Compliance certificate
Project RifleSperry
Energy Code:
2018 IECC
Location:
Rifle, Colorado
Construction Type:
Single-family
Project Type:
New Construction
Project SubType:
None
Conditioned Floor Area
3,328 ft2
Glazing Area
25%
Climate Zone:
5 (6881 MD)
Permit Date:
Permit Number:
All Electric
true
Is Renewable
true
Has Charger
true
Has Battery:
true
Has Heat Pump:
true
Construction Site:
Owner/Agent: Designer/Contractor:
Sperry
New Construction Architectural Plans
Rifle, CO
Compliance: 0.7% Better Than Code Maximum UA: 292 Your UA: 290
The % Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum -code home.
Slab -on -grade tradeoffs are no longer considered in the UA or performance compliance path in REScheck. Each slab -on -grade
assembly in the specified climate zone must meet the minimum energy code insulation R-value and depth requirements.
Envelope Assem lied
Ceiling area of home forming top of insulation
1,368 49.0
0.0 0.026
0.026
36
36
envelope: Flat Ceiling or Scissor Truss
Wall area of home forming sides of insulation
1,377 0.0
0.0 0.087
0.082
90
85
envelope: Log
Energy efficient door unit: Glass Door (over 50%
42
0.300
0.300
13
13
glazing)
Energy efficient door unit: Glass Door (over 50%
42
0.300
0.300
13
13
glazing)
Energy efficient door unit: Glass Door (over 50%
21
0.300
0.300
6
6
glazing)
Energy efficient door unit: Glass Door (over 50%
21
0.300
0.300
6
6
glazing)
Window area of home using energy efficient units:
220
0.260
0.300
57
66
Vinyl Frame
Project Title: RifleSperry Report date: 06/04/25
Data filename: Page 1 of10
Basement wall area of home forming bottom of
insulation envelope: Solid Concrete or Masonry
Wall height: 9.0' 1,334 0.0 10.0 0.052 0.050 69 67
Depth below grade: 9.0'
Insulation depth: 9.0'
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2018 IECC requirements in
REScheck Version : REScheck-Web and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Jobe Leonard 6/4/25
Name - Title Signature Date
Project Title: RifleSperry Report date: 06/04/25
Data filename: Page 2 of10
REScheck Software Version : REScheck-Web
qr(] Inspection checklist
9Y
Ener Code: 20181ECC
Requirements: 0.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Pre-Inspection/Plan Review
Plans Verified Field Verified
Complies?
& Req.ID
I
Value Value
103.1,
Construction drawings and
❑Complies
103.2
documentation demonstrate
❑Does Not
[PR1]1
energy code compliance for the
❑Not Observable
building envelope. Thermal
❑Not Applicable
envelope represented on
construction documents.
103.1,
Construction drawings and
❑Complies
103.2,
documentation demonstrate
❑Does Not
403.7
energy code compliance for
I❑Not Observable
[PR3]1
lighting and mechanical systems.
❑Not Applicable
`L
Systems serving multiple
dwelling units must demonstrate
compliance with the IECC
Commercial Provisions.
302.1,
Heating and cooling equipment is
Heating: Heating:
LICompiies
403.7
sized per ACCA Manual S based
Btu/hr Btu/hr
❑Does Not
[PR2]2
on loads calculated per ACCA
Cooling: Cooling:
❑Not Observable
Manual J or other methods
Btu/hr Btu/hr
El Not Applicable
approved by the code official.
Additional Comments/Assumptions:
Comments/Assumptions
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3)
Project Title: RifleSperry Report date: 06/04/25
Data filename: Page 3 of10
Section Plans Verified Field Verified
# Foundation Inspection Value Value
& Fie .1 D
402.1.1
:Conditioned basement wall R-
[F04]1
insulation R-value. Where interior R-
insulation is used, verification
-
may need to occur during
Insulation Inspection. Not
required In warm -humid locations
in Climate Zone 3.
303.2
Conditioned basement wall
[FO5]1
insulation installed per
manufacturer's instructions.
402.2.9
:Conditioned basement wall ft
[FO6]1
insulation depth of burial or
distance from top of wall.
J
303.2.1
A protective covering is installed
[FO11]2
to protect exposed exterior
J
insulation and extends a
minimum of 6 in. below grade.
403.9
Snow- and ice -melting system
[FO12]2
controls installed.
Additional Comments/Assumptions:
R-
R-
Complies? Comments/Assumptions
❑Complies See the Envelope Assemblies
❑Does Not table for values.
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
I❑Not Observable
❑Not Applicable
ft ❑Complies See the Envelope Assemblies
❑Does Not table for values.
