HomeMy WebLinkAboutCompression Strength 1Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
1-1 13 07/09/24 13 / 0 4.00 12.57 47,181 3,750 4 N
Test Age Average Strengths (psi): 13 Day - 3750
Tested By: Sandon Thibault (1)
Checked In : 07/09/2024 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:1
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:65 / 0300
Contractor:
Technician:Peskuski, Ryan
Cast By:Peskuski, Ryan
Date Cast:06/26/24
Sampled From:Chute
Placement Method:Chute
Sample Details
Batched:
Sampled:07:15 MDT
Cast:07:30 MDT
Truck Empty:
Placement Time:
Placement Location:Footings
Location Details:Bldg. A retaining wall footings.
Sample Location / Notes:10 of 10 yards
Batch Log
Strength:4000 (psi)
Specifications
Supplier:Casey Concrete Mix Design:4000 Exterior
On-Site Admixtures: None
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:143.4 (lb/ft³)
Air Content:4.4
Load Volume:10.00 (yd³)
Weather:Consistency:Slump
Air Temperature (F):Concrete Temp (F):72
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 131413
06/26/2024
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 07/22/2024
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
1-1 13 07/09/24 13 / 0 4.00 12.57 47,181 3,750 4 N
1-2 30 07/26/24 13 / 17 4.00 12.57 63,739 5,070 3 C4 N
1-3 30 07/26/24 13 / 17 4.00 12.57 62,885 5,000 5 C4 N
1-4 30 07/26/24 13 / 17 4.00 12.57 63,519 5,050 3 C4 N
1-5 30 07/26/24 13 / 17
Test Age Average Strengths (psi): 13 Day - 3750, 30 Day - 5040
C4: Strength is greater than or equal to f'c.
Tested By: Sandon Thibault (1), Ryan Peskuski (2,3,4,5)
Checked In : 07/09/2024 (1,2,3,4,5)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:1
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:65 / 0300
Contractor:
Technician:Peskuski, Ryan
Cast By:Peskuski, Ryan
Date Cast:06/26/24
Sampled From:Chute
Placement Method:Chute
Sample Details
Batched:
Sampled:07:15 MDT
Cast:07:30 MDT
Truck Empty:
Placement Time:
Placement Location:Footings
Location Details:Building A retaining wall footings
Sample Location / Notes:10 of 10 yards
Batch Log
Strength:4000 (psi)
Specifications
Supplier:Casey Concrete Mix Design:4000 Exterior
On-Site Admixtures: None
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:143.4 (lb/ft³)
Air Content:4.4
Load Volume:10.00 (yd³)
Weather:Consistency:Slump
Air Temperature (F):Concrete Temp (F):72
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39
Sample: 131413
06/26/2024
Report #: CC-000001
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 08/02/2024
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
2-1 13 07/09/24 13 / 0 4.00 12.57 53,882 4,290 3 N
Test Age Average Strengths (psi): 13 Day - 4290
Tested By: Ryan Peskuski (1)
Checked In : 07/09/2024 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:2
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:3140 / 190310
Contractor:
Technician:Schulz, Cayden
Cast By:Schulz, Cayden
Date Cast:06/26/24
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:09:00 MDT
Cast:09:15 MDT
Truck Empty:
Placement Time:
Placement Location:Footings
Location Details:Center dive building footings
Sample Location / Notes:110/180
Batch Log
Strength:4000 (psi)
Air:3.5 - 6.5 (%)
Specifications
Supplier:Casey Concrete Mix Design:4000 PSI 3/4" Exterior
On-Site Admixtures: None
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:145.7 (lb/ft³)
Air Content:3.5
Load Volume:10.00 (yd³)
Weather:Slump (in):3-3/4
Air Temperature (F):Concrete Temp (F):72
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 131457
06/26/2024
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 07/22/2024
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
2-1 13 07/09/24 13 / 0 4.00 12.57 53,882 4,290 3 N
2-2 30 07/26/24 13 / 17 4.00 12.57 66,127 5,260 3 C4 N
2-3 30 07/26/24 13 / 17 4.00 12.57 66,716 5,310 5 C4 N
2-4 30 07/26/24 13 / 17 4.00 12.57 69,008 5,490 5 C4 N
2-5 30 07/26/24 13 / 17
Test Age Average Strengths (psi): 13 Day - 4290, 30 Day - 5350
C4: Strength is greater than or equal to f'c.
