HomeMy WebLinkAboutEngineer's OWTS Design Planr s ti I�:P7`IC C'O\�ii�L1 I\C� February 24, 2022 CBO INC. 129 CAINS LANE CARBONDALE, CO 81623 970.309.5259 OARLA.OSTBERG@GM AI L.COM Project No. C1697 Tom Lester to m I . ieste rdev elopme nt. coni Onsite Wastewater Treatment System (OWTS) Preliminary Planning TBD Skipper Drive Garfield County, Colorado Tom, CBO Inc. has visited the subject property to assess onsite wastewater treatment system (OWTS) alternatives for the existing and proposed development on the property. There was significant snow cover at the time of our visit. The 4.945-acre property is located outside of Carbondale, in an area where OWTSs are necessary. The legal description of the property is as follows: Section: 29 Township: 7 Range: 87 Subdivision: STIRLING RANCH PUD Lot: 5 Parcel ID: 2391-293-05-005 EXISTING CONDITIONS The property is currently undeveloped. A 5-bedroom single-family residence is proposed. The proposed development will be served potable water by a community water system. The water line will enter the property from the subdivision road to the north. No OWTS component will come within 25- feet of any water line. The proposed STA will be located to the southeast of the proposed residence. The area is vegetated with native grasses, sage, and pinion trees and has an approximate 15% slope to the southeast. SOILS The subsurface was investigated by both All Service Septic and HP Geotech in 2006. All Service Septic documents their findings in a report dated October 18, 2006, Project No. 1263 (enclosed). One Test Pit was excavated and three percolation tests were run. The Test Pit consisted of silty clayey, silty sand to 1.5-feet, underlain by colluvial cobbles and small boulders in a silty sand matrix to a maximum depth explored of 8.5-feet. No groundwater or bedrock was encountered. Percolation tests ranged from 8 to 27 minutes per inch(MPI) with an average of 18 MPI. HP Geotech documents their findings in a report dated October 16, 2006, Job No 106 0877 (enclosed). One Profile Pit was excavated in the proposed STA. The Profile Pit consisted of topsoil to 1.0-feet, underlain by basalt cobbles and boulders in a silt and sand matrix, medium dense to dense, slightly moist to moist, light brown to white calcareous. A gradation was taken from a sample of the soil taken 7 to 8- feet below grade from Pit 1 (excavated north of the proposed foundation) and resulted in 53% gravel, 22% sand, and 25% silt and clay. Page 2 These results are consistent with soils typical in this area. For preliminary planning purposes, we are classifying the soils as Soil Type 2. A long-term acceptance rate (LTAR) of 0.6 gallons per square foot will be used to design the OWTS. Prior to completion of the final OWTS design, a subsurface evaluation meeting the requirements outlined in current OWTS regulation will be required. PRELMINARY OWTS DESIGN Design Calculations: 3 bedrooms x 75 GPD/person x 2 ppl/bedroom + 150 GPD (4th and 5th bedrooms) = 600 GPD 600 GPD / 0.6 gal/SF = 1000 SF 1000 SF x 1.0 (gravity trenches) x 0.7 (chambers) = 700 SF 700 SF / 12 SF/chamber = min. 59 "Quick 4' Infiltrator® chambers The proposed OWTS will accommodate 5-bedrooms in the residence. The proposed OWTS will consist of a 1500-gallon, two -compartment septic tank with an Orenco® Biotube Effluent filter. Effluent will gravity flow to a distribution box and then to four gravelless chamber trenches, each with 15 `Quick 4' Infiltrator® chambers for a total of 60 chambers and 720 SF of infiltrative area. Please call with questions. Sincerely, CBO Inc. ow,- O's-4t'A's Carla Ostberg, MPH, REHS m � � ao'o 3 �� v m m -S 0 o O N o C CD r �o r 0 vv v m N m (U `GC:r a N Q N O n o Wtj O N C T (D m CD O T r -a n p �3c� — Z Z 0 m N T aZ,,c� _ �� Z m<O� Z C p -U p 0 Az=m N Z C N N m v_ z E 0 z m 2DZ� 02;oDZ 710= m Omwmlm c c �oomvmm �mCD;upD OO Cz Z. -nO0R Z m Z, I O mw En 0 0.