HomeMy WebLinkAboutCompression Strength 8Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
45-1 7 04/07/25 1 / 6 4.00 12.57 51,497 4,100 3 N
45-2 28 04/28/25 1 / 27 4.00 12.57 68,196 5,430 3 C4 N
45-3 28 04/28/25 1 / 27 4.00 12.57 66,014 5,250 3 C4 N
45-4 28 04/28/25 1 / 27 4.00 12.57 71,130 5,660 3 C4 N
45-5 28 04/28/25 1 / 27
Test Age Average Strengths (psi): 7 Day - 4100, 28 Day - 5450
C4: Strength is greater than or equal to f'c.
Tested By: Sandon Thibault (1,2,3,4,5)
Checked In : 04/01/2025 (1,2,3,4,5)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:45
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:67 / 2480
Contractor:
Technician:Peskuski, Ryan
Cast By:Peskuski, Ryan
Date Cast:03/31/25
Sampled From:Chute
Placement Method:Chute
Sample Details
Batched:
Sampled:08:45 MDT
Cast:09:00 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:Curb and gutter south west side of Building A.
Sample Location / Notes:7 of 16+ yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:K35565
On-Site Admixtures: 17.00 Gal Water (7 yd³)
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:140.3 (lb/ft³)
Air Content:5.4
Load Volume:7.00 (yd³)
Weather:Consistency:Slump
Air Temperature (F):Concrete Temp (F):60
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39
Sample: 141591
03/31/2025
Report #: CC-000044
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 05/05/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
46-1 7 04/09/25 1 / 6 4.00 12.57 55,468 4,410 4 N
Test Age Average Strengths (psi): 7 Day - 4410
Tested By: Sandon Thibault (1)
Checked In : 04/03/2025 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:46
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:166 / 2498
Contractor:Andover construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/02/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:13:00 MDT
Cast:13:15 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:south of Building A curb & gutter, island and, radius'.
Sample Location / Notes:@4/4 yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:K35565
On-Site Admixtures: None
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:145.0 (lb/ft³)
Air Content:4.5
Load Volume:4.00 (yd³)
Weather:Slump (in):4-1/2
Air Temperature (F):Concrete Temp (F):67
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 141688
04/02/2025
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 04/10/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
46-1 7 04/09/25 1 / 6 4.00 12.57 55,468 4,410 4 N
46-2 28 04/30/25 1 / 27 4.00 12.57 72,285 5,750 4 C4 N
46-3 28 04/30/25 1 / 27 4.00 12.57 77,629 6,180 3 C4 N
46-4 28 04/30/25 1 / 27 4.00 12.57 76,039 6,050 3 C4 N
46-5 28 04/30/25 1 / 27
Test Age Average Strengths (psi): 7 Day - 4410, 28 Day - 5990
C4: Strength is greater than or equal to f'c.
Tested By: Sandon Thibault (1,2,3,4,5)
Checked In : 04/03/2025 (1,2,3,4,5)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:46
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:166 / 2498
Contractor:Andover construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/02/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:13:00 MDT
Cast:13:15 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:south of Building A curb & gutter, island and, radius'.
