5558 www.mountaincross-eng.com
Kenworthy Residence
Jrtne,2025
Page 2 of3
. PVC lateral supply and distribution pipes should be Schedule 40,l-112" in diameter.
o Each lateral pipe should have seven /t" diameter holes drilled in the lateral at7' spacing
with the first hole located at 4' from the start of the bed'
The components manufacturers are typical for the area. Alternatives may be considered by
contacting this office. Construction must be in accordance with the specifications of Garfield
County Environmental Health, the OWTS permit, and this design'
Topsoil should be placed over the OWTS and planted with native grasses. No large vegetation
andlor plants with taproots should be planted over the absorption area nor grasses that require
excessive irrigation. Calculations are attached.
Setbacks
The location for the septic and dosing tanks are limited by setback requirements per Garfield
County and the State of Colorado. These include:
o 50' FROM WELL
o 10' FROM WATER SUPPLY LINE
o 5, FROM BUILDING WITH BASEMENT
o l0' FROM PROPERTY LINE
o 10' FROM LINED POND, DITCH, OR STREAM
o 50' FROM WATER BODY
o 10' FROM CREST OF BANK
o 5, FROM LEACH FIELD
o 100' FROM WELL
o 25'FROM WATER SUPPLY LINE
o 20, FROM BUILDING WITH BASEMENT
o 10' FROM PROPERTY LINE
o 10' FROM LINED POND, DITCH, OR STREAM
o 50' FROM WATER BODY
o 25'FROM CREST OF BANK
o 5,FROM SEPTIC TANK
The setback requirements deal primarily with buildings and potential contamination from the
septic tank, dosing tank, and leach field to either culinary water or surface water. These setbacks
have been included on the plans for reference.
Oneration Infor and Maintenance
The Owner will need to be responsible for the operation and management of the OWTS. Geo-
fabrics or plastics should not be used over the absorption area. No heavy equipment, parking of
machinery, or materials should be placed on the absorption area. Livestock should not graze on
Mountain Cross Enoineering. lnc.
Civil and Environmental Consulting and Design
826'/, Grand Avenue, Glenwood Springs, CO 81 601
P: 970.945.5 544 F : 970.945. 5558 www. mountaincross-eng.com
The leach field setback requirements are:
l(cu worthy l{csitlcltcc
.ltrtrc,2025
l)age .3 ol J
the llrsorlrtiorr area. PlLtnlbing lixtrrres shoLrld hc checl<c:d 1o etrsttLe that tto aclditionnl water is
lrcing clischirrgerl to OSi'lS; firr exanrplc, runring triilcts ot' lcnk1, flttccts catt tlischiu'gc ltuttrlrcds
of gallons o1'rvatcr a rlaf illill ltarnt the absorptioti arca.
Garbagc clisposal use shoulcl be rrrinirrrizccl. and non-bioclegraclahlc ntatet'izrls sltottlcl ltot be placetl
inlo (lrc (lW'l'S, (ircirse should n<rt bc plncccl in rlrains aurl glcasc traps shoulcl bc irrstallcd
upstrcaln of thc scptic tanlt llut clorvnstlcnrtt ll'ottt any hitchcn. l,oacling ltnttt a rvntcr sollcltcr
shoulcl nol lre clischargecl into thc OW'['S. No har.arclrrus rvastcs sltoulcl bc dilcctccl into tltc OW'l'Si.
't'hc OW'l'S is engitrcet'ecl [irr tbrucstic rvastc ortly.
