HomeMy WebLinkAboutBlower Door TestTesting Company: Name: Address: Technician: Name:Elan Bouchet Credentials:BPI Building Analyst #: 5068881 Email:elan@netzerobuilders.com Building Information: Project ID:Sunlight Dr Address:148 Sunlight Dr Carbondale, CO 81623 Year Built:2025 Geo-Tag Data:Latitude: Longitude: Timestamp: Customer Information: Name: Address:148 Sunlight Dr Carbondale, CO 81623 Measured Leakage:2.25 ACH50 Leakage Target:3.00 ACH50 Compliance with Leakage Target:Pass Test ID:sunlight Dr Purpose of Test:Envelope (IECC) Measured CFM50:2,364.7 (+/- 2.4%)Effective Leakage Area: 118.3 in² Building Volume:63,197.0 ft³Enclosure Surface Area: 7,954.0 ft² Coefficient (C):160.7 (+/- 18.2%)Exponent (n): 0.687 (+/- 0.050) Correlation Coefficient:0.99731 Test Standard:ASTM E779 (single mode)Test Mode: Depressurize Test Characteristics:Pre Indoor Temp: 71 °F Pre Outdoor Temp: 50 °F Altitude: 7,270.0 ft Post Indoor Temp: 71 °F Post Outdoor Temp: 50 °F Time Average Period: 10 seconds Test Date and Time:2025-10-16 10:33:43 Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline -0.9 -60.0 -60.0 -59.1 -28.1 2,577.6 Open Fan -54.0 -50.6 -49.7 -170.1 2,326.4 Ring A -48.0 -49.3 -48.4 -167.5 2,308.9 Ring A -42.0 -43.8 -42.9 -141.2 2,124.3 Ring A -36.0 -37.0 -36.1 -103.8 1,828.7 Ring A -30.0 -31.1 -30.1 -84.8 1,656.5 Ring A -24.0 -24.6 -23.7 -63.9 1,443.1 Ring A -18.0 -20.3 -19.3 -42.5 1,182.5 Ring A Baseline -1.0 Test Equipment: Flow Device:Model 3 110V Fan Pressure Gauge:DG1000 Serial #: 14795 Calibration Date: 2023-09-06 Deviations from Standard: None Comments: None Envelope Leakage Test Page 2 of 2Report by TEC Auto Test 1.10.0 (238), © 2024 The Energy Conservatory, Inc.