Sample Location / Notes:@4/4 yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:K35565
On-Site Admixtures: None
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:145.0 (lb/ft³)
Air Content:4.5
Load Volume:4.00 (yd³)
Weather:Slump (in):4-1/2
Air Temperature (F):Concrete Temp (F):67
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39
Sample: 141688
04/02/2025
Report #: CC-000045
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 05/05/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
47-1 7 04/11/25 3 / 4 4.00 12.57 54,606 4,340 3 N
Test Age Average Strengths (psi): 7 Day - 4340
Tested By: Sandon Thibault (1)
Checked In : 04/07/2025 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:47
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:166 / 2495
Contractor:Andover construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/04/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:11:00 MDT
Cast:11:15 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:East side of Building A curb and gutter
Sample Location / Notes:@6/6 yards
Batch Log
Strength:4500 (psi)
Specifications
On-Site Admixtures: None
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:143.2 (lb/ft³)
Air Content:5.6
Load Volume:6.00 (yd³)
Weather:Slump (in):4
Air Temperature (F):Concrete Temp (F):67
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 141772
04/04/2025
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 04/11/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
47-1 7 04/11/25 3 / 4 4.00 12.57 54,606 4,340 3 N
47-2 28 05/02/25 3 / 25 4.00 12.57 68,262 5,430 3 C4 N
47-3 28 05/02/25 3 / 25 4.00 12.57 71,251 5,670 3 C4 N
47-4 28 05/02/25 3 / 25 4.00 12.57 72,089 5,740 3 C4 N
47-5 28 05/02/25 3 / 25
Test Age Average Strengths (psi): 7 Day - 4340, 28 Day - 5610
C4: Strength is greater than or equal to f'c.
Tested By: Sandon Thibault (1,2,3,4,5)
Checked In : 04/07/2025 (1,2,3,4,5)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:47
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:166 / 2495
Contractor:Andover construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/04/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:11:00 MDT
Cast:11:15 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:East side of Building A curb and gutter
Sample Location / Notes:@6/6 yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:K35565
On-Site Admixtures: None
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:143.2 (lb/ft³)
Air Content:5.6
Load Volume:6.00 (yd³)
Weather:Slump (in):4
Air Temperature (F):Concrete Temp (F):67
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39
Sample: 141772
04/04/2025
Report #: CC-000046
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 05/09/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
48-1 7 04/14/25 1 / 6 4.00 12.57 54,939 4,370 4 N
Test Age Average Strengths (psi): 7 Day - 4370
Tested By: Sandon Thibault (1)
Checked In : 04/08/2025 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:48
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:166 / 2500
Contractor:Andover Construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/07/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:11:30 MDT
Cast:11:45 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:West and south side of Building C curb & gutter
Sample Location / Notes:@8/8 yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:K35565
On-Site Admixtures: 8.00 Gal Water (8 yd³)
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:142.5 (lb/ft³)
Air Content:5.4
Load Volume:8.00 (yd³)
Weather:Slump (in):4
Air Temperature (F):Concrete Temp (F):70
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 141799
04/07/2025
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 04/21/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
48-1 7 04/14/25 1 / 6 4.00 12.57 54,939 4,370 4 N
48-2 28 05/05/25 1 / 27 4.00 12.57 70,251 5,590 4 C4 N
48-3 28 05/05/25 1 / 27 4.00 12.57 65,210 5,190 3 C4 N
48-4 28 05/05/25 1 / 27 4.00 12.57 66,863 5,320 3 C4 N
48-5 28 05/05/25 1 / 27
Test Age Average Strengths (psi): 7 Day - 4370, 28 Day - 5370
C4: Strength is greater than or equal to f'c.
Tested By: Sandon Thibault (1,2,3,4,5)
Checked In : 04/08/2025 (1,2,3,4,5)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:48
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:166 / 2500
Contractor:Andover Construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/07/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:11:30 MDT
Cast:11:45 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:West and south side of Building C curb & gutter
Sample Location / Notes:@8/8 yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:K35565
On-Site Admixtures: 8.00 Gal Water (8 yd³)
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:142.5 (lb/ft³)
Air Content:5.4
Load Volume:8.00 (yd³)
Weather:Slump (in):4
Air Temperature (F):Concrete Temp (F):70
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39
Sample: 141799
04/07/2025
Report #: CC-000047
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 05/09/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
49-1 7 04/15/25 1 / 6 4.00 12.57 55,694 4,430 5 N
Test Age Average Strengths (psi): 7 Day - 4430
Tested By: Sandon Thibault (1)
Checked In : 04/09/2025 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:49
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:166 / 2501
Contractor:Andover Construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/08/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:08:15 MDT
Cast:08:30 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:Southwest corner of Building C curb & gutter
Sample Location / Notes:@8/8 yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete
On-Site Admixtures: 6.00 Gal Water
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:143.3 (lb/ft³)
Air Content:5.6
Load Volume:8.00 (yd³)
Weather:Slump (in):4
Air Temperature (F):Concrete Temp (F):67
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 141826
04/08/2025
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 04/21/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
49-1 7 04/15/25 1 / 6 4.00 12.57 55,694 4,430 5 N
49-2 28 05/06/25 1 / 27 4.00 12.57 69,965 5,570 3 C4 N
49-3 28 05/06/25 1 / 27 4.00 12.57 73,219 5,820 3 C4 N
49-4 28 05/06/25 1 / 27 4.00 12.57 73,731 5,870 3 C4 N
49-5 28 05/06/25 1 / 27
Test Age Average Strengths (psi): 7 Day - 4430, 28 Day - 5750
C4: Strength is greater than or equal to f'c.
