HomeMy WebLinkAboutComments-CorrectionsOrd �� Cv�`�'�►� J CORRECTION LIST: 1. RESUBMIT (2) full sized paper sets of REVISED ARCHITECTURAL PLANS referencing Garfield County's adopted 2018 International Energy Conservation Code IECC and Climate Zone 5B. As plans were originally drafted in June 2022, the previously adopted 2009 IECC edition and older R- values appear to be referenced. The more stringent 2018 IECC went into effect on June 30, 2023. Thank you. Response - Please see sheet CP-1 noting 2018 IECC as applicable energy code 2. RESUBMITTED plan sets should clearly state your chosen ENERGY COMPLIANCE PATH: 2.a. If you intend to build according to the PRESCRIPTIVE PATH using Table R402.1.2 2018 IECC, please state this in writing directly on the architectural plan sheet(s). Response - Please see sheet CP-1 2.b. If you intend to build according to the PRESCRIPTIVE PATH using a RESCHECK REPORT, then please state this in writing and submit a current RESCHECK REPORT with owner's name and job site address on the report. Response - Please see sheet CP-1 2.c. If you intend to construction under the PERFORMANCE PATH, using a HERS RATER and HERS RATING SOFTWARE REPORT, then supply HERS contact information and their prepared preliminary HERS report (s) for plans examination. Thank you. Response - NA 3. Media Room and Office spaces on sheet A-101 have no natural light or natural ventilation openings to the exterior. Can you please expound on what method of mechanical ventilation is anticipated for these two living spaces? Response - both the media room and office space shall utilize dedicated ERV's to ensure aesh air delivery at a rate to meet IRC 2015 R303.4 4. The 55 sq ft "office" space accessed from the master bedroom does not meet code minimum 7 ft room dimension nor minimum 70 sq ft minimum size for habitable rooms under the adopted 2015 International Residential Code Section R304. Please discuss other room configuration options with your client. Please alter or amend this office space to comply to the 2015 IRC Section R304 and resubmit (2) full size amended sheets A-101 for further review. Response -We have decided that this area u +e home shall be used Cbr auxiliary storage (closet space) and shall not be considered habitable space. REScheck*Web TM Compliance Certificate Project Information Project Title: ELR Residence Energy Code: 2018 IECC Location: Silt, Colorado Construction Type: Single Family Project Type: New Construction Project Sub Type: None Conditioned Floor Area: 3607 ft2 Glazing Area: 9% Climate Zone: 5b (6881 HDD) Project No: 1782171 All Electric: false Is Renewable: false Has Battery: false Has Charger: false Has Heat Pump false Construction Site: TBD COUNTRY ROAD 346 Owner/Agent: Esau Ruiz Designer/Contractor: Esau Ruiz SILT, CO 81652 GARFIELD COUNTY PARCEL NUMBER:217916103004 Project Notes: Report Title: ELR Residence Report Date: 10/29/25, 3:03 PM 1 of 12 Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value Prop. U- Factor/ F-Factor Req. U- Factor/ F-Factor Prop. UA Req. UA Ceiling: Flat Ceiling or Scissor 3607 49.0 0.0 0.026 0.026 94 94 Truss Garage Floor: Slab -On -Grade 102 10.0 0.540 0.540 0 0 (Unheated) Insulation depth: 2.00' Insulation position: Vertical Insulation Crawl Wall: Solid Concrete or 1419 19.0 15.0 0.030 0.055 27 49 Masonry Wall height: 4.00 Depth below grade: 0.50 Insulation depth: 3.00' North Facade: Wood Frame, 1170 21.0 0.0 0.057 0.060 46 48 16" o.c. Window Block: Wood Frame 80 0.300 0.300 24 24 1 - FRONT DOOR: Solid Door 30 0.300 0.300 9 9 (under 50% glazing) GARAGE DOOR BLOCK: Solid 216 0.300 0.300 65 65 Door (under 50% glazing) Door 2: Glass Door (over 50% 45 0.300 0.300 14 14 glazing) South Facade: Wood Frame, 1590 21.0 0.0 0.057 0.060 82 86 16" o.c. Window Block: Wood