HomeMy WebLinkAboutSubsoils Report for Foundation DesignHuddleston-Berry
Engineering & Testing, LLC
February 14,2025
Project#02205-0002
Casey Sheets
59 County Road 317
Rifle, Colorado 81650
Subject:Geotechnical Investigation
Parcel 217927 101002 ADU
Silt, Colorado
Reference:Geotechnical Investigation, Parcel 217927101002, Silt, CO by Huddleston-Berry
Engineering & Testing,LLC for Casey Sheets, February 24,2027
Dear Mr. Sheets,
This letter presents the results of a geotechnical investigation conducted by Huddleston-Berry
Engineering & Testing, LLC GAET) for Parcel 2T7927101002 in Silt, Colorado. The site
location is shown on Figure I - Site Location Map. The proposed construction is anticipated to
consist of a new Accessory Dwelling Unit (ADU). The scope of our investigation included
evaluating the subsurface conditions at the site to aid in developing foundation recommendations
for the proposed construction.
Site Conditions
At the time of the investigation, the northern portion of the site was occupied by an existing
residence. The remainder of the site was open and generally sloping down to the southwest.
Vegetation consisted of weeds, grasses, and small to large bushes. The site was bordered to the
north, west, and east by open land, and to the south by Alta Mesa Road.
Subsurface Investigation
The current subsurface investigation included five test pits at the site as shown on Figure 2 - Site
Plan. The test pits were excavated to depths of between 3.0 and 8 0 feet below the existing
ground surface. Typed test pit logs are included in Appendix A.
As indicated on the logs, the subsurface conditions encountered at the site were fairly consistent.
The test pits encountered up to 1.0 foot of topsoil above tan, moist, very stiff sandy lean clay
soils with gravel and cobbles that extended to the bottoms of the excavations. Groundwater was
not encountered in the subsurface at the time of the investigation.
Laboratorv Testing
Laboratory testing was conducted on samples of the native soils collected from the test pits. The
testing included grain-size analysis, Atterberg limits determination, natural moisture content
determination, and maximum dry density and optimum moisture content @roctor) determination.
The laboratory testing results are included in Appendix B.
2789 Riverside Parkway
Grand Jrurction, Colorado 8 I 501
Phone: 970-255-8005
Info @huddlestonbeny. com
N
'_N
\
\
s
P arcel 217 927 I 0 I 0002 ADU
#02205-O}W
02ltt/25
Huddloston-Berry
EnBir.rhg & T.$ing, l,Lc
The laboratory testing results indicate that the native clay soils are slightly plastic. In general,
based upon the Atterberg limits and upon our experience with similar soils in the vicinity of the
subject site, the native clay soils are anticipated to be slightly collapsible.
Foundation Recommendations
Based upon the results of the subsurface investigation and nature of the proposed construction,
shallow foundations are generally recommended. Spread footings and monolithic (tumdown)
structural slab foundations are both appropriate alternatives. However, as discussed previously,
the native soils are anticipated to be slightly collapsible. Therefore, in order to provide a uniform
bearing stratum and reduce the risk of excessive differential movements, it is recornmended that
the foundations be constructed above a minimum of Z4-inches of structural fill.
The native clay soils, exclusive of topsoil, are suitable for reuse as structural fill; provided
particles in excess of 3-inches in diameter are removed. Imported structural fiIl should consist of
a granular, non-expansive, W&g i!d!!ng material with greater than l0% passing the #200
sieve and Liquid Limit of less than 30. However, all proposed imported structural fill materials
should be approved by HBET.
For spread footing foundations, the footing areas may be trenched. However, for monolithic slab
foundations, the structural fill should extend across the entire building pad area to a depth of 24-
inches below the turndown edges. Structural fill should extend laterally beyond the edges of the
foundations a distance equal to the thickness of structural fill for both foundation types.
Prior to placement of structural fill, it is recommended that the bottom of the foundation
excavation be scarifred to a depth of 6 to 9 inches, moisture conditioned, and compacted to a
minimum of 95o/o of the standard Proctor maximum dry density, within + 2Yo of the optimum
moisture content as determined in accordance with ASTM D698. Structural fill should be
moisture conditioned, placed in maximum 8-inch loose lifts, and compacted to a minimum of
95% of the standard Proctor maximum dry density for fine grained soils and 90% of the modified
Proctor maximum dry density for coarse grained soils, within + 2Ya of the optimum moisture
content as determined in accordance with ASTM D698 and Dl557, respectively.