-l'lrc Orvncl rvill lilccly necrl to contract r.vith a sc:ptic systcnr clcancl to cican thc sc;ltic tanl< evcty
{wo years, ur ls nscclcd garrgcrd b}, ,,-r.'r",tt'c:ntertt ol- solids irr the latrl<. 'l'hc sl.attchrtls ol'
pcrfirlrrrancc lirr'1he sclttic systcru clc,ancr ilt$ r'cL:onrrtctttlctl to lrc thc hrllorvilrg, a[ a nriltitttttnr:
l. 'l'he Systcrrrs (lkrarter shnll be licensecl,
2. 'l'hc Systcrtrs (llcRnrjl', \\,hen clcarting a scptic tatrk, shrtll l'elrlove tlrc liclrrid. slutlge, ltttl
sculn, lcaving nc) morc than thlcc (3) inchcs rlcpth o1's*va14c in a scptic tanl<.
l. 'l'hc Systcnrs Cleaner^ shall rnaintain his crluipntcttt sct as to cttsulc that no spillagc o1'
st:1ys1g$ rvill ocrcur clLn'ing trnnsporlatit-rn, itrttl tlrtrt il,s cnrltlol,ecs irrc rtot sulrject tii uttclurr
lrcallh hazitrcls.
4. 'l'hc Systr:nrs Lllcnncl sliall disposc ol thc collcotccl sowago ortly lt tt dcsigttatcil ,silc
rccognizccl try thc IJoarcl o1'llcallh.
(l gns t ru ctio rL O b.scrv a tio rr
l'rior to bcing lrackllllerl, lhc constnrctiorr ol thc OW'l'S and all ol'tltcr c:onrpottcnls lvill ncctl to [rc
obscrverl by reltresentatirres ol' Mountaitt Ct'oss Iingirtcct'irrg, Ittc.
'l'hc conclrrsions anrl opiniolis that r-u'o cxpresssrl itblrvc flrs Lritsccl ott thu inlirrrttitlion avirilnblc at
tlrc tirne of ltrcpnlation o1'this rcllolt. Any acklitiortal ittlcrrntittiott pt'cscntcel it{icrt'nat'tl tttity t'celuirr:
lhll llrese opirtiotts attcl tlte tlcsigrt bc rutrcliliccl.
'l'hnnl< yorr l-ul tlic oppor'tunily to provitlc lhis lcport. ll'ccI li'r-,c to call il'1,,-rt, l]nvc ntt)'rlttcsliotts,
c() ltcclls, oL r:ttp'l nterilts.
Sinccrc:ly,
/r4ottttl
tt, ,
\..
lr
in ( lros,'^ Iitt nt!ittg, lttt:
I Ialc:. Irli
lz
Mourrtain Cross Engineering. lnc.
Civil anrJ Envlronrnental Oonsultlng and Deslgn
826 lt Grand Avenue, Glertwood Springs, CO 81601
P : 970.945,5544 F: 970.945.5558 www, tnotttttaitrcross'errg.conr
)fls
Step 1: Flows
MOUNTAIN CROSS
ENGINEERING, INC.
Givil and Environmental Consulting and Design
826 l/2 Grand Avenue Glenwood Springs, CO 8160'l
ph 970.945.5544 tx 970.945.5558 w,mountaincroe*ng.mm
5 Bedrooms
10 assumed people
600 gallons per day
4 doses per day
150 gallons perdose
7466.5
7462.5
7461.9
7458.22
DOSING DESIGN CALCULATIONS, foT
Lot 21 Coulter Creek Ranch, Garfield County, CO
6t21t2025
Table 6-1
Step 2: BOD5
'10 persons
600 gpd used by residence
BOD5 for domestic uses:
0.2 lb/person/day from CDPHE
Step 3: Dosing Basin
Third Compartment of Septic Tank
70 inch length
38 inch width
18.47 square feet
depth of dose volume =
lnvert at dosing tank
Sump = bottom of third compartment
Pump "Off' 1
Pump On "Lead" Float 2.09
Pump On "Lag" Float 2.59
High Alarm (min) 3.09
High Alarm (max) in -12" 1.00
minutes of run time per dose =
(5 minute rule of thumb)
Step 4: Elevations, Orifices, and Head loss
Septic Tank Rim Elevation =
High Point Elevation =
lnvert at dosing =