Frame 152 0.300 0.300 45 45 East Facade: Wood Frame, 1415 21.0 0.0 0.057 0.060 77 81 16" o.c. Window block: Wood Frame 70 0.300 0.300 21 21 West Facade: Wood Frame, 500 21.0 0.0 0.057 0.060 23 25 16" o.c. Window: Wood Frame 21 0.300 0.300 6 6 Door: Solid Door (under 50% 22 0.300 0.300 7 7 glazing) Door 1: Glass Door (over 50% 45 0.300 0.300 14 14 glazing) The % Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules. It DOES NOT provide an estimate of energy use or cost relative to a minimum -code home. Slab -on -grade tradeoffs are no longer considered in the UA or performance compliance path in REScheck. Each slab -on -grade assembly in the specified climate zone must meet the minimum energy code insulation R-value and depth requirements. Compliance Statement The proposed building design described here is consistent with the building plans, specifications, and other calculations submitted with the permit application. The proposed building has been designed to meet the 2018 IECC requirements in REScheck-Web and to comply with the mandatory requirements listed in the REScheck Inspection Checklist. Michael Blea 10.29.2025 Name - Title Signature Date Report Title: ELR Residence Report Date: 10/29/25, 3:03 PM 2 of 12 CNJ/Inspection Checklist Energy Code: 2018 IECC Requirements: 60% were addressed directly in the RESCheCk software Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Pre-Inspection/Plan Review Section Plans Field # Verified Verified & Req.ID Pre-Inspection/Plan Review Value Value Complies? Comments/Assumptions 103.1, Construction drawings and Complies 103.2 [PR1]1 documentation demonstrate energy code compliance for the Does Not amply building envelope. Thermal envelope represented on Not construction documents. servable Not pplicable 103.1, Construction drawings and O Complies Location on plans/spec: 103.2, documentation demonstrate D Does Not SEE NOTES ON CP-1 OF 403.7 energy code compliance for lighting omply ARCH DRAWINGS & MANUAL J [PR3]1 and mechanical systems. Systems serving n Not multiple dwelling units must servable demonstrate compliance with the IECC Commercial Provisions. Not pplicable 302.1, Heating and Cooling equipment Heating: Heating: Complies Location on plans/spec: 403.7 [PR2]2 is sized perACCA Manual S based on loads calculated per Btulhr Btu/hr Does Not MANUALJ ACCA Manual I or other methods omply approved by the code official. Cooling: Cooling: Btu/hr Not Btuthr servable PNot able Additional Comments/Assumptions: 1 1 High Impact (Tier 1) 1 2 1 Medium Impact (Ter 2) 1 3 1 Low Impact (Tier 3) Report Title: ELR Residence Report Date: 10/29/25, 3:03 PM 3 of 12 Foundation Inspection Section Plans I Field # Verified Verified & Req.ID Foundation Inspection Value Value Complies? Comments/Assumptions 402.1.2 Slab edge insulation R-value. R= R i� Q Complies See the Envelope table for [FOl] i 1� QDoes Not Assemblies values � Unheated Unheated C Mply Heated Heated Not Observable PNot pplicable 303.2.1 A protective covering is 0 Complies [F011]z instaEEed to protect exposed exterior insulation and extends Q Does Not a minimum of 6 in. below grade. Comply Not servable PNot licable 403.9 Snow- and ice -melting system [FO12]2 controls installed. 