-iv-np Xmmc_ O 0 m055AO A xO S O w m- lzZO� �O M. C)M Mw XZ�OcO D w0zmK Hamm{z O y T p S z o FZ c m w nNC.) I �z OZl OD m z N m w w .1 `y OZ z m O 0 O z N 3 d�0 1 1 tl �IJ n l Q V N N `I �iP pro C coo r °•tea 0 3 \. 21 r rn a _ XN i d m mX f Z o- no m g OPP 54 n p -a Z n � m c o cr i(33 3 ? v CCC .. 0 p N o o o V o a) ( K A r SCR ZZ!� o� �o �Ta 0 0 1. r ZT : r cn O Hymn zo �1 m y* 00 m 1aTi=n Tn _v O3: coWA ZD _TTx 1mC- Co co M m m� < ZO nu-4 Z (l)Z I W n KZD Z1 " Wm nm rxn:U Z WWn mx yw Z W mm X m m Z O Wpmm m m(n 0m m z 1 ZT pm 1A X� m m p� X O �m D �O m - n x _ � Z 1 Z11 n x m Z n x b LLI 'J (1�y45ti454 10 : y wv-. u s OCT-23-2N6 15:25 From:HP-GEOTECH }{,•I,�,,ni1+ I's�sIiL 0cosechm_.11, Irn 5.}�:Z C .nnNl ii,ri.l 15� I'i•wnw 070Q15 aiR,> G Of *t .'k' 97LI )45 HEPWORTH-PAWLAK GEOTECHNICAL -M d: hpwi,iD�Nr''Fr.h r.sns October 16, 2006 Jon Burnett P.O. Box 6 Carbondale, Colorado 81623 Job No.106 0877 Design, Proposed Kesidence, Lot 5, Stirling Subject: 6ubsoil study for f bundatian Ranch P.U.D., Garfield County, Colorado Dear Mr. Burnett: As requested, Ilepworth-Pawlak (ieotechnical,lnc. performed a subsoil study far desigi► of foundations at the subject site. The study was conducted in accordance with our agreement for geotechnical en6dneering services to you dated October 5, 2006. The data obtained and our recommendations based on the proposed construction and subsurface conditions encountered are presented in this report. proposed Constrnc&u-. The proposed residence will be a two story wood frame structure above a crawlspace with an attached garage. The budding footprint is shown on Figure 1. Garage floor will be slab -on -grade. Cut depths are expected to range between about 2 to 4 feet. Foundation loadings for this type of construction are assumed to be relatively light and typical of the proposed type of construction. if building conditions or foundation loadings are significantly different from those described above, we should be notified to re-evaluate the recommendations presented in this report. Site Conditions: The site is located on the south side of Skipper Drive. Vegetation consists of pinion and juniper trees with sage brush, grass and weeds. The ground surface is relatively flat in the building area and moderately steep down to the west and east with grades of about 20 to 25 percent. Basalt cobbles and houlders are visible on the ground surface. Parker 303-841-7119 • Colorado Sprrnp 719-633-5562 + Sllverrhorne 970-468.1959 .� . w ..wu �.J �u � r �rrr• r n �,uu r udr i � r u� .�.� . v • � r yr..ti.rru r .. . � � -2- Subsurface Conditions: The subsurface conditions at the site were evaluated by excavating two exploratory pits in the building area and a profile pit in the septic disposal area at the approximate locarions shown on figure 1. The logs of the pits are presented on Figure 2. The subsoils encountered, below about one foot of topsoil, consist of basalt cobbles and boulders in a silt and sand matrix. Results of a gradation analysis performed on a sample of basalt gravel (minus 5 inch fi•action) obtained from the site are presented on Figure 3. No fi-ee water was observed in the pits at the time of excavation and the soils were slightly moist to moist. Foundation Recommendations: Considering the subsoil conditions encountered in the exploratory pits and the nature of the proposed construction, we recommend spread footings placed on the undisturbed natural soil designed for an allowable soil bearing pressure of 2,000 psf for support of the proposed residence. The matrix soils tend to compress after wetting and there could be some post -construction foundation settlement. Footings should be a minimum width of 16 inches for continuous walls and 2 feet for columns. Utility trenches and deep cut areas may require rock excavating techniques such as chipping or blasting. Loose and disturbed soils encountered at the foundation bearing level within the excavation should be removed and the footing bearing level extended down to the undisturbed natural