Tested By: Ryan Peskuski (1,2,3,4,5)
Checked In : 07/09/2024 (1,2,3,4,5)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:2
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:3140 / 190310
Contractor:
Technician:Schulz, Cayden
Cast By:Schulz, Cayden
Date Cast:06/26/24
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:09:00 MDT
Cast:09:15 MDT
Truck Empty:
Placement Time:
Placement Location:Footings
Location Details:Building A wall footings
Sample Location / Notes:110/180
Batch Log
Strength:4000 (psi)
Air:3.5 - 6.5 (%)
Specifications
Supplier:Casey Concrete Mix Design:4000 PSI 3/4" Exterior
On-Site Admixtures: None
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:145.7 (lb/ft³)
Air Content:3.5
Load Volume:10.00 (yd³)
Weather:Slump (in):3-3/4
Air Temperature (F):Concrete Temp (F):72
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39
Sample: 131457
06/26/2024
Report #: CC-000002
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 08/02/2024
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
3-1 7 07/10/24 5 / 2 4.00 12.57 55,124 4,390 4 N
Test Age Average Strengths (psi): 7 Day - 4390
Tested By: Sandon Thibault (1)
Checked In : 07/08/2024 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:3
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:158 / 190499
Contractor:Andover
Technician:Downing, Thomas
Cast By:Downing, Thomas
Date Cast:07/03/24
Sampled From:Chute
Placement Method:Pump
Sample Details
Batched:12:38 MDT
Sampled:13:40 MDT
Cast:13:50 MDT
Truck Empty:
Placement Time:
Placement Location:Footings
Location Details:Building A retaining wall footing
Sample Location / Notes:Along 36 line, from A line to PP line
Batch Log
Strength:4000 (psi)
Air:3.5 - 6.5 (%)
Specifications
Supplier:Casey Concrete Mix Design:4000
On-Site Admixtures: 8.00 Gal Water (10 yd³)
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:
Air Content:4.8
Load Volume:10.00 (yd³)
Weather:Slump (in):5
Air Temperature (F):Concrete Temp (F):76
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 131739
07/03/2024
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 07/22/2024
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
3-1 7 07/10/24 5 / 2 4.00 12.57 55,124 4,390 4 N
3-2 28 07/31/24 5 / 23 4.00 12.57 67,913 5,400 5 C4 N
3-3 28 07/31/24 5 / 23 4.00 12.57 68,569 5,460 5 C4 N
3-4 28 07/31/24 5 / 23 4.00 12.57 68,508 5,450 5 C4 N
3-5 28 07/31/24 5 / 23
Test Age Average Strengths (psi): 7 Day - 4390, 28 Day - 5440
C4: Strength is greater than or equal to f'c.
Tested By: Sandon Thibault (1,2,3,4,5)
Checked In : 07/08/2024 (1,2,3,4,5)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:3
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:158 / 190499
Contractor:Andover
Technician:Downing, Thomas
Cast By:Downing, Thomas
Date Cast:07/03/24
Sampled From:Chute
Placement Method:Pump
Sample Details
Batched:12:38 MDT
Sampled:13:40 MDT
Cast:13:50 MDT
Truck Empty:
Placement Time:
Placement Location:Footings
Location Details:Building A retaining wall footing
Sample Location / Notes:Along 36 line, from A line to PP line
Batch Log
Strength:4000 (psi)
Air:3.5 - 6.5 (%)
Specifications
Supplier:Casey Concrete Mix Design:4000
On-Site Admixtures: 8.00 Gal Water (10 yd³)
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:
Air Content:4.8
Load Volume:10.00 (yd³)
Weather:Slump (in):5
Air Temperature (F):Concrete Temp (F):76
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39
Sample: 131739
07/03/2024
Report #: CC-000003
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 08/14/2024
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
4-1 7 07/16/24 1 / 6 4.00 12.57 47,407 3,770 3 N
Test Age Average Strengths (psi): 7 Day - 3770
Tested By: Sandon Thibault (1)
Checked In : 07/10/2024 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:4
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:66 / 1633
Contractor:
Technician:Peskuski, Ryan
Cast By:Peskuski, Ryan
Date Cast:07/09/24
Sampled From:Chute
Placement Method:Pump
Sample Details
Batched:
Sampled:12:20 MDT
Cast:12:35 MDT
Truck Empty:
Placement Time:
Placement Location:Wall
Location Details:Building A Retaining Walls. West side and partial north side.