402.1.2 Slab edge insulation [F0311 depth/length. Complies ❑ Does Not Comply Ob Not servable Not pplicable �.ft ft 0 Complies Q Does Not Comply Not servable PANot pplicable Exception: Requirement is not applicable. I I See the Envelope I Assemblies table for values 402.2.11 Unvented crawl space wall i R= R� 0 Complies See the Envelope Assemblies table for [F0711 insulation R-value. Does Not values R= R= omply Not servable PNot plicable 303.2 Unvented crawl space wall 0 Complies [F08]1 insulation installed per Does Not manufacturer's instructions. omply Not servable Not pplicable 402.2.11 Unvented crawl space 0 Complies IFO911 continuous vapor retarder Installed over exposed earth, Does Not omply Joints overlapped by 6 in, and sealed, extending at least 6 in. Not [—] up and attached to the wall. servable PNot pplicable 402.2.11 Unvented crawl space wall in. 0 Complies See the Envelope [FO10]1 insulation depth of burial or in. Does Not Assemblies table for distance from top of wall. values m PRIy Not servable 0ppNot Additional Comments/Assumptions; Report Title: ELR Residence Report Date: 10/29/25, 3:03 PM 4 of 12 1 [High Impact (Tier 1) 1 2 1 Medium Impact (Ter 2) 1 3 1 Low Impact (Tier 3) Report Title: ELR Residence Report Date: 10/29/25, 3:03 PM 5 of 12 Framing / Rough -In Inspection Section # Framing /Rough -In & Req.ID Inspection 402.1.1, Door U-factor 402.3.4 [FR111 402.1.1, Glazing U-factor (area -weighted 402.3.1, average). 402.3.3, 402.5 [FR2]1 402.4.1.1 Air barrier and thermal barrier [FR23]1 installed per manufacturer's instructions. 402.4.3 Fenestration that is not site built [FR20]1 is listed and labeled as meeting AAMA /WDMA/CSA 101/1.5.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. 402.4.5 IC -rated recessed lighting [FR16]2 fixtures sealed at housing/interior finish and labeled to indicate 152.0 cfm leakage at 75 Pa. 1 403.3.1 Supply and return ducts in attics [FR12]1 insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the bui[din.9 insulated >= R-6 For diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Plans Field Verified Verified Value Value Complies? Comments/Assumptions U= U� Complies See the Envelope Assemblies table for Does Not values omply Not servable PANot pplicable i U� U �] Complies See the iesEnvelope to for Assemblies tablele Does Not values omply Not 6 servable PNot pplicable 403.3.2 Ducts, air handlers and filter j [FR13]1 boxes are sealed with joints/seams compliant with i1 International Mechanical Code or International Residential Code, as applicable. 403.3.5 Building cavities are not used as [FR15]3 ducts or plenums. { Complies PoDoesNot omply Ob Not servable Not pplicable Complies Does Not omply Not servable PNot plicable Complies o❑ Does Not Pomply Not servable PNot plicable Q Complies Does Not Comply PNot .servable Not pplicable Complies Does Not omply Not servable Not pplicable O Complies PDoes Not mply Not servable Not pplicable Exception: Ducts located completely inside the building envelope. Location on plane/spec: SEE NOTES ON CP-1 OF ARCH DRAWINGS Location on plane/spec. SEE NOTES ON CP-1 OF ARCH DRAWINGS Report Title: ELR Residence Report Date: 10/29/25, 3:03 PM 6 of 12 Section Plans Field # & Req.ID Framing / Rough -In Inspection Verified Value Verified Value Complies? Comments/Assumptions 403.4 HVAC pipin conveying fluids -F R {� R� Complies Exception: Requirement is [FR1712 above 105 or chilled fluids below 55 °F are insulated to >_R- 1 l Does Not not applicable. 3. omply ` Not servable Not pplicable 403.4.1 Protection of insulation on HVAC Complies Exception: Requirement Is not applicable. [FR24)1 piping. �] Does Not Pomply Not servable PpNot pplicable 403.5.3 Hot water pipes are insulated to R f = I I Rj� i�l Complies Location on plans/OF SEE NOTES N CP-1 OF [FR1817 ? R-3• Does Not I ARCH DRAWINGS omply Not servable Not pplicable 403,E Automatic or gravity dampers Q Complies [FR19),. are installed on all outdoor air Does Not intakes and exhausts. omply Not i servable 0ppNot { licable 303.13 U-factors of fenestration [FR411 products are determined in 'accordance with the NFRC test procedure or taken from the default table. Additional Comments/Assumptions: E) Complies PoDoesNot omply Not servable Not pplicable 1 High Impact (Ter 1) 2 Medium Impact (Tier 2) 3 Low Impact (tier 3) Report Title: ELR Residence