SumP =
Elev Diff = y',.3 feet
Length from pump to leach field of 1-1-2" =
Length of 1-112" in leach field =
1-112" fittings in equivalent pipe length:
0.6 average day in gallons per minute
1.25 peak day in gallons per minute
2.50 peak hour in gallons per minute
2 lb BODS/day
138.2 gallons per foot of depth
1.09 feet of depth in manhole
4.3
7462.30
7458.22
7459.22
7460.30
7460.80
7461.30
7461.30
35 gpm
Design analysis for only one of leaching areas
50 feet
212 feet
check 90 90 check 90 gate tee 4-45
13.4 4 4 13.4 4 1.1 8.1 B.B
Equivalent 2" Length from pump = 140.7 feet
from Fig F, using 8.82 ft of friction head per 100' of 2" plastic pipe =
from Fig F, using 0.83 ft of friction head per 100' of 1-112" plastic pipe =
check
13.4
2-tee
16.2 86.4 feet
12.4 head loss @ 35 gpm
1.8 head loss @ 9 gpm
1.04 gpm
Dynamic Head (TDH) 18.5 system condition use TDH of 25 feet
Per Table 7-13 in OWTS Design Manual, 114 " dia. orifice @2' of Head yields
4 Laterals 7 orifices per lateral 29.12 gpm
Step 5: Velocity verification
35 gpm in 1.5 inch pipe
0.012 -- area
0.078 = flow in cfs
6.355 = velocity in feet per second, must be greater than 2.0 feet per second
but less than 10 feet per second
9 gpm in 1.5 inch pipe
0.012 = area
0.020 = flow in cfs
1.634 = velocity in feet per second
Step 6: Pipe Volume & Drain Back
assume only drainback from d-valve
Discharge Assembly Size
Transport Length
Transport Pipe Class
Transport Line Size
Distributing Valve Model
Max Elevation Lift
Manifold Length
Manifold Pipe Class
Manifold Pipe Size
Number of Laterals per Cell
Lateral Length
Lateral Pipe Class
Lateral Pipe Size
Orifice Size
Orifice Spacing
Residual Head
Flow Meter
'Add-on' Friction Losses
Pump Selection for a Pressurized System - Single Family Residence Project
Parameters
1.50
50
40
1.50
None
5
12
40
1.50
4
50
40
1.50
114
8
2
None
5.6
Galculations
Minimum Flow Rate per Orifice 1.09
Number of Orifices per Zone 28
Total Flow Rate perZone 30.8
Number of Laterals per Zone 4
% Flow Differential l sulast Orifice 1 .7
Transport Velocity 4.9
Frictional Head Losses
gpm
gpm
inches
feet
inches
feet
feet
inches
feet
inches
inches
feet
feet
inches
feet
100
90
80
70
oool!r60oFd
{Ed,.50
.9
El!
o40
E
o
o/o
fps
30
20
10
Loss through Discharge
Loss in Transport
Loss through Valve
Loss in Manifold
Loss in Laterals
Loss through Flowmeter
'Add-on' Friction Losses
Pipe Volumes
2.8
2.7
0.0
0.2
0.1
0.0
5.6
feet
feet
feet
feet
feet
feet
feet 0 02040 60 80 100
Net Discharge (Spm)
120 140 160
Vol of Transport Line
Vol of Manifold
Vol of Laterals per Zone
Total Volume
5.3
1.3
21.2
27.7
gals
gals
gals
gals
PumpData nd
PFEF40 Effluent Pump
4t10HP,1151230V 1@
Minimum Pump uirements
Design Flow Rate
Total Dynamic Head
30.8
18.5
gpm
feet
I
l
I
I
I
I
I
I
I
I
/
LI I J
I
I
I
A
{/)
System Curve: -
Pump Curve: ' '
PUmp uptrmal Hange:
Operating Point:
o
Design Point:
rcn Kumar & Associales, lnc.'