Tested By: Sandon Thibault (1,2,3,4,5)
Checked In : 04/09/2025 (1,2,3,4,5)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:49
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:166 / 2501
Contractor:Andover Construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/08/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:08:15 MDT
Cast:08:30 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:Southwest corner of Building C curb & gutter
Sample Location / Notes:@8/8 yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete
On-Site Admixtures: 6.00 Gal Water
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:143.3 (lb/ft³)
Air Content:5.6
Load Volume:8.00 (yd³)
Weather:Slump (in):4
Air Temperature (F):Concrete Temp (F):67
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39
Sample: 141826
04/08/2025
Report #: CC-000048
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 05/09/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
50-1 7 04/16/25 1 / 6 4.00 12.57 54,670 4,350 4 N
Test Age Average Strengths (psi): 7 Day - 4350
Tested By: Sandon Thibault (1)
Checked In : 04/10/2025 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:50
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:166 / 2505
Contractor:Andover Construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/09/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:08:15 MDT
Cast:08:30 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:Building C west side curb and gutter
Sample Location / Notes:@8/8 yards
Batch Log
Strength:4500 (psi)
Specifications
On-Site Admixtures: 8.00 Gal Water (8 yd³)
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:143.8 (lb/ft³)
Air Content:5.7
Load Volume:8.00 (yd³)
Weather:Slump (in):4
Air Temperature (F):Concrete Temp (F):68
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 141881
04/09/2025
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 04/21/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
50-1 7 04/16/25 1 / 6 4.00 12.57 54,670 4,350 4 N
50-2 29 05/08/25 1 / 28 4.00 12.57 71,133 5,660 3 C4 N
50-3 29 05/08/25 1 / 28 4.00 12.57 70,091 5,580 4 C4 N
50-4 29 05/08/25 1 / 28 4.00 12.57 71,498 5,690 4 C4 N
50-5 29 05/08/25 1 / 28
Test Age Average Strengths (psi): 7 Day - 4350, 29 Day - 5640
C4: Strength is greater than or equal to f'c.