soils_ Voids created from boulder removal at footing grade should be filled with a structural material such as road base compacted to 95 percent standard Proctor density at a moisture content near optimum. Exterior footings should be provided with adequate cover above their bearing elevations for frost protection. Placement of footings at least 36 inches below the exterior grade is typically used in this area. Continuous foundation walls should be reinforced top and bottom to span local anomalies such as by assuming an unsupported length of at least 10 feet. Foundation was acting as retaining structures should be designed to resist a lateral earth pressure based on an equivalent fluid unit weight of at least 50 pef for the on -site soil as backfill. lob No. i06 0877 C,+3�c�beGh ul. 1 -C.3-L'OUb lt5; o f F r om: Hr-l7Gu 1 Lk_m ti t 177 JL9`IJ i 1 0: 7 r u7: OiJJ r J -3- Floor Slabs: The natural on -site soils, exclusive of topsoil, are suitable to support lightly loaded slab -on -grade construction. To reduce the effects of some differential movement, floor slabs should be scparatcd from all bearing walls and columns with expansion joints which allow unrestrained vertical movement. Floor slab control joints should be used to reduce damage due to shrinkage cracking. The requirements for joint spacing and slab reinforcement should be established by the designer based on experience and the intended slab use. A minimum 4 inch layer of free -draining gravel should be placed beneath basement level slabs to facilitate drainage. This material should consist of minus 2 inch aggregate with less than 50% passing the No. 4 sieve and less than 2% passing the No. 200 sieve. All fill materials for support of floor slabs should be compacted to at least 95% of maximum standard .Proctor density at a moisture content near optimum. Required fill can consist of the on -site soils devoid of vegetation, topsoil and oversized rock. Underdrain System: Although free water was not encountered during our exploration, it has been our experience in mountainous areas that local perched groundwater can develop during times of heavy precipitation or seasonal runoff. Frozen ground during spring runoff can create a perched condition. We recommend below -grade construction, such as retaining walls and crawlspacc arcas, be protectcd from wetting and hydrostatic pressure buildup by an underdrain system. The drains should consist of drainpipe placed in the bottom of the wall backfill surrounded above the invert level with free -draining granular material. The drain should be placed at each level of excavation and at least I foot below lowest adjacent finish grade and sloped, at a minimum 1 % to a suitable gravity outlet. Free -draining granular material used in the underdrain system should contain less than 2% passing the No. 200 sieve, less than 50'/o passing the No. 4 sieve and have a maximum size of 2 inches. The drain gravel backfilI should be at least 1 %: feet deep - Job N& 1 O6OM Ul. I -ei-ewub i': ed f r om: W-UhU I tl.H �J (bye4tk:H59 I o : 9 709360375 P. 5'9 -4- Surface Drainage: The following drainage precautions should be observed during construction and maintained at all times after the residence has been completed: 1) Inundation of the foundation excavations and underslab areas should be avoided during construction. 2) Exterior backfill should be adjusted to near optimum moisture and compacted to at least 95% of the maximum standard Proctor density in pavement and slab areas and to at least 90% ol'the maximum standard Proctor density in landscape areas. Free -draining wall backfill should be capped with about 2 feet of the on-si.e, finer graded soils to reduce surface water infiltration. 3) The ground surface surrounding the exterior of the building should be sloped to drain away from the foundation in all directions. We recommend a minimum slope of 12 inches in the first 10 feet in unpaved areas and a minimum slope of 3 inches in the first 10 feet in pavement and walkway areas. 