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
[❑Complies
❑Does Not
I❑Not Observable
;❑Not Applicable
1 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: RifleSperry Report date: 06/04/25
Data filename: Page 4 of10
:tion I Plans Verified
# Framing / Rough -In Inspection Value
& Be .I D ` 1
402.1.1,
Glazing U-factor (area -weighted U-
402.3.1,
average).
402.3.3,
402.5
[FR2]1
303.1.3
U-factors of fenestration products
[FR4]1
are determined in accordance
with the NFRC test procedure or
taken from the default table.
402.4.1.1
Air barrier and thermal barrier
[FR23]1
installed per manufacturer's
instructions.
402.4.3
Fenestration that is not site built
[FR20]1
is listed and labeled as meeting
AAMA /WDMA/CSA 101/I.S.2/A440
or has infiltration rates per NFRC
400 that do not exceed code
limits.
402.4.5
IC -rated recessed lighting fixtures
[FR16]2
sealed at housing/interior finish
and labeled to indicate 152.0 cfm
leakage at 75 Pa.
403.3.1
Supply and return ducts in attics
[FR12]1
insulated >= R-8 where duct is
>= 3 inches in diameter and >_
R-6 where < 3 inches. Supply and
return ducts in other portions of
the building insulated >= R-6 for
diameter >= 3 inches and R-4.2
for < 3 inches in diameter.
403.3.2
Ducts, air handlers and filter
[FR13]1
boxes are sealed with
joints/seams compliant with
International Mechanical Code or
International Residential Code, as
applicable.
403.3.5
Building cavities are not used as
[FR15]3
ducts or plenums.
403.4 HVAC piping conveying fluids R-_
[FR17]2 above 105 °F or chilled fluids
below 55 °F are insulated to >_R-
- . 3.
403.4.1 Protection of insulation on HVAC
[FR24]1 piping.
Field Verified Complies? Comments/Assumptions
Value
U- ❑Compiles See the Envelope Assemblies
❑Does Not table for values.
❑Not Observable
❑Not Applicable
M
403.5.3 Hot water pipes are insulated to R- R-,
[FR18]2 >_R-3.
403.6 'Automatic or gravity dampers are
[FR19]z installed on all outdoor air
intakes and exhausts.
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable _
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
(❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
LJComplies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
El Not Applicable
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: RifleSperry Report date: 06/04/25
Data filename: Page 5 of10
Additional Comments/Assumptions:
111 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: RifleSperry
Data filename:
Report date: 06/04/25
Page 6 of10
Insulation Inspection I
Plans Verified Field Verified
Value Value
303.1
All installed insulation is labeled
[IN13]2
or the installed R-values
provided.
402.1.1,
Wall insulation R-value. If this is a R-
R-
402.2.5,
mass wall with at least 1/2 of the
❑ Wood
❑ Wood
402.2.6
wall insulation on the wall
❑ Mass
❑ Mass
[IN3]1
exterior, the exterior insulation
❑Steel
❑Steel
requirement applies (FR10).
303.2 Wall insulation is installed per
[IN4]1 manufacturer's instructions.
Additional Comments/Assumptions:
Complies? Comments/Assumptions
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies See the Envelope Assemblies
❑Does Not table for values.
❑Not Observable
❑Not Applicable
ucompues
❑Does Not
;❑Not Observable
❑Not Applicable
L.ILHigh Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: RifleSperry Report date: 06/04/25
Data filename: Page 7 of10
sections
#
Final Inspection Provisions
Plans Verified
Value
Field Verified
Value Complies?
& Re .10
402.1.1,
Ceiling insulation R-value.
R-
R- ❑Complies
402.2.1,
❑ Wood
❑ Wood ❑Does Not
402.2.2,
❑ Steel
❑ Steel ❑Not Observable
402.2.E
❑ Not Applicable
[FI1]1
303.1.1.1,
Ceiling insulation installed per
❑Complies
303.2
manufacturer's instructions.
❑Does Not
[FI2]1
Blown insulation marked every
❑Not Observable
300 ft2.
❑Not Applicable
Vented attics with air permeable
❑Complies
�402.2.3
[FI22]2
insulation include baffle adjacent
❑Does Not
to soffit and eave vents that
❑Not Observable
extends over insulation.
❑Not Applicable
402.2.4
Attic access hatch and door
R-
R- v❑Complies
[FI3]1
insulation >_R-value of the
❑Does Not
adjacent assembly.
❑Not Observable
❑Not Applicable
402.4.1.2 Blower door test @ 50 Pa. <=5 ACH 50 =
[FI17]1 ach in Climate Zones 1-2, and
<=3 ach in Climate Zones 3-8.
403.3.3
[FI27]1
403.3.4
[FI4]1
403.3.2.1
[FI24]1
Ducts are pressure tested to cfm/100
determine air leakage with ft2
either: Rough -in test: Total
leakage measured with a
pressure differential of 0.1 inch
w.g. across the system including
the manufacturer's air handler
enclosure if installed at time of
test. Postconstruction test: Total
leakage measured with a
pressure differential of 0.1 inch
w.g. across the entire system
including the manufacturer's air
handler enclosure.