Tested By: Sandon Thibault (1,2,3,4,5)
Checked In : 04/10/2025 (1,2,3,4,5)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:50
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:166 / 2505
Contractor:Andover Construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/09/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:08:15 MDT
Cast:08:30 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:Building C west side curb and gutter
Sample Location / Notes:@8/8 yards
Batch Log
Strength:4500 (psi)
Specifications
On-Site Admixtures: 8.00 Gal Water (8 yd³)
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:143.8 (lb/ft³)
Air Content:5.7
Load Volume:8.00 (yd³)
Weather:Slump (in):4
Air Temperature (F):Concrete Temp (F):68
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39
Sample: 141881
04/09/2025
Report #: CC-000049
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 05/09/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
51-1 7 04/17/25 1 / 6 4.00 12.57 40,124 3,190 5 N
Test Age Average Strengths (psi): 7 Day - 3190
Tested By: Sandon Thibault (1)
Checked In : 04/11/2025 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:51
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:148 / 4565
Contractor:Andover Construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/10/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:11:30 MDT
Cast:11:45 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:North of Building A curb & gutter
Sample Location / Notes:@ 7/13 yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:K35565
On-Site Admixtures: 7.00 Gal Water (7 yd³), 64.00 Oz ARA-Air Reducing Admixture (7 yd³)
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:140.2 (lb/ft³)
Air Content:8.0
Load Volume:7.00 (yd³)
Weather:Slump (in):5
Air Temperature (F):Concrete Temp (F):73
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 141980
04/10/2025
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 04/21/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
52-1 7 04/21/25 1 / 6 4.00 12.57 48,278 3,840 3 N
Test Age Average Strengths (psi): 7 Day - 3840
Tested By: Sandon Thibault (1)
Checked In : 04/15/2025 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:52
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:167 / 4573
Contractor:Andover construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/14/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:11:30 MDT
Cast:11:45 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:East of Building A curb & gutter
Sample Location / Notes:@9/9 yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:K35565
On-Site Admixtures: None
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:141.2 (lb/ft³)
Air Content:6.2
Load Volume:9.00 (yd³)
Weather:Slump (in):4
Air Temperature (F):Concrete Temp (F):68
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 142156
04/14/2025
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 04/28/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
53-1 7 04/23/25 1 / 6 4.00 12.57 53,051 4,220 3 N
Test Age Average Strengths (psi): 7 Day - 4220
Tested By: Sandon Thibault (1)
Checked In : 04/17/2025 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:53
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:167 / 2428
Contractor:Andover construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/16/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:11:30 MDT
Cast:11:45 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:Sidewalk and curb along the north side of Building A.
Sample Location / Notes:@10/20+ yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:K35565
On-Site Admixtures: None
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:140.0 (lb/ft³)
Air Content:7.0
Load Volume:10.00 (yd³)
Weather:Slump (in):4
Air Temperature (F):Concrete Temp (F):65
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 142295
04/16/2025
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 04/28/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
54-1 7 04/24/25 1 / 6 4.00 12.57 48,054 3,820 3 N
Test Age Average Strengths (psi): 7 Day - 3820
Tested By: Sandon Thibault (1)
Checked In : 04/18/2025 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:54
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:166 / 4621
Contractor:Andover construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/17/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:11:30 MDT
Cast:11:45 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:Northeast and Northwest corners of Building A
Sample Location / Notes:@8/8 yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:K35565
On-Site Admixtures: 12.00 Gal Water (8 yd³)
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:139.1 (lb/ft³)
Air Content:7.2
Load Volume:8.00 (yd³)
Weather:Slump (in):5
Air Temperature (F):Concrete Temp (F):68
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 142356
04/17/2025
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 04/28/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
55-1 7 04/28/25 1 / 6 4.00 12.57 57,025 4,540 3 N
Test Age Average Strengths (psi): 7 Day - 4540
Tested By: Sandon Thibault (1)
Checked In : 04/22/2025 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:55
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:166 / 4627
Contractor:Andover Construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/21/25
Sampled From:Chute
Placement Method:Chute
Sample Details
Batched:
Sampled:13:15 MDT
Cast:13:30 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:North of Building C curb and gutter.
Sample Location / Notes:@6/6 yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:K35565
On-Site Admixtures: 4.00 Gal Water (6 yd³)
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:141.8 (lb/ft³)
Air Content:5.9
Load Volume:6.00 (yd³)
Weather:Slump (in):4
Air Temperature (F):Concrete Temp (F):68
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 142473
04/21/2025
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 05/05/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
56-1 7 04/29/25 1 / 6 4.00 12.57 49,248 3,920 3 N
Test Age Average Strengths (psi): 7 Day - 3920
Tested By: Sandon Thibault (1)
Checked In : 04/23/2025 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:56
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:06 / 4629
Contractor:Ashley Concrete
Structures
Technician:Peskuski, Ryan
Cast By:Peskuski, Ryan
Date Cast:04/22/25
Sampled From:Chute
Placement Method:Chute
Sample Details
Batched:07:13 MDT
Sampled:08:15 MDT
Cast:08:30 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:Building C. Curb and gutter northwest side of the building.