4) Roof downspouts and drains should discharge well beyond the limits of all backfill. 5) Landscaping which requires regular heavy irrigation should be located at least 5 feet from the building. Consideration should be given to the use of xeriscape to limit potential wetting of the matrix soils below the foundation caused by irrigation. Unitations: This study has been conducted in accordance with generally accepted geotechnical engineering principles and practices in this area at this time. We make no warranty either express or implied. The conclusions and recommendations submitted in this report are based upon the data obtained from the exploratory pits excavated at the locations indicated on Figure I and to the depths shown on Figure 2, the proposed type of construction, and our experience in the area. Our services do not include determining the presence, prevention or possibility of mold or other biological contaminants (MOBC) developing in the fuVare. If the client is concerned about MOBC, then a professional in this special field of practice should be consulted. Our findings include interpolation and Job No.106 OV7 OCT-23-2006 15:30 From:HP-GEOTECH 970945EH54 Io:yrby3bb.sr� -5- extrapolation of the subsurface conditions identified at the exploratory pits and variations in the subsurface conditions may not become evident until excavation is performed. If conditions encountered during construction appear di fferent from those described in this report, we should be notified at once so re-evaluation of the recommendations may be made. This report has been prepared for the exclusive use by our client for design purposes. We are not responsible for technical interpretations by others of our information. As the project evolves, we should provide continued consultation and field services during construction to review and monitor the implementation of our recommendations, and to verify that the recommendations have been appropriately interpreted. Sigrtificant design changes may require additional analysis or modifications to the recommendations presented herein. We recommend on -site observation of excavations and foundation bearing strata and testing of structural fill by a representative of the geotechnical engineer. If you have any questions or if we may be of Further assistance, please let us know. Respectfully Submitted, HEPWORTH - PAWLAK GEOTECHNICAL, INC. uis E. Eller Reviewed by: L.4� S. Daniel E. Hardin, P.F. LEE/ vad attachments Figure l — LocajMKmff"Zpioratory Figure 2 — Logs of Exploratory Pits Figure 3 — Gradation Test Results Pits cc: Patrick Stuckey Architects — Attn: Patrick Stuckey Job No.106 0877 — G 7165 7170 7160 / loe PIT 1 7160 f / r f PROPOSED RESIDENCE f 7165 i f f / / 7180 / / r I PR 2 f ` � f / 7180 � r 7170 / 7175 APPROXIMATE SCALE 1" =4U' 7175 7175 / PERC / HOLE PROFILE / PIT / Q PMC PERC ND HOLE PROPOSED SEPTIC FIELD 106 W77 I !M I LOCATION OF EXPLORATORY PITS , Figure 1 PIT 1 PIT 2 vmLn-ILt rii ELEV. = 7176' ELEV.— 717 P ELEV. = 7175' 0 0 .• U. LL 5 5 1C 10 LEGEND: ® TOPSOIL; organic slit and clay, sandy, cobbles and boulders, firm, moist, dark brown. BASALT COBBLES AND BOULDERS (GM); in a sill and sand matrix, medium dense to dense, slightly moist to moist, light brown to white, calcareous. Disturbed bulk sample. NOTES: 1. Exploratory pits were observed on October 5, 2006 and had been dug with a backhoe prior to our site visit. 2. Locations of exploratory pits were measured approximately by pacing from features shown on the site plan provided. 3. Elevations of exploratory pits were obtained by interpolation between contours shown on the site plan provided and checked by instrument level. 4. The exploratory pit locations and elevations should be considered accurate only to the degree implied by the method used. 5. The lines between materials shown on the exploratory pit logs represent the approximate boundaries between material types and transitions may be gradual. 