Geotechnical and Materials Engineers
and Environmental Scienlists
An Employse Owned Compony
5020 County Road 154
Glenwood Springs, CO 81601
phone: (970)945-7988
fax: (970) 945-8454
ernail : kaglenwood@kumarusa.com
rvu'n,. k ttntaru sa. cott.t
Office Locations: Denver'(HQ), Parker, Colorado Springs. Fort Collins, Clenwood Springs, and Surnrnit County, Colorado
October 21,2021
Lisa McPherson
78 River Glen
Carbondale, Colorado 81623
ldrn47 4 5 (rD,i c I oud. corr
Project No.2I-7-764
Subject: Subsoil Study for Foundation Design, Proposed Residence, Lot2l, Ranch at
Coulter Creek, Saddle Drive, Garfield County, Colorado
Dear Ms. McPherson:
As requested, Kumar & Associates, Inc. performed a subsoil study for design of foundations at
the subject site. The study was conducted in accordance with our agreement for geotechnical
engineering services to you dated September 16,2021 The data obtained and our
recommendations based on the proposed construction and subsurface conditions encountered are
presented in this report.
Proposed Construction: Residence building plans were not available at the time of our study.
In general, a single-family residence is proposed in the northeast part of the lot roughly between
the exploratory borings located as shown on Figure 1. Ground floors could be a combination of
structural over crawlspace and slab-on-grade. Cut depths are assumed to range between about2
to 6 feet. Foundation loadings for this type of construction are assumed to be relatively light and
typical of the proposed type of construction.
If building conditions or foundation loadings are significantly different from those described
above, we should be notified to re-evaluate the recommendations presented in this report.
Site Conditions: The subject site was vacant at the time of our field exploration. The proposed
building site is a broad hilltop with gentle to moderate side slopes down away from Boring 2
shown on Figure 1. Vegetation consists of sagebrush, grass and scrub oak with basalt rocks
exposed on the ground surface throughout the lot including the proposed building area.
Subsurface Conditions: The subsurface conditions at the site were evaluated by drilling
2 exploratory borings at the approximate locations shown on Figure 1. The logs of the borings
are presented on Figure 2. The subsoils encountered, below about 4 inches of topsoil, consist of
dense basalt gravel, cobbles and boulders in a calcareous sand and silt matrix to the maximum
boring depth of 7 feet. Drilling in the dense cobbles and boulders was difficult and practical
-2-
auger refusal was encountered in the borings. Results of gradation analyses performed on small
diameter drive samples of the sand and silt matrix soils (minus llz-inch fraction) of the coarse
granular subsoils are presented on Figure 3. The laboratory test results are summarized in
Table 1. No free water was encountered in the borings at the time of drilling and the soils were
slightly moist.
Foundation Recommendations: Considering the subsoil conditions encountered in the
exploratory borings and the nature of the proposed construction, we recommend spread footings
placed on the undisturbed natural rocky soil designed for an allowable bearing pressure of 2,500
psf for support of the proposed residence. Foundation settlement potential should be low, up to
around 1 inch. Footings should be a minimum width of 16 inches for continuous walls and 2 feet
for columns. The topsoil and loose disturbed soils encountered at the foundation bearing level
within the excavation should be removed and the footing bearing level extended down to the
undisturbed natural rocky soils. Voids created by boulder removal should be backfilled with
compacted road base or concrete. We should observe the completed building excavation for
bearing conditions prior to forming footings. Exterior footings should be provided with adequate
cover above their bearing elevations for frost protection. Placement of footings at least 36 inches
below the exterior grade is typically used in this area. Continuous foundation walls should be
reinforced top and bottom to span local anomalies such as by assuming an unsupported length of
at least 12 feet. Foundation walls acting as retaining structures should be designed to resist a
lateral earth pressure based on an equivalent fluid unit weight of at least 50 pcf for the on-site
soil as backfill, excluding organics and rock larger than 6 inches. A sliding coefficient of 0.45
and equivalent fluid lateral passive earth pressure of 375 pcf can be used to resist lateral loading
on the foundation.
Floor Slabs: The natural on-site soils, exclusive of topsoil, are suitable to support lightly loaded
slab-on-grade construction. To reduce the effects of some differential movement, floor slabs
should be separated from all bearing walls and columns with expansion joints which allow
unrestrained vertical movement. Floor slab controljoints should be used to reduce damage due
to shrinkage cracking. The requirements for joint spacing and slab reinforcement should be
established by the designer based on experience and the intended slab use. A minimum 4-inch
layer of free-draining gravel should be placed beneath basement level slabs to facilitate drainage.