Structural fill should be extended to within 0.l-feet of the bottom of the foundation. No more
than O.l-feet of gravel should be placed below the footings or turndown edge as a leveling
course.
For structural fill consisting of the native soils or imported granular materials, and foundation
building pad preparation as recommended, a maximum allowable bearing capacity of 1,500 psf
may be used. In addition, a modulus of subgrade reaction of 150 pci may be used for structural
fill consisting of the native soils and a modulus of 200 pci may be used for suitable imported
structural fill. Foundations subject to frost should be at least 36 inches below the finished grade.
Water soluble sulfates are common to the soils in Western Colorado. Therefore, at a minimum,
cement adequate for Sulfate Exposure Class S 1 is recommended for construction at this site.
2Z:\2008 Al-L PROJECT5\02205 - Caey Sheets\o2205-0002 Puc€l 217927101002 ADLA200 - Geo\02205-0002 LR02l425.dm
P arcel 217 927 I 0 I 0002 ADU
#02205-00a2
a2111i25
Iluddleston-Betty
tirBi'r..tnrs e rctins l-LC
Any stemwalls or retaining walls should be designed to resist lateral earth pressures. For backfill
consisting of the native soils or imported granular, non-free draining, non-expansive material, we
recommend that the walls be designed for an equivalent active fluid unit weight of 45 pcf in
areas where no surcharge loads are present. An at-rest equivalent fluid unit weight of 65 pcf is
recommended for braced walls. Lateral earth pressures should be increased as necessary to
reflect any surcharge loading behind the walls.
Non-Structural Floor Slab and Exterior Flatwork Recommendations
In order to limit the potential for excessive differential movements of slabs-on-grade it is
recommended that non-structural floating floor slabs be constructed above a minimum of 18-
inches of structural fiIl with subgrade preparation and fill placement in accordance with the
Foundation Recommendstions section of this report. It is recommended that exterior flatwork be
constructed above a minimum of l2-inches of structural fiIl.
Drainage Recommendations
Gradins and drainase are critical to the lons-term perfonnnnce of the structure. Grading
around the structure should be designed to carry precipitation and runoff away from the
structure. It is recommended that the finished ground surface drop at least twelve inches within
the first ten feet away from the structure. It is also recommended that landscaping within five
feet of the structure include primarily desert plants with low water requirements. In addition, it
is recommended that automatic irrigation, including drip lines, within ten feet of foundations be
minimized.
F{BET recommends that surface downspout extensions be used which discharge a minimum of
15 feet from the structure or beyond the backfill zone, whichever is greater. However, if
subsurface downspout drains are utilized, they should be carefully constructed of solid-wall PVC
and should daylight a minimum of 15 feet from the structure. In addition, an impermeable
membrane is recommended below subsurface downspout drains. Dry wells should not be used.
General Notes
The recommendations included above are based upon the results of the subsurface investigation
and on our local experience. These conclusions and recommendations are valid only for the
proposed construction.
As discussed previously, the subsurface conditions encountered at the site were fairly consistent.
However, the precise nature and extent of subsurface variability may not become evident until
construction. As a result, it is recommended that HBET provide construction materials testing
and engineering oversight during the entire construction process. In addition, the builder and any
subcontractors working on the project should be provided a copy of this report and informed of
the issues associated with the presence of moisture sensitive subgrade materials at this site.
JZ:U008 ALL PROJECIS\02205 - Cffiy Sheets\02205-0002 Pucel 2 179271 0l 002 ADU\200 - Geo\02205-0002 LR021425.d@
P arcel 217 927 10 1 0002 ADU
#02205-00w
02ltu25
,,A,.
@ Huddlestor-Berfy
En8ine.rhs & liJh& t-l-C
It is important to note that the recommendations herein are intended to reduce the risk of
structaral movement flnd/or damngq to varvins degrees, {tssociated with volume change of the
native soils. However, HBET cannot oredict long-tefm changes in subsurface moisture
conditions and/or the precise mnsnitade or extent of volame change in the native soils. Where
significant increases in subsutfsce maisture occur due to poor gradins. imDroper stormwater
msnagement, utilitv line failure, ecess irrteafion. or other cause, either durins construction
or the result of actions of the propertv ownen several inches of movement are oossible.In
addition, anv failure to cottwlv with the recorylryJndgtiow in this reoort releases Huddleston-
Berrv Ensineerins & Testing, LLC of anv liabilitv with regard to the structure performance.