Sample Location / Notes:Sampled at 6 of 6 yards.
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:CDOT #2019076 B,D,P
On-Site Admixtures: 8.00 Gal Water (6 yd³)
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:140.6 (lb/ft³)
Air Content:6.0
Load Volume:6.00 (yd³)
Weather:Consistency:Slump
Air Temperature (F):Concrete Temp (F):45
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 142503
04/22/2025
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 05/05/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
57-1 7 04/30/25 1 / 6 4.00 12.57 46,977 3,740 5 N
Test Age Average Strengths (psi): 7 Day - 3740
Tested By: Sandon Thibault (1)
Checked In : 04/24/2025 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:57
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:156 / 4642
Contractor:Andover Construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/23/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:13:30 MDT
Cast:13:45 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:West of Building C curb and gutter
Sample Location / Notes:@6/6 yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:K35565
On-Site Admixtures: None
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:141.2 (lb/ft³)
Air Content:6.5
Load Volume:6.00 (yd³)
Weather:Slump (in):4
Air Temperature (F):Concrete Temp (F):70
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 142607
04/23/2025
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 05/05/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
58-1 7 05/01/25 1 / 6 4.00 12.57 47,292 3,760 3 N
Test Age Average Strengths (psi): 7 Day - 3760
Tested By: Sandon Thibault (1)
Checked In : 04/25/2025 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:58
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:162 / 4648
Contractor:Andover Construction
Technician:Cozza, Seth
Cast By:Cozza, Seth
Date Cast:04/24/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:10:00 MDT
Cast:10:15 MDT
Truck Empty:
Placement Time:
Placement Location:Sidewalk
Location Details:North of Building C sidewalk and curb
Sample Location / Notes:@20/20 yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:K35565
On-Site Admixtures: None
Location
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:140.8 (lb/ft³)
Air Content:5.8
Load Volume:10.00 (yd³)
Weather:Slump (in):4
Air Temperature (F):Concrete Temp (F):68
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 142739
04/24/2025
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 05/09/2025
Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
59-1 7 05/02/25 1 / 6 4.00 12.57 54,315 4,320 3 N
Test Age Average Strengths (psi): 7 Day - 4320
Tested By: Sandon Thibault (1)
Checked In : 04/26/2025 (1)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:59
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:66 / 4660
Contractor:Ashley Concrete
Technician:Peskuski, Ryan
Cast By:Peskuski, Ryan
Date Cast:04/25/25
Sampled From:Truck
Placement Method:Chute
Sample Details
Batched:
Sampled:07:45 MDT
Cast:08:00 MDT
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:Radius curb and gutter from center drive, north towards Building A
Sample Location / Notes:@6/6+ yards
Batch Log
Strength:4500 (psi)
Specifications
Supplier:Casey Concrete Mix Design:CDOT #2019076 B,D,P
On-Site Admixtures: None
Location
Min / Max Temp (F):65/65
Standard Cure Field Cure
Field Measurements
Plastic Unit Weight:142.8 (lb/ft³)
Air Content:4.6
Load Volume:10.00 (yd³)
Weather:Consistency:Slump
Air Temperature (F):Concrete Temp (F):49
Lab Test Results
Testing Lab: Glenwood Springs, 234 Center Drive, Glenwood Springs, CO, 81601
General Remarks
Notified contractor of physical property results. Reviewed by RB.
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Andover Management Group
Louisville, KY 40202
333 East main Street
Suite 300
Project:
214 Center Drive
GS06693.001F-365
Garfield County, CO
214 Center Drive
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 142740
04/25/2025
Glenwood Springs
234 Center Drive
Glenwood Springs, CO 81601
Phone: 970-945-2809
Report Date: 05/09/2025