This material should consist of minus Z-inch aggregate with less than 50o/o passing the No. 4
sieve and less than 2%o passing the No. 200 sieve.
All fill materials for support of floor slabs should be compacted to at least 95o/o of maximum
standard Proctor density at a moisture content near optimum. Required fill can consist of the
onsite soils devoid of vegetation, topsoil and oversized rock or imported gravel such as road
base.
Kumar & Associates, lnc, @ Project No. 21-7-764
-3-
Underdrain System: Although free water was not encountered during our exploration, it has
been our experience in the area that local perched groundwater can develop during times of
heavy precipitation or seasonal runoff. Frozen ground during spring runoffcan create a perched
condition. We recommend below-grade construction, such as retaining walls, crawlspace and
basement areas, be protected from wetting and hydrostatic pressure buildup by an underdrain
system.
The drains should consist of drainpipe placed in the bottom of the wall backfill surrounded above
the invert level with free-draining granular material. The drain should be placed at each level of
excavation and at least 1 foot below lowest adjacent finish grade and sloped at a minimum Io/o to
a suitable gravity outlet. Free-draining granular material used in the underdrain system should
contain less than ZVo passing the No. 200 sieve, less than 50% passing the No. 4 sieve and have a
maximum size of 2 inches. The drain gravel backfill should be at least 1/z feet deep.
Surface Drainage: The following drainage precautions should be observed during construction
and maintained at all times after the residence has been completed:
1) Inundation ofthe foundation excavations and underslab areas should be avoided
during construction.
2) Exterior backfill should be adjusted to near optimum moisture and compacted to
at least 95o/o of the maximum standard Proctor density in pavement and slab areas
and to at least 90o/o of the maximum standard Proctor density in landscape areas.
Free-draining wall backfill should be covered with filter fabric and capped with
about 2 feet of the on-site, finer graded soils to reduce surface water infiltration.
3) The ground surface surrounding the exterior of the building should be sloped to
drain away from the foundation in all directions. We recommend a minimum
slope of 12 inches in the first 10 feet in unpaved areas and a minimum slope of
3 inches in the first 10 feet in pavement and walkway areas.
4) Roof downspouts and drains should discharge well beyond the limits of all
backfill.
5) Landscaping which requires regular heavy irrigation should be located at least
5 feet from the building. Consideration should be given to the use of xeriscape to
limit potential wetting of soils below the foundation caused by irrigation.
Limitations: This study has been conducted in accordance with generally accepted geotechnical
engineering principles and practices in this area at this time. We make no warranty either
express or implied. The conclusions and recommendations submitted in this report are based
upon the data obtained from the exploratory borings drilled at the locations indicated on Figure 1
and to the depths shown on Figure 2, the proposed type of construction, and our experience in
Kumar & Associates, lnc. ^Project No. 21-7-764
4-
the area. Our services do not include determining the presence, prevention or possibility of mold
or other biological contaminants (MOBC) developing in the future. If the client is concerned
about MOBC, then a professional in this special field of practice should be consulted. Our
findings include interpolation and extrapolation of the subsurface conditions identified at the
exploratory borings and variations in the subsurface conditions may not become evident until
excavation is performed. If conditions encountered during construction appear different from
those described in this report, we should be notified at once so re-evaluation of the
recommendations may be made.
This report has been prepared for the exclusive use by our client for design purposes. We are not
responsible for technical interpretations by others of our information. As the project evolves, we
should provide continued consultation and field services during construction to review and
monitor the implementation of our recommendations, and to verify that the recommendations
have been appropriately interpreted. Significant design changes may require additional analysis
or modifications to the recommendations presented herein. We recommend on-site observation
of excavations and foundation bearing strata and testing of structural fill by a representative of
the geotechnical engineer.
If you have any questions or if we may be of further assistance, please let us know.
Respectfully Submitted,
Kumar & Associates, Inc.
Steven L. Pawlak, P.E.
Reviewed by:
Daniel E. Hardin, P.E.