6. No free water was encountered in the pits at the time of excavating. Ructuation in water level may occur with tine. 7. Laboratory Testing Results: +4 = Percent retained on the No. 4 sieve -200 - Percent passing No. 200 sieve 1060877 �'. LOGS OF EXPLORATORY PITS I Figure 2 ]R� < < PO&K M4 .. &"roo0*W%C081M Ph9706165033 RX303-216-2796 October 18, 2006 Patrick Stuckey P.O. Box 532 Basalt, Colorado 81621 Onsite Wastewater System Design, Proposed Residence Lot 5, Stirling Ranch Subdivision 0797 Skipper Drive Garfield County, Colorado Mr. Stuckey, Project No. 1263 ALL SERVICE septic, LLC has performed a subsurface investigation and prepared an onsite wastewater system (OWS) design for the subject residence. The subsluFace investigation was performed on October 4, 2006. The property is located in an area where OWS are necessary. SITE CONDMONS A five -bedroom residence and an A.D.U. are proposed as indicated on plans provided. The site is currently vacant. The slope is approximately 5% to the southeast. Vegetation consists of a moderate cover of native grasses with pifion trees and cacti. Water will be provided to the site by an onsite well to be located greater than 100 feet from the proposed drain field area. SUBSURFACE The subsurface was investigated by excavating an 8.5-foot test pit near the proposed drain field location as shown on attached plans. Three percolation holes were dug. Subsurfikee conditions consisted of slightly clayey, silty, sand to 1.5 feet, underlain by colluvial cobbles and small boulders in a silty, sand matrix to the maximum depth explored of 8.5 feet. Groundwater or bedrock was not encountered. Percolation rates ranged f om 8 to 27 minutes per inch (MPI) with an average rate of 18 UPI. DESIGN SPECIFICATIONS The OWS design is based on 5 bedrooms for the main residence, I bedroom for the A.D.U., an average sewage load of 1050 GPD, and a percolation rate of 18 UPI. The installation must include a. 1500-gallon, two -compartment, concrete septic tank with an effluent filter in the second compartment at the main residence and a 1000-gallon, two -compartment, concrete septic tank with an effluent filter in the second compartment at the A.D.U. Tank alternatives may be considered. Four gravelless Onsite Wastewater Systems Page 2 chamber -trenches must be installed as indicated on plans provided. Four rows of 18 `Quick 4' chambers, for a total of 72 chambers and 705.6 ft of infiltrative area are required. Serial overflow distribution should be used to distribute effluent. Construction must be according to the county ISDS regulations, the septic permit provided by Garfield County Environmental Health Department, and this design. OPERATION INFORMATION AND MAINTENANCE The surface of the drain field should be seeded upon completion. Vegetation is an important factor in drain field performance. Erosion control should be practiced during and after construction. Geo- fabrics or plastics should not be used over the drain field. Livestock should not graze on the drain field. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWS. For Example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a drain field. The homeowner should pump the septic tank every two years and clean the effluent filter as needed. Garbage disposal use should be minimized, and non -biodegradable materials should not be placed into the OWS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWS. No hazardous wastes should be directed into the OWS. Mechanical room drains should not discharge into the OWS. The OWS is engineered for domestic waste only. If easements have been encroached upon, it is the homeowner's responsibility to understand potential issues. We can be contacted for information regarding easements. ADDITIONAL CONSTRUCTION NOTES If design includes a pump, air release valves and weep holes should be installed to allow pump lines to drain to minimize risk of freezing. Excavation equipment must not drive in excavation of drain field due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Precast concrete tanks and distribution boxes should be used, unless plastic or fiberglass is required. Septic tank risers should extend to grade. Access to all tank compartments and distribution devices is optimal. INSTALLATION OBSERVATIONS ALL SERVICE septic, LLC, and the county must view the OWS during construction. The OWS' observation should be performed before backfill, after placement of chambers and distribution pipes. