Loading...
HomeMy WebLinkAboutHeat CalcsHVAC Load Calculations for Dockers Construction Lot H-34 200 Saddleback Rd Aspen Glen —Garfield County,Co RHVACHVACRESIIDICNwMAL LOADS Prepared By: M. Dunne MDA Design Consulting, LLC 5001 N Blazingstar Trail Castle Rock, Co. 80109 888-903-6255 Tuesday, October 7, 2025 Rhvac is an ACCA approved Manual J, D and S computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2.50, and ACCA Manual D. Rhvac - Residential & Light Commercial HVAC Loads MDA Design Consultinq, LLC - — �ProJect Report - - LGeneral Pr 'ect Inf ffn 'on Designed By: MDA Project Date: 10-8-2025 Client Name: Dockers Construction Client Address: Lot H-34 200 Saddleback Rd Client City: Aspen Glen —Garfield County,Co Company Name: MDA Design Consulting, LLC Company Representative: M. Dunne Company Address: 5001 N Blazingstar Trail Company City: Castle Rock, Co. 80109 Company Phone: 888-903-6255 Company E-Mail Address: mdunne@mdadesignconsulting.com Company Website: MDA Design Consulting.com Desiqn Data — Reference City: Building Orientation: Daily Temperature Range: Latitude: Elevation: Altitude Factor: Outdoor Dry Bulb Writer: -5 Summer: 88 Check Figures Total Building Supply CFM: Square ft. of Room Area: Volume (ft'): Elite Software Development, inc. Aspen Glen, Co Front door faces East High (40 rees �O 8600 ft. 0.726 Outdoor Outdoor Indoor Indoor Grains Wet Bulb Rel.Hum Rel.Hum D[y Bulb Difference -4 n/a n/a 70 n/a 62 27% 50% 70 -2 3,280 — 4,615 0 Building Loads - Total Heating Required Including Ventilation Air: Total Sensible Gain: Total Latent Gain: Total Cooling Required Including Ventilation Air: CFM Per Square ft.: 0.711 Square ft. Per Ton: 618 67,049 Btuh 67.049 MBH 68,158 Btuh 76 % 21,386 Btuh 24 % 89,544 Btuh 7.46 Tons (Based On Sensible + Latent) Notes-- ^Rhvac is an ACCA approved Manual J, D and S computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2.50, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\ ...\Aspen Glen _ .. _10-8 25.r10 Tuesday, October 7, 2025, 2:20 PM Rhvac - Residential & Light Commercial HVAC Loads MDA Design Consulting, LLC Castle Rock, GO 801+09 Load Preview Report Scope Buildinq System 1 Misc. Return Zone 1 1-Main Level foyer 1st FI Level 2-Laundry Rm 3-Master Bath 4-Master Bdrm 5-Great Room 6-Dininq Rm 7-Kitchen 8-Pantry 9-Office-Bdrm #1 10-Mud Room 11-Closet System 2 Misc. Return Zone 2 12-Upper Level -Loft 13-Upper Level-Bdrm #3 14-1-lpper Level -Bath #3 & Closet 15-Upper Level- Bdrm #2 16-Upper Level- Bath #2 & Closet 17-Foyer 2nd FlLevel System 3 Misc. Return Zone 3 18-Lower Level Bath #4 19-Lower Level Bdrm #4 20-Lower Level Entertainmenr Room 21-Lower Level Bath #4 22-Lower Level Bdrm #4 Net Ton 7.46 3.94 1.67 1.85 Elite Software Development, Inc. Penn 4 Sys Sys Sys ft' ]Ton Area Sen Gain Lat Gain Netl Gain Sen Loss IF CIF Clg CFM Act CFM 618 4,615 68,158 21,386 89,544 67,049 2,221 3,280 3,281 475 1,872 36,189 11,087 47,276 41,539 1,156 1,679 1,679 0 8,000 8,000 1,872 36,189 3,087 39,276 41,539 1,156 1,679 1,679 372 3,962 185 4,147 4,443 124 184 184 85 1,210 198 1,408 578 16 56 56 121 1,364 -3 1,364 3,912 109 63 63 272 5,931 384 6,315 13,177 367 275 275 361 12,060 787 12,847 8,255 230 559 559 195 4,348 793 5,141 3,187 89 202 202 180 2,416 357 2,773 1,448 40 112 112 25 387 -1 387 314 9 18 18 156 3,683 391 4,074 3,309 92 171 171 70 414 -2 414 1,868 52 19 19 35 414 -2 414 1,048 29 19 19 775 1,298 14,940 0 1,298 14,940 275 2,477 176 2,462 140 1,267 231 3,763 104 1,748 372 3,223 782 1,446 17,029 0 1,446 17,029 47 4,391 216 1,774 920 4,699 47 4,391 216 1,774 5,152 20,092 12,706 4,000 4,000 1,152 16,092 12.706 195 2,672 1,777 395 2,857 1,219 -9 1,267 1,993 385 4,148 3.852 -3 1,748 809 189 3,412 3,056 5,147 22,176 12,804 2,000 2,000 3,147 20,176 12,804 796 5,187 790 391 2,165 2,121 773 5,472 6,982 796 5,187 790 391 2,165 2,121 530 748 748 530 748 748 74 124 124 51 123 123 83 63 63 161 188 188 34 88 88 128 161 161 534 853 853 534 853 853 33 220 220 89 89 89 291 235 235 33 220 220 89 89 89 C:\ ...