Report Date: 10/29/25, 3:03 PM 7 of 12 Insulation Inspection Section Plans Field Verified Verified & Req.ID Insulation Inspection Value Value Complies? Comments/Assumptions 303.1 All installed insulation is labeled ❑ Complies [IN131- or the installed R-values provided. Does Not omply Not servable PNot pplicable i 402.1.1, Wall insulation R-value. If this is 1h R = R ❑ Complies See the Envelope Assemblies table for 402.2.5, 402.2.6 a mass wall with at least of the wall insulation on the wall ❑ Wood ❑ Wood Does Not values [IN3)1 exterior, the exterior insulation requirement applies (FR10). ❑ Mass ❑ Mass omply j� Not ❑ Steel ❑ Steel Qservable i Not pplicable 303.2 Wall insulation is installed per ❑ Complies IIN411 manufacturer's instructions. (] Does Not Pomply PNot .servable Not ]applicable Additional Comments/Assumptions: 1 1 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Report Title: ELR Residence Report Date: 10/29/25, 3:03 PM 8 of 12 Final Inspection Provisions Section Plans Field # Verified Verified & Req.ID Final Inspection Provisions Value Value 402.1.1, Ceiling insulation R-value. R_ R- 402.2.1, 402.2.2, Q Wood Q Wood 402.2.6 [FI1]1 0Steel 0 Steel I i 303.1.1.1, Ceiling insulation installed per 303.2 manufacturer's instructions. [FI211 Blown insulation marked every 300 ft2. N Complies? Complies PoDoesNot omply PNot ervable ONot plicable Complies Does Not omply Not servable PNot plicable Comments/Assumptions See the Envelope Assemblies table for values 403.1.2 Heat pump thermostat installed on heat 0 Complies Exception: Requirement is not applicable. [FI10]2 pumps. ❑ Does Not Comply Not servable Not ]pplicable 403.5.1 Y Circulating service hot water Complies Exception: Requirement [FI11]2 systems have automatic or Does Not is not applicable. accessible manual controls. omply Not servable PNot plicable 403.6.1 All mechanical ventilation _ Complies Location on plans/spec: SEE NOTES ON CID-1 OF [FI25]2 system fans not part of tested and listed HVAC equipment Does Not ARCH DRAWINGS meet efficacy and air flow limits omply per Table R403.6.1. (� Not servable Not pplicable ,403.2 Hot water boilers supplying heat Q Complies Location on plans/spec: SEE NOTES ON CP-1 OF [FI26]2 through one- or, two -pipe heating systems have outdoor Does Not omply ARCH DRAWINGS i setback control to lower bailer water temperature based on Not I outdoor temperature. servable ` Not pplicable 403.5.1.1 Heated water circulation 0 Complies Location on plans/spec: NOTES ON CP-1 OF [FI28]2 systems have a circulation pump. The system return pipe is [� Does Not SEE ARCH DRAWINGS a dedicated return pipe or a omply cold water supply pipe. Gravity Not and thermos -syphon circulation servable systems are not present. Controls for circulating hot (—j Not water system pumps start the pplicable pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set point temperature and no demand for hot water exists. 403.5.1.2 Electric heat trace systems T Complies Location on plans/spec: SEE NOTES ON CP-1 OF [FI29]2 comply with IEEE 515.1 or UL 515. Controls automatically Does Not ARCH DRAWINGS adjust the energy Input to the omply heat tracing to maintain the (� Not desired water temperature in servable the piping. PpNot pplicable Report Title: ELR Residence Report Date: 10/29/25, 3:03 PM 9 of 12 Section Plans Field # Verified Verified & Req.ID Final Inspection Provisions Value Value Complies? Comments/Assumptions 403.5.2 Demand recirculation water ❑ Complies Location on plans/spec: [F13011 systems have controls that Does Not SEE NOTES ON CP-1 OF ARCH DRAWINGS manage operation of the pump and limit the temperature of the amply water entering the cold water Not [�F. piping to <= 104° servable I Not pplicable I 403.5.4 Drain water heat recovery units 0 Complies Location on plans/spec: [FI31]2 tested in accordance with CSA B55.1. Potable water -side Does Not SEE NOTES ON CP-1 OF ARCH DRAWINGS pressure loss of drain water omply heat recovery units < 3 psi for o Not individual units connected to Observable one or two showers. Potable Not water -side pressure loss of drain water heat recovery units < 2 pplicable psi for individual units connected to three or more showers. 