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. ALL SERVICE septic, LLC should be notified 48 hours in advance to observe the installation. Onsite Wastewater Systems Page 3 LBM: Results are based on field investigations and data provided by the client. If soil, or any other conditions, encountered are different from conditions described in report, ALL SERVICE septic, LLC should be notified. Please call with questions. Sincerely, ALL SERV septic, LLC Timothy R. Petz 3 copies sent Reviewed By: Richard H. PARTIAL SITE PLAN AND LOCATION OF PERCOLATION HOLES NOTE: NO WELLS MAY BE LLOCATED WITHIN 100' OF PROPOSED DRAIN FIELD / / I PROPOSED DRIVEWAY PROP ED 5-BEDROOM RESIDENCE SCALE 1' = 40' NORTH i P oP . ED AI FI D R P-I TEST PIT i i P-3 P-2 PROPOSEDI-BEDROOM ADU THE LOCATION OF EXISTING AND PROPOSED IMPROVEMENTS SHOWN HEREIN; AND THE WELL AND/OR DRAIN FIELD LOCATIONS STAKED AT THE SITE; ARE NOT THE RESULT OF A PROPERTY SURVEY. IMPROVEMENT LOCATIONS ARE APPROXIMATE. IT IS THE PROPERTY OWNER'S RESPONSIBILITY TO DEFINE PROPERTY BOUNDARIES AND ENSURE ALL ONSITE IMPROVEMENTS ARE LOCATED WITHIN THE PLATTED SITE AND OUT OF INAPPROPRIATE EASEMENTS. ALL SEPARATION DISTANCES ARE TO BE VERIFIED PRIOR TO EXCAVATION. 0797 SKIPPER DRIVE ALL PROJECT NO. 1263 GARFIELD COUNTY, COLORADO SERVICE SEPTIC, LLC FIGURE I 970-618�5033 W O = Y w ^ U) -J Z W Z Q W U �� J J W O W V 1 Z WO Z~~O ~ U Z�' QLLJ-i co �Z ��Dw LU Z ~� �Qw>w= Q _ 2 m XW LL LL LL OU >. [L LL-(D N 3U OJW WWZ W wl- ZLYwHTr- W fn Z � LY (n U) F- Q O W Q� > } m0 > 0 O H O O _ E _ � C pZFco - (?mUOQ o�� ` uiwaw30 0 A� IN r� LU w z z LL O J w ,� Q Z�w w N Z o U D fr t L� wLL �> u W Q W J � v Q 0 I Zo z LLUU w ;r J W U cn = op,cn L- Q � U Y � U Z d W g`kl< ZZLLuu ._ mo o �3W C- V = H UF-O Q _U LY LU �EL ~h- J_ z in W F- W LU IX Z j 2uw W) %D N o N z LIJ w D O a- LL 0 0 0 u w 0 Z �D LLJ 0 0- U CL p Y J Cn LU t\ V- OQ o cD L^AIIV rILLL) Ur- II AILJ f DESIGN 5-BEDROOM RESIDENCE = 750 GPD 1-BEDROOM ADU = 300 GPD TOTAL LOADING = q =1050 GALLONS PER DAY PERCOLATION RATE = t =18 MINUTES PER INCH (MPI) CALCULATED AREA = (1.5 X q X sgrtt15) = 1336 SF MINIMUM AREA = 1146 SF X 50% REDUCTION = 668 SF TYPICAL CROSS-SECTION - N.T.S. 1 WSDR 35 OBSERVATION/ ENT PIPE WITH CAP 4' MAX L 6' MIN. X, F1L TEP I1-7EL 1-L _IE"E ;•IE"E li- PLAN VIEW - TYP. 4" EFFLUENT LINE T(')T-L - FOUP TPEI IC:HES -•:t FILL TRENCH SPECIFICATIONS WIDTH OF TRENCHES = 3 FEET =1 CHAMBER LENGTH OF TRENCHES = 72 FEET =18 CHAMBERS TOTAL NUMBER OF'QUICK4 CHAMBERS = 72 TOTAL INFILTRATIVE AREA = 705.6 SF FOUR TOTAL TRENCHES INFILTRATOR(R) QUICK4(TM) CUT SHEET 2' (EFFECTIVE LENGTH) BASALT BOULDERS REMOVED DURING CONSTRUCTION SHOULD BE REPLACED WITH COMPACTED SAND FILTER MATERIAL 3' J INFILTRATOR(R) QUICK4(TM) --n r— 1'-4" CHAMBERS. 3' x 4' I*] 4" PVC SERIAL OVERFLOW LINES QUICK4(TM) END CAPS OBSERVATION/VENT PIPES (TYP.) 6' MIN. 1'-4" 1 v ruul 1 Iv1vrL , 11",-1 . 0797 SKIPPER DRIVE ALL PROJECT NO. 1263 GARFIELD COUNTY, COLORADO SERVICESEPTIC,IIC FIGURE 3 970.61&5033 1 'I kCM E 0 Q 0 N 0 U W >r M . 