Duct tightness test result of <=4 cfm/100
cfm/100 ft2 across the system or ftz
<=3 cfm/100 ft2 without air
handler @ 25 Pa. For rough -in
tests, verification may need to
occur during Framing Inspection.
Air handler leakage designated
by manufacturer at <=2% of
design air flow.
ACH 50 =
❑Does Not
❑Not Observable
❑Not Applicable
cfm/100 ❑Complies
ft2 ❑Does Not
❑Not Observable
❑Not Applicable
cfm/100
ft2
403.1.1
Programmable thermostats
[FI9]2
installed for control of primary
heating and cooling systems and
initially set by manufacturer to
code specifications.
403.1.2
Heat pump thermostat installed
[FI10]2
on heat pumps.
403.5.1
Circulating service hot water
[F[11]2
systems have automatic or
accessible manual controls.
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
DCornplies
❑Does Not
❑Not Observable
❑Not Applicable
Comments/Assumptions
See the Envelope Assemblies
table for values.
1 I High Impact (Tier 1) 2 Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3)
Project Title: RifleSperry Report date: 06/04/25
Data filename: Page 8 of10
Sectlon 1 Plans Verified
Field Verified
Complies?
# Final Inspection Provisions Value
& Rey.ID
Value
403.6.1 All mechanical ventilation system
❑Complies
[FI25]2 fans not part of tested and listed
[]Does Not
HVAC equipment meet efficacy
[]Not Observable
and air flow limits per Table
❑Not Applicable
R403.6.1.
403.2
Hot water boilers supplying heat
❑Complies
[FI26]2
through one- or two -pipe heating
❑Does Not
systems have outdoor setback
❑Not Observable
control to lower boiler water
❑Not Applicable
temperature based on outdoor
temperature.
403.5.1.1
Heated water circulation systems
❑Complies
❑Does
[FI28]2
have a circulation pump. The
Not
system return pipe is a dedicated
❑Not Observable
return pipe or a cold water supply
❑Not Applicable
pipe. Gravity and thermos-
syphon circulation systems are
not present. Controls for
circulating hot water system
pumps start the pump with signal
for hot water demand within the
occupancy. Controls
automatically turn off the pump
when water is in circulation loop
is at set -point temperature and
no demand for hot water exists.
403.5.1.2
Electric heat trace systems
_
❑Complies
[FI29]2
'comply with IEEE 515.1 or UL
❑Does Not
515. Controls automatically
❑Not Observable
adjust the energy input to the
❑Not Applicable
heat tracing to maintain the
desired water temperature in the
piping.
403.5.2
Demand recirculation water
❑Complies
[F130]2
systems have controls that
❑Does Not
manage operation of the pump
❑Not Observable
and limit the temperature of the
❑Not Applicable
water entering the cold water
piping to <= 104°F.
403.5.4
Drain water heat recovery units
❑Complies
[FI31]2
tested in accordance with CSA
❑Does Not
B55.1. Potable water -side
❑Not Observable
pressure loss of drain water heat
❑Not Applicable
recovery units < 3 psi for
individual units connected to one
or two showers. Potable water-
side pressure loss of drain water
heat recovery units < 2 psi for
individual units connected to
three or more showers.
404.1
90% or more of permanent
❑Complies
[F16]1
fixtures have high efficacy lamps.
❑Does Not
❑Not Observable
❑Not Applicable
404.1.1 Fuel gas lighting systems have
[FI23]3 no continuous pilot light.
401.3 Compliance certificate posted.
[FI7]2
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
UComplies
❑Does Not
❑Not Observable
❑Not Applicable
Comments/Assumptions
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: RifleSperry Report date: 06/04/25
Data filename: Page 9 of10
Final Inspection Provisions Plans Verified
Value
303.3 Manufacturer manuals for
IFI1813 mechanical and vaster heating
systems have been provided.
Additional Comments/Assumptions:
Field Verified Compiles?
Value
❑Complies
Does Not
❑Not observable
❑Not Applicable
Comments/Assumptlons
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3)
Project Title: RifleSperry Report date: 06/04/25
Data filename: Page 10 of10
l�(018 iECC Energy
, Efficiency Certificate
Insulation Rating
R-Value
Above -Grade Wall
0.00
Below -Grade Wall
10.00
Floor
0.00
Ceiling / Roof
49.00
Ductwork (unconditioned spaces):
Glass & Door Rating •
Window 0.26 0.25
Door 0.30
CoolingHeating &
Heating System:
Cooling System:
Water Heater;
Name: _ Date:
Comments