We are pleased to be of service to your project. Please contact us if you have any questions or
comments regarding the contents of this report.
Respectfully Submitted :
Huddleston-Berry Engineering and Testingo LLC
Michael A. Berry, P.E.
Vice President of Engineering
4Z:\2008 AI,L PROJECTS\o2205 - Casy Sheets\02205-0002 Prcel 217927101002 AD[A200 - Ceo\02205-0002 LR02l425.dm
FIGT]RES
G)qPublic.h€t'" Garfi eld County, Co
Location
llD
Date createdt 215/2O25
Last Data Uploaded: 2/512O25 2206:51 AM
FIGURE 1
Site Location Map
Develoned bvlp SCHNEIDER
c€o5P^TrAL
G)qPublic.net* Garfield County, Co
FIGURE 2
Site PlanDate created: 1/16/2025
Last Data Uploaded: 1/16/2025 2:O5:58AM
Developedbye SCHNEIDERc30aPA?lAl
APPENIDIX A
Typed Test Pit Logs
PROTECT NI\ME Parce) Zl7g27'lUW2 ADU
PRO'ECT LOGANON SiIt, COPROJECT NUMBER 02205-0@2
Riverside
Junctisr,
Parkway
co 81501
CLIENT Casev Sheets
Huddleston-Berry Engineering & Testing LLC
9?0-255-8005
TEST PIT NUMBER TP.{
PAGE 1 OF 1
TEST PITSIZEDATE STARITED 1fi725 @MPIETED 1N7T25
EXCAVATION CONTMGTOR Client
CHECKEDBY MAB
EXCAVATION METHOD TrackhlBackhoe
GROUND ELEVANON
LOGGEDBY TC
NOTES AFTERB(CAVATION --
AT ENDOF EXCAVATIO{II Dry
GROUNDWATERLEIIELS:
ATflMEOF B(CAVATION Drv
ATTERBERG
LIMITSul&>IrFrrl
1gaL::r>2.
at)
a
E8gs
ult
aG>Fl<2. J;asoz.
z.
uJoFGill l4
oo(L
5F^
=_Euo
-ot-U o\E:-
-F
tt, Floz
=oo
o,
l=a=
J-
otrF
3=o
Fot
42o-
FzulFzoG'O=a
LUzit
IE
IFo-ulo
0.0
o
+Et-o
MATERIAL DESCRIPTION
I GB
1
5 m 17 I 53
Sandy Lean CLAY with Gravel and Cobbles (CL), tan, moid, very
stiff
G&1: Lab Classified
Fz(]
a
jo
Noo
o
FNoF
N
J
IU
Otr
A
No
o
@oNNo
u)z
:lJoo
Im
of test pit at 7.0 feet.
Huddleston-Berry Engineering & Testing LLC
2789 Riverside Parkway
Crrand Jrmctigr, CO 81501
970-255-8005
TEST PIT NUMBER TP-2
PAGE 1 OF 1
PRO.TECT Ifl\ME Parcel 2175271O10f)2 NU
PROJECT NUMBER PROJECT LOCATION sitr co
CLIENT Casey Sheets
EXCAVATION METHOD Trackh/Backhoe
LOGGEDBY TC CHFCKEDBY MAB
DATESTARTED 1N7T25 @MPLETED 1117N5 TEST PIT SIZE
EXCAVATION CONTRAGIOR Client
ATNMEOF E(CAVATION Drv
GROUND ELEVATION
t{oTEs
ATENDOFEXCAVATION Dry
AFTEREXqVATION -
GROT' Nfi } WATER LEVEI.S:
ATTERBERG
LIMITSt!(L>EFut
-rtg(L=
=2.a
s
qa
8(-ulE
au>Fl
^z.J;3soz
z.ulIL
FCirg
()o.L
E
F^
=Eto
r-rr;e(r:-
tD Floz>oo
o,
3=lr
otrF
3=&
F0t
42o-
FzulFz
88a
UJztr
g
IF(L
Lrlo
0.0
o:
+Et"o
MATERIAL DESCRIPTION
Sandy Lean CLAY with Gravel and Cobbles (cl), tan, moist, very
stiff
oN
N
F
si
Jol
Fz
6
o-
jo
oz
lJa-c0
IouFoI
Bottom of test pit at 6.Ofeet.