0 RIC, LU 0 U CL 0 Uw A O U i ` GARFIELD COUNTY ENVIRONMENTAL HEALTH DEPARTMENT Percolation Test and Soils Data Form - TABLE 1 - PROJECT 1263 PROFILE PIT Date of Test: 10/04/06 0 -1.5' Sand, silty, slightly clayey, moist, dark brown, micaceous, root zone 1.5' - 8.5' Colluvial cobbles in a silty, sand matrix, moist, tan, white, calcareous No Groundwater or Bedrock was Encountered Hole Hole Intmal Measuraementat Mnasuvnentat Change (n.) Percolation Rabe No. Depth (in.) (rain.) Siam of Interval End of Interval (min.fin.) MPI (in) fn.) 1 36 10 3.88 6.13 2.25 10 3.63 5.25 1.63 10 5.25 6.63 1.38 10 6.63 7.75 1.13 10 7.75 8.50 0.75 10 8.50 9.00 0.50 20 2 29 10 2.50 5.50 3.00 10 2.13 4.38 2.25 10 2.50 4.13 1.63 10 4.13 5.00 0.88 10 5.00 5.50 0.50 10 5.50 5.88 0.38 27 3 31 10 2.25 4.88 2.63 10 2.00 4.25 2.25 10 4.25 6.25 2.00 10 2.25 4.50 2.25 10 4.50 6.25 1.75 10 6.25 7.50 1.25 8 AVG=IS MPI c Tj1 W F I i r i •o*tee® ��._{� a; MI f� ® 81 h \ dk Rn i e Mil #N,,gPubIic.net Garfield County, CO Account Number R008780 Physical Address OSKIPPER DR 2019Total Actual Value $275,000 Parcel Number 239129305005 CARBONDALE 81623 Acres 5 Owner Address SKIPPERDRIVELLC Land SgFt 0 PO BOX 3302 Tax Area 011 ASPEN CO 81612 2019 Mill Levy 79.7760 Date created: 2/25/2022 Last Data Uploaded: 212512022 3:15.45 AM Developed by4,1 Schneider GE.;>;rnr i AL Overview Legend ❑ Parcels Roads Parcel/Account Numbers Highways a Limited Access — Highway Major Road -- Local Road — Minor Road Other Road Ramp Ferry Pedestrian Way Owner Name Lakes & Rivers — County Boundary Line Last 2 Sales Date Price 9/15/2021 $0 7/19/2021 $0 2/24/22, 1:00 PM gPublic.net - Garfield County, CO - Property Record Card: R008780 gPublic.net Garfield County, CO Summary Account R008780 Parcel 239129305005 Property 0 SKIPPER DR, CARBONDALE. CO 81623 Address Legal Section: 29 Township: 7 Range: 87 Subdivision: STI RLI NG RANCH Description PUD Lot: 5 4.945 ACRES Acres 4.945 Land SgFt 0 TaxArea 11 Mill Levy 79.7760 Subdivision STIRLING RANCH PUD View Map Owner SKIPPER DRIVE LLC PO BOX 3302 ASPEN CO 81612 Land Unit Type VACANT RESLOTS -0100(VACANT LAND) Square Feet 0 Actual Values Assessed Year 2021 2020 Land Actual $275,000.00 $275,000.00 Improvement Actual $0.00 $0.00 Total Actual $275,000.00 $275,000.00 Assessed Values Assessed Year 2021 2020 Land Assessed $79,750.00 $79,750.00 Improvement Assessed $0.00 $0.00 Total Assessed $79.750.00 $79,750.00 Tax History Tax Year 2021 2020 2019 2018 2017 Taxes Billed $6,362.12 $6,024.16 $6,077.68 $5,482.96 $5,241.04 Click here toview he Int r ati n for l h� a,rcel an the Gari�eld�,Qunt T easur r' ti i e_ Transfers Sale Date Deed Type Reception Number Book - Page Sale Price 9/15/2021 AFFIDAVIT 345827 635-813 $0 7/19/2021 PERSONAL REP DEED 344443 632-220 $0 3/29/2021 WARRANTY DEED 953404 $350.000 3/29/2021 STATEMENT OF AUTHORITY 953403 $0 7/31/2006 QUITCLAIM DEED 705103 1835-0160 $0 3/3/2006 WARRANTY DEED 693565 1778-2 $475,000 3/3/2006 STATEMENT OF AUTHORITY 693584 1778-1 $0 5/14/2002 DECLARATION 603327 1354-672 $0 5/13/2002 AGREEMENT 603326 1354-662 $0 1/15/2002 SPECIAL WARRANTY DEED 596038 1322-402 $0 1/15/2002 WARRANTY DEED 596037 1322-401 $5.500.000 7/3/2001 PERSONAL REP DEED 584536 1269-478 $0 11/26/1999 LETTERS 558189 1169-631 $0 12/2/1985 RESOLUTION 365025 679-804 $0 7/19/1983 QUITCLAIM DEED 344442 632-219 $0 4/7/1981 QUITCLAIM DEED 315719 574-304 $0 12/14/1970 WARRANTY DEED 248558 416-75 $26,000 Property Related Public Documents Click here to view PropSLIX Related Public OccumenIs https://gpub]ic.schneidercorp.com/Application.aspx?AppiD=1038&LayerlD=22381&PageTypeID=4&PagelD=9447&KeyValue=RO08780 1/2 2/24/22, 1:00 PM gPublic.net - Garfield County, CO - Property Record Card: R008780 No data available for the following modules: Buildings, Photos, Sketches. The Garfield Countv Assessor's Office makes every effort to produce the most accurate information possible. No warranties, expressed or Developed by implied are provided for the data herein. its use or interpretation. Data is subject to constant change and its accuracy and completeness Schneider cannot be guaranteed. G E a S aA 7 1 AL User Privacy Polity, GDPR Privacy Notice t Dala Upload: 2/24/2022 12:10:43 AM Version 2.3.177 hftps;//qpublic.schneidercorp.com/Applicafion.aspx?ApplD=l 038&LayerlD=22381&PageTypelD=4&PageID=9447&KeyValue=R008780 2/2