HomeMy WebLinkAboutEnginer's Letter 11.13.25November 13, 2025
tderson
tructural
Engineering
RECEIVED
Ms. Colleen Wurth DEC 0 9 2025
Building Plans Examiner GARFIELD COUNTY
Garfield County Community Development COMMUNITYIJEvELOPMENT
108 81h Street, Suite 401
Glenwood Springs, CO 81601
RE: BLRE-09-25-9509 Wells ADU 540 Panoramic Dr, Lot 10 outside Silt
Dear Ms. Wurth:
Regarding the subject project, please note the following;
1. A structural floor and crawl space was selected by the owner and is applicable for this
project.
2. See "Revised Permit" drawings for crawl space access framing.
3. Foundation type has been determined by engineering judgement to be acceptable for this
site. Non structural slabs and spread footing foundations are both referenced in the
geotechnical report. Frost depth as noted on the structural drawings shall be maintained.
4. See "Revised Permit" drawings for egress door header location.
Please do not hesitate to call our office for any additional questions.
Sinc rely,
andon Ander n
Anderson Structural Engineering, Inc.
�00 HEM
r
35435
&J3' ,-
448 Elk Run Road ■ New Castle, CO 81647
(970) 984-0320 a email: landon anderson-structural,com
5. What is your chosen ENERGY COMPLIANCE PATH for the ADU?
5.a. Are you building in accordance with the PRESCRIPTIVE PATH and the 2018 IECC Table
R402.1.2? If so, provide a statement in writing. The proposed heating system for the
subject structure consists of a 2-18,000 BTU, 208/230-volt mini -split condenser, which
provides adequate capacity to serve the combined conditioned floor area up to 2,000
square feet. The design and associated equipment selection are in compliance with the
2018 International Energy Conservation Code (IECC).
5.b. Are you building in accordance with the PRESCRIPTIVE PATH using a RESCHECK
REPORT? If so, provide a statement in writing along with your RESCHECK REPORT.
5.c. Are you building in accordance with the PERFORMANCE PATH using a HERS RATER
AND HERS RATER REPORT(S)? If so, provide a statement in writing, your HERS Rater
contact information and report.
5.d. What proposed window / door fenestration U-factors are you proposing to install? No
U-factor readily found on DS sheet window / door schedule, thank you.
5.e. Do you have any air -sealing details to include in the FIELD COPY for sealing openings
along the thermal envelope, as found at framing joints, windows / doors / electrical /
mechanical penetrations?
(The handwritten R-value floor wall ceiling sections are helpful and appreciated, but more `
Limited in air -sealing details. Garfield County Climate Zone 513 now requires new build
homes to have a `blower door'test performed during construction. We are striving to aid in
alleviatingtoo much leakage. Where further information available, please include in your
response or resubmission plan materials, thank you!)
Pursuant to Garfield County requirements, the project is evaluated under Climate Zone 5.
The buildingthermal envelope meets or exceeds the prescriptive insulation requirements
of the 2018 IECC, as outlined below:
Ceilings: R-49
Above -Grade Exterior Walls: R-20
Floors: R-30
Crawlspace: R-19