SLP/kac
Attachments: Figure 1 - Location of Exploratory Borings
Figure 2 - Logs of Exploratory Borings
Figure 3 - Gradation Test Results
Table 1 - Summary of Laboratory Test Results
Kumar & Associates, lnc. ^Project No. 21-7-764
l:l
::.
!
!
:
.l
5STELLOF I
TRACT D
ttt$).w1 q746l{' 1
ENft@r Ef,bTAn 7
a.aarg,ril
*o.r&tto
Fi
{
ril! vsfrt
T hEMI
Ju rat
rl tB
tna ns969q
:mra Htr^t
( ibo
€G rD.cl
l!s
\rrn"n
I LL ttL,
Ldt t6 a4
I
I
I
,
I
II Lpr18
I
I
I
I
I
I
I
I
I
I
I
tr. cstArct Mli 4r mir G ,4lm aoNret
rlr Y qtE &m! nuE N trct' q ilffI Srd qlr ffffiati'o E6a n, ffi ^t a
I 3!!tr rl@!r -adr4{ rt@lr-o_N_tlaoJ.,_n!,
50 0 50 100
APPROXIMATE SCALE _FEET
f--rf;lr7-+-*--r-rtr;r.Fir_hl
uzt^tridr.---\\\\\_
BORING 2
o
FfEIIa Altft alL3 r:llt I
I
I
BORING 1
O tor 2t
Zq02a .$rlt
&2la oc'',tt
v c xf, t{.TD
I
I
I
I
t
.bt
i?E8r
4t R atattI Artnl Ct'Lr lrart ,l
er
El
t
I
I
t
I
t
I\,
L'
fi
(+,.
tt'
v\
ral .t.l, cxal arl{
i--{!i
ffitD,|lln(nql ?t,
I
I
I
I
I
I
I
ucr, rtred (@ tr:,at 6 rtgtarux4r( r,lru
14
ttt t, frpa
Ll at6ll,*l t xt4a ,(tano u,rt agttl
f,{j#e .i.sf?f
N
4
si
21 -7 -764 Kumar & Associates LOCATION OF EXPLORATORY BORINGS Fig. 1
I
!
E
WC=11.5
+4=1 9
-2OO=37
BORING 1 BORING 2
0 0
F
trJ
trJu-
I-F(L
trJo
so/3 28/6,50/3.5 F
trJ
UJtL
I-Fo-
LJo
R
26/6,35/3
WC=12.8
+4=21
-2O0=48
5so/3.5
10 10
LEGEND
N
TOPSOIL; ORGANIC SAND AND SILT WITH BASALT GRAVEL, COBBLES AND BOULDERS, BROWN
BASALT COBBLES AND BOULDERS (GM); CALCAREOUS SAND AND SILT MATRIX, DENSE,
SLIGHTLY MOIST, GRAY.
I DRTVE SAMpLE, 1 5/8-|NCH t.D. SPL|T SPOON STANDARD PENETRATION TEST
28/6 DRIVE SAMPLE BLOW COUNT. INDICATES THAT 28 BLOWS OF A 14o-POUND HAMMER
FALLING 50 INCHES WERE REQUIRED TO DRIVE THE SAMPLER 6 INCHES.
t PRACTICAL AUGER REFUSAL.
NOTES
1. THE EXPLORATORY BORINGS WERE DRILLED ON SEPTEMBER 23, 2021 WITH A 4-INCH DIAMETER
CONTINUOUS-FLIGHT POWER AUGER.
2. THE LOCATIONS OF THE EXPLORATORY BORINGS WERE MEASURED APPROXIMATELY BY PACING
FROM FEATURES SHOWN ON THE SITE PLAN PROVIDED.
3. THE ELEVATIONS OF THE EXPLORATORY BORINGS WERE NOT MEASURED AND THE LOGS OF THE
EXPLORATORY BORINGS ARE PLOTTED TO DEPTH.
4. THE EXPLORATORY BORING LOCATIONS SHOULD BE CONSIDERED ACCURATE ONLY TO THE
DEGREE IMPLIED BY THE METHOD USED.