Sample Location / Notes:20 of 100+ yards
Batch Log
Strength:4000 (psi)
Air:3.5 - 6.5 (%)
Specifications
Supplier:Casey Concrete Mix Design:4000 PSI 3/4" Exterior
On-Site Admixtures: None
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:144.6 (lb/ft³)
Air Content:4.9
Load Volume:10.00 (yd³)
Weather:Consistency:Slump
Air Temperature (F):Concrete Temp (F):79
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 131830
07/09/2023
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 07/22/2024
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
4-1 7 07/16/24 1 / 6 4.00 12.57 47,407 3,770 3 N
4-2 28 08/06/24 1 / 27 4.00 12.57 67,468 5,370 3 C4 N
4-3 28 08/06/24 1 / 27 4.00 12.57 68,287 5,430 3 C4 N
4-4 28 08/06/24 1 / 27 4.00 12.57 68,654 5,460 3 C4 N
4-5 28 08/06/24 1 / 27
Test Age Average Strengths (psi): 7 Day - 3770, 28 Day - 5420
C4: Strength is greater than or equal to f'c.
Tested By: Sandon Thibault (1,2,3,4,5)
Checked In : 07/10/2024 (1,2,3,4,5)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:4
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:66 / 1633
Contractor:
Technician:Peskuski, Ryan
Cast By:Peskuski, Ryan
Date Cast:07/09/24
Sampled From:Chute
Placement Method:Pump
Sample Details
Batched:
Sampled:12:20 MDT
Cast:12:35 MDT
Truck Empty:
Placement Time:
Placement Location:Wall
Location Details:Building A Retaining Walls. West side and partial north side.
Sample Location / Notes:20 of 100+ yards
Batch Log
Strength:4000 (psi)
Air:3.5 - 6.5 (%)
Specifications
Supplier:Casey Concrete Mix Design:4000 PSI 3/4" Exterior
On-Site Admixtures: None
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:144.6 (lb/ft³)
Air Content:4.9
Load Volume:10.00 (yd³)
Weather:Consistency:Slump
Air Temperature (F):Concrete Temp (F):79
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39
Sample: 131830
07/09/2024
Report #: CC-000004
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 08/14/2024
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
5-1 7 07/17/24 2 / 5 4.00 12.57 56,148 4,470 3 N
Test Age Average Strengths (psi): 7 Day - 4470
Tested By: Sandon Thibault (1)
Checked In : 07/12/2024 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:5
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:58 / 0583
Contractor:
Technician:Peskuski, Ryan
Cast By:Peskuski, Ryan
Date Cast:07/10/24
Sampled From:Chute
Placement Method:Pump
Sample Details
Batched:
Sampled:12:10 MDT
Cast:12:25 MDT
Truck Empty:
Placement Time:
Placement Location:Grade Beam
Location Details:Bldg. A south grade beam
Sample Location / Notes:10 of 30+ yards
Batch Log
Strength:4000 (psi)
Air:3.5 - 6.5 (%)
Specifications
Supplier:Casey Concrete Mix Design:4000 PSI 3/4" Exterior
On-Site Admixtures: 5.00 Gal Water (10 yd³)
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:144.6 (lb/ft³)
Air Content:3.8
Load Volume:10.00 (yd³)
Weather:Consistency:Slump
Air Temperature (F):Concrete Temp (F):76
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 131889
07/10/2024
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 07/25/2024
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
5-1 7 07/17/24 2 / 5 4.00 12.57 56,148 4,470 3 N
5-2 28 08/07/24 2 / 26 4.00 12.57 72,036 5,730 3 C4 N
5-3 28 08/07/24 2 / 26 4.00 12.57 76,034 6,050 3 C4 N
5-4 28 08/07/24 2 / 26 4.00 12.57 81,319 6,470 3 C4 N
5-5 28 08/07/24 2 / 26
Test Age Average Strengths (psi): 7 Day - 4470, 28 Day - 6080
C4: Strength is greater than or equal to f'c.
Tested By: Sandon Thibault (1,2,3,4,5)
Checked In : 07/12/2024 (1,2,3,4,5)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:5
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:58 / 0583
Contractor:
Technician:Peskuski, Ryan
Cast By:Peskuski, Ryan
Date Cast:07/10/24
Sampled From:Chute
Placement Method:Pump
Sample Details
Batched:
Sampled:12:10 MDT
Cast:12:25 MDT
Truck Empty:
Placement Time:
Placement Location:Grade Beam
Location Details:Building A south grade beam
Sample Location / Notes:10 of 30+ yards
Batch Log
Strength:4000 (psi)
Air:3.5 - 6.5 (%)
Specifications
Supplier:Casey Concrete Mix Design:4000 PSI 3/4" Exterior
On-Site Admixtures: 5.00 Gal Water (10 yd³)
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:144.6 (lb/ft³)
Air Content:3.8
Load Volume:10.00 (yd³)
Weather:Consistency:Slump
Air Temperature (F):Concrete Temp (F):76
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39
Sample: 131889
07/10/2024
Report #: CC-000005
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 08/14/2024