PROTECT nlAME Parcel ?.79271O1ffI2 ADU
PRO.TECT I.oCATTON Sitt. COPROJECT NUMBER 02205@2
Riverside
Engineering & Testing LLC
CLIENT Casey Sheets
TEST PIT NUMBER TP.3
PAGE 1 OF 1
Crrand Junctiur, CO 81501
970-255-8005
MMPLETED 1117f25 TEST PITSIZEDATE STARITED 1N7T25
EXCAVATIONCONTMGTOR Client
CHrcKEDBY MAB
EXCAVATIONMETHOD Trackh/Backhoe
GROUNDELF'ANON
ATENDOFEXCAVAilON Drv
AFTEREXCAVANON _
LOGGEDBY TC
t{oTEs
GROT'NDWATERLEIIEIS:
ATTIMEOFE(CAVATION Drv
ATTERBERG
LIMITS
Fqil
42(L
Fz
uJFzoG'o=
U)
UJz
l!
I
IF(Lulo
o
o
o-X
sY(,
MATERIAL DESCRIPTION
ul(L>uFUI
sg(L -!>=
a
s
E--
E3
8s
UJ
E.
ai>Fl<zJ
Xasoz
zul{LFG
UJ JA
oo(L
I
F^
=Eto
ur;at-
i, Pl_Foz.>oo
oF
a=lJ
()
FF
3=
1
.ry.:.!i+
{_a.' j
?$r
rt r/ rl
2: "!-t'
ir r).'^t
? $r:
Sandy Lean Clay with Organics (TOPSOIL)
2
3
Sardy Lean CLAY with Gravel ard Cobbles (cl), tan, moi$, very
siff
oN
N
Foo
di
Ja)
Fz
(9
a
C?:)o
Noo
o
FNoF
N
Boltom of teS pit at 3.Ofeet.
Huddleston-Berry Engineering & Testing LLC
2789 Riverside Parkway
Grand Junction, CO 81501
9?0-255-8005
TEST PIT NUMBER TP4
PAGE 1 OF 1
PRO.JECf ]I|AME Parce) 217527101@,2 ADU
PRO.TECT LOCATTON Sitt, COPROJECT NUMBER O2O5-OOO2
CLIENT Casey Sheets
TEST PIT SIZE@MPLETED U17N5DATESTARTED il1725
EXCAVATION CONTMGTOR Client
CHECKEDBY MAB
EX$VATIONMETHOD Trackh/Backhoe
GROUND ELEI'ATION
ATENDOF B(CAVATKhI Drv
AFIEREXCAVANON _
LOGGEDBY TC
ITIOTES
GROUNDWATERLEVELS:
ATTIMEOF E(CAVATION Drv
ATTERBERG
LIMITSulI>trFut
5g(L=)
=2.a
s
qa
8sulE
au>Fl
^zJXasoz.
2
uJ(L
FGi!g
oo(L
5F^ZQflJ
Eo
.uFE--rL1
tD Froz
=oo
o,
f=o=
l-
oEF
q=
L
Eqd
69
5=o
Fz
UJFzoG-og
ct)
[rJztroo
TF-^
O- rE
o
o
3qo
MATERIAL DESCRIPTION
Sandy Lean Clay with Organics (TOPSOIL)
2.5
Sardy Lean CLAY with Gravel and Cobbles {cl), tan, moi$, very
stiff
4NEN
Fo(,
ai
Jaf
Fz
o
o-
jo
Noo
Bottom of test pit at 8.0 feet.
Huddleston-Berry Engineering & Testing LLC
2789 Riverside Parkway
Grand Junclisr, CO 81501
970-255-8005
PROTECT I|I|AME Parcel A7S271UW2 ADU
PROJECT LOGATION SiIt. COPROJECT NUMBER 02205-OOO2
CLIENT Casev Sheets
TEST PIT NUMBER TP.s
PAGE 1 OF 1
GROUNDELryANON
GROUNDWATERLEIIELS:
ATilMEOFEXCAVATON Drv
@MPLETED 1N7N5 TEST PITSIZEDATE STARITED 1117N5
EXCAVATION CONTMCTOR Client
CHFCKEDBY tvlAB
EXCAVATION METHOD Trackh/Backhoe
ATENDOFE(AVATlOill Drv
AFIEREXCAVATION _
LOGGEDBY TC
f{oTEs
ATTERBERG
LIMITS
o
IF^(L rE
o
()
Irn
+d
(,
MATERIAL DESCRIPTION
rrlL>lrF-ut
sgIL
=r=z
U)
.:g
$a
8sult
rnO>Fl
^,2.JHastJ=
z.ulILFCirg
oo(L
5
F^
=EE.o
u.r;eE:'
tD FI
-Foz
=oo
o,
d>
J_
oFF
3=o-
F0t
42
Fz
u.lFzoG'O=
U)utztr
E:."!
t..sx,
$ !.'{
r. ii rr
Sandy Lean Clay with Organics (TOPSOIL)
Sandy Lean CLAY with Gravel and Cobbles (cl), tan, moist, very
diff
Bottom of test pit at 3,0 feet.