5. THE LINES BETWEEN MATERIALS SHOWN ON THE EXPLORATORY BORING LOGS REPRESENT THE
APPROXIMATE BOUNDARIES BETWEEN MATERIAL TYPES AND THE TRANSITIONS MAY BE GRADUAL.
6. GROUNDWATER WAS NOT ENCOUNTERED IN THE BORINGS AT THE TIME OF DRILLING.
7. LABORATORY TEST RESULTS:
WC = WATER CONTENT (%) (ASTM D2216);
+4 = PERCENTAGE RETAINED ON NO. 4 SIEVE (NSTV OOSIS);
_2OO= PERCENTAGE PASSING NO. 2OO SIEVE (ASTM D1140).
21 -7 -764 Kumar & Associates LOGS OF EXPLORATORY BORINGS Fig. 2
I
TIME READINGS
100
90
ao
70
80
50
10
30
20
10
o
HRS
!'llN 0
t0
20
30
,+o
50
60
70
80
90
to0
,
6
-g
.o37 .o75
DIAMETER OF
.125
PARTICLES IN
CLAY TO SILT COBBLES
GRAVEL 19 % SAND 41
LIQUID LIMIT
SAMPLE OF: Sllty Sond with Grovel Molrlx
%
PLASTICITY INDEX
SILT AND CLAY 37 %
FROM: Borlng 1 O 2.5' & 5' (Combined)
n
100
90
ao
70
60
50
10
50
20
lo
o
o
10
20
3o
10
50
60
70
80
90
ro0
-
.o37 .o75 .1 50
IAMETER OF
.125
PARTICLES IN MI RS
CLAY TO SILT COBBLES
GRAVEL 21 %
LIQUID LIMIT
SAND 31 %
PLASTICITY INDEX
SILT AND CLAY 4A %
SAMPLE OF: Very Silty Sond wiih Grovel FROM: Boring 2 @ 5'
Thos€ lssl rssulls qpply only lo the
somples whlch were lesled. The
lssllng report shqll nol b6 r€producod,
oxcepl ln full, wllhoul lhs wrlllenqpprovql ot Kumqr & Associol€s, lnc.
Sl6vo onolysls losllng ls porformcd ln
occordoncs wlth ASTM 069|3, ASTM D7928,
ASTM C156 ond/or ASTM D1140,
Motrix
HYDROMETER ANALYSIS SIEVE ANALYSIS
CLEAR SQUARE OPENINCS
il:o110
:
I
I
I
i I
I
I
I
I
i
l
I,r
L
l
GRAVELSAND
FINE MEDIUM COARSE FINE COARSE
HYDROMETER ANALYSIS SIEVE ANALYSIS
CLEAR SOUARE OPENINGS
.trr ./^, . trr'
IITIE READINGS
24 HRS 7 HRS
i MINlutN Itoo
U.S. STANDARD SERIES
a50 {ao {50 {t6 4io ta
./',
,l
ll
:i
:
I r rl
l
GRAVELSAND
FINE MEDIUM ICOARSE FINE COARSE
21 -7 -7 64 Kumar & Associates GRADATION TEST RESULTS Fig. 3
rcn *iffil[##l:fifn"'n3; n''**
TABLE 1
SUMMARY OF LABORATORY TEST RESULTS
Silty Sand with Gravel
Matrix
Very Silty Sand with
Gravel Matrix
SOIL TYPE
(ps0
UNCONFINED
COMPRESSIVE
STRENGTH
PLASTIC
INDEX
g"l
ATTERBERG LIMITS
(%l
LIQUID LIMIT
PERCENT
PASSING NO.
200 stEVE
37
48
(/"\
SAND
44
31
I1
I2
GRADATION
(7")
GRAVEL
(ocfl
NATURAL
DRY
DENSITY
(Y"l
NATURAL
MOISTURE
CONTENT
1 1.5
12.8
(ft)
DEPTH
2r/z andS
combined
52
SAMPLE LOCATION
BORING
1
No. 21-7-764