404.1 90% or more of permanent Complies Location on plans/spec: [F16]1 fixtures have high efficacy lamps. Does Not SEE NOTES ON CP-1 OF ARCH DRAWINGS omply Not servable ❑ Not Applicable 404.1.1 Fuel gas lightingsystems have O Complies Location on plans/spec: [FI23]3 no continuous pilot light. SEE NOTES ON CP-1 OF Does Not ARCH DRAWINGS Comply � I Not servable PpNot plicable 401.3 Compliance certificate posted. Complies [FI7]2 Does Not Pomply Not servable y 0 Not Applicable 303.3 a Manufacturer manuals for 0 Complies [FI18]3 mechanical and water heating P Does Not systems have been provided. Comply N Wot servable Not pplicable 402.2.3 Vented attics with air permeable Complies [FI22]2 insulation include baffle 4' Does Not adjacent to soffit and eave vents that extends over ?, omply insulation. ❑ Not F Observable Not Applicable 402.2.4 Attic access hatch and door Rf R i� l= Complies [FI3]1 insulation >_R-value of the Does Not adjacent assembly. omply Not servable Not pplicable 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and ACH 50 = ACH 54 = Q Complies Does Not <=3 ach in Climate Zones 3-8. omply Not servable E) Not Applicable Report Title: ELR Residence Report Date: 10/29/25, 3:03 PM 10 of 12 Section Plans Field # Verified Verified & Req.ID Final Inspection Provisions Value Value Complies? Comments/Assumptions 403.3.3 Ducts are pressure tested to Q Complies Exception: All ducts and handlers located [FI27]1 determine air leakage with either: Rough -in test: Total cfm/100 ft z cfm/100 ft z Does Not air are within conditioned space. P leakage measured with a � amply Location on plans/spec: SEE NOTES ON CP-1 OF pressure differential of 0.1 inch Q Not w.g. across the system including Observable ARCH DRAWINGS the manufacturer's air handler enclosure if installed at time of Not test. Postconstruction test: Total Applicable leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer's air handler enclosure. 403.3.4 Duct tightness test result of Complies Exception: All ducts and I air handlers are located [FI4]1 < = 4 cfm7100 ft2 across the system or E=3 cfm/100 ft2 z y, cfm/100 ft cfm/100 ft 2 Does Not i within conditioned space. P without air handler @ 25 Pa. For amply Location on plans/spec: rough -In tests, verification may o Not SEE NOTES ON CP-1 OF need to occur during Framing Observable ARCH DRAWINGS Inspection. PA Not pplicable � 403.3.2.1 Air handler leakage designated I Complies Location on plans/spec: [FI24]1 I by manufacturer at <=2 /o of design airflow. Does Not omply SEE NOTES ON CP-1 OF ARCH DRAWINGS Not servable ❑Not applicable 403.1.1 Programmable thermostats Complies Location on plans/spec: SEE NOTES ON CP-1 OF [FI9]2 installed for control of primary heating and cooling systems Does Not ARCH DRAWINGS j and initially Set by manufacturer amply to code specifications. (� Not servable [� Not pplicable Additional Comments/Assumptions: 1 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3) 771 Report Title: ELR Residence Report Date: 10/29/25, 3:03 PM 11 of 12 2018 IECC Energy Lr I Efficiency Certificate Above -Grade Wall 21.00 Below -Grade Wall 34.00 Floor 10.00 Ceiling / Roof 49.00 Ductwork (unconditioned spaces): Window 0.30 Door 0.30 Skylight 00 Cooling Heating System: Cooling System: Water Heater: Signature Name: Date: Comments: Report Title: ELR Residence Report Date: 10/29/25, 3:03 PM 12 of 12