Jtxoe
(]-
Nooo
a
N
No
g)
lJ
O
Id!
IO
t].tFoU
APPEIIDIX B
Laboratory Testing Results
Huddloston-Berry Engineering & Testing LLC
2789 Riverside Parkway
Grand Junctiqr, CO 81501
970-255-8005
GRAIN SIZE DISTRIBUTION
PRO.IECT iIAME Parce| 2'7927101'ffJ2 ADU
PROJECT LOCAnON Sitt. COPROJECT NUMBER 02205-OOO2
CLIENT Casey Sheets
U.S. SIEVE OPENING IN INCHES I U.S, SIEVE NU'BERS I
1m14)2m
HYDROMETER6 4 3 21.5 14 20 :n {}
FI(,
tr3
co
trtrtztr
Fztrlo
E.t!
o-
100
95
90
85
80
75
70
65
60
55
50
45
40
35
30
20
15
't0
5
o
100 1 1
GRAIN SIZE IN MILLIMETERS
0.1 o.01 0.001
*,
I
I I tt
\L_
t:
n
li \
!
:li
t:
I I
\
li
:l
'l
l:
li
COBBLES GRAVEL SAND SILT OR CLAY
@aIse fine coarse mdium fine
Specimen ldentifi cation Classification LL PL PI Cc Cu
a TP-l, GB-l 1t17 SANDYLEAN CI-AY(CL)26 17 I
D60 D30 D10 ToGravel ToSand %sitt %ClaySpecimen ldentification D100
0.t45 4.6 42.0 53.4oTP-1, GB-l 1t17 {9
NaN
Fno
{d
J
(t):l
tt
NoI
o
N
ulN6z
t
ATTERBERG LIMITS' RESULTS
PR(UECT TtlAME Parcel 21792710,1'C(I2 ADU
PrcJECT NUMBER gff,-cnp.z PRO.TECI LOCATTON Sin. CO
CLIENT Casey Sheets
Huddleston-Berry Engineering & Testing Ll,C
970-255-8005
Riverside Parkway
Junctim, CO 81501
@
@
LIOUID LIMIT
@
@
4020
CL-ML
50
40
30
20
10
0
P
L
A
s
T
Ic
I
T
I
N
D
E
X
Specimen ldentification LL PL PI #204 Classification
a SANDY LEAN CLAY(CL)TP-1, GB-'1t17 26 17 I 53
-Aojo
N
Jtll
OE
c
N
BooNNo
U}F
:loEr.!d)t
I.xt
MOISTURE.DENSIW RELATIONSHIP
PROTECT ]tlAME Parcel 21752710,1.0(J2 ADV
Prc.'ECT NUMBER Affi-opp'2 PRO.'EGI LCICATION SiIt. CO
CLIENT Casev Sheets
Huddleston-Berry Engineering & Testing, Ll-C
Riverside Parkwav
Grand Junctisr, CO 81501
970-255-8005
)ul
\
I
\
\
\\
\\
I
\
\
\
\
\
\
\
,a
7 \\
7
t
7 \\
\
\
\
\
\
\
\\
\
\
PLLL
26
201
oo-tFaz.ulo
E.o
145
140
135
130
125
115
110
105
100
90
1n7t2025
254022
TP.{GB-1
SANDY I-EAN CLAY{CL)
Test Method (manual):ASTM D698A
TEST RESULTS
Maximum Dry Density {23-0 PCF
Optimum Water Content 11.5 %
GRADATION RESULTTi (% PASSTNG)
#200 # 3t4"
53 95 100
ATIERBERG LIMITS
PI
17 9
Sample Date:
Sample No.:
Source of Material:
Description of Material:
15
Curves of 100% Saturation
for Specific Gravity Equalto:
2.84
2.74
2.60
t
di
Ja:)
Fz
(,
q
l
N
o
o
F
!
ts
N
95
50 10
\A/ATtrR NOhTTtr.\TT OA
20 25 30