\Aspen Glen _ .. _10-8-25.r10 Tuesday, October 7, 2025, 2:20 PM 1r Rhvac - Residential & Light Commercial HVAC Loads MDA Design Consu@inq, LLC LQpA Rods. Gn N109 _ Total Building Summary Loads Component - Description _ 3A-f-d-. Glazing -Double pane low-e (e = 0.40), sliding glass door, insulated fiberglass frame, outdoor insect screen with 50% coverage, U-value 0.3, SHGC 0.56 3A-f-d: Glazing -Double pane low-e (e = 0.40), sliding glass door, insulated fiberglass frame, outdoor insect screen with 50% coverage, in partition wall, U-value 0.3, SHGC 0.56 11 F: Door -Wood - Solid Core With Metal Storm, U-value 0.28 12F-6sw: Wali-Frame, R-21 insulation in 2 x 6 stud cavity, R-6 board insulation, siding finish, wood studs, U-value 0.04 12F-6sw: Wall -Frame, R-21 insulation in 2 x 6 stud cavity, R-6 board insulation, siding finish, wood studs, U-value 0.048 12F-6sw: Part -Frame, R-21 insulation in 2 x 6 stud cavity, R-6 board insulation, siding finish, wood studs, U- value 0.048 vaulted ceiling: Partition Roof/Ceiling (STD=15, WTD=15)-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, typ wood roof assembnly with R-49 Sprayed open cell insulation, U-value 0.02 typical roof assembl: Partition Roof/Ceiling (STD=15, WTD=15)-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, typical roof assembly wit R-49 spray open cell insulation, U-value 0.02 vaulted ceiling: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, typ wood roof assembnly with R-49 Sprayed open cell insulation, U-value 0.02 ceiling -attic above: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, typ wood roof assembnly with R-49 Sprayed open cell insulation, U-value 0.02 22C-10pl-over crawl-v: Partition Floor (STD=O, WTD=25)- Slab on grade, Horizontal board insulation extends 4' under slab, vinyl covering, R-10 insulation, passive, light dry soil, U-value 0.937 19B-5sp-slab: Partition Floor (STD=O, WTD=25)-Over enclosed crawl space, R-4 insulation on exposed walls, sealed crawl space, passive, R-5 or R-6 board, U-value 0.125 Subtotals for structure: People. - Equipment: Lighting: Ductwork: Infiltration: Winter CFM: 0, Summer CFM: 0 Ventilation: Winter CFM: 0, Summer CFM: 0 Return Misc. Gain: Total Building Load Totals: Check Figures Total Building Supply CFM: 3,280 Elite Software Development, Inc — _Pane 4 ,I Area Sen Lat Sen Total Quan Loss _ Gain _ Gain Gain 705 15,867 0 22,578 22,578 75 564 0 0 0 18 378 0 121 121 1836.5 5,510 0 690 690 1698 6,113 0 765 765 1885 2,194 0 100 100 1789.1 536 0 536 536 623 186 0 186 186 301.6 452 0 259 259 372 558 0 320 320 499.2 11,694 0 0 0 1445.5 4,517 0 0 0 48,569 0 25,555 i 25,555 1 37 7,400 8,510 15,910 161 3,758 3,919 8200 27,962 27,962 0 0 0 0 18,480 -175 2,373 2,198 0 0 0 0 0 14,000 0 14,000 . 67,049 21,386 68,158 89,544 CFM Per Square ft.: 0.711 C:\ ...\Aspen Glen _ .. _10-8-25.r10 Tuesday, October 7, 2025, 2:20 PM Rh►►ac _ Residential & Light Commercial HVAG Loads Elite Software Development, Inc. MDA Desinn Consultinq, LLC Castle Rom, CQ 80109- Total Building Summary Loads_(con#d) Check Figures- _- - — — - — _- - Square ft. of Room Area: 4,615 Square ft. Per Ton: 618 Volume (ft3): 0 -Building. Loads Total Heating Required Including Ventilation Air: 67,049 Btuh 67.049 MBH Total Sensible Gain: 68,158 Btuh 76 % Total Latent Gain: 21,386 Btuh 24 % Total Cooling Required Including Ventilation Air: 89,544 Btuh 7.46 Tons (Based On Sensible + Latent) Notes Rhvac is an ACCA approved Manual J, D and S computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2.50, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\ ...\Aspen Glen _ ... _10-8-25.0 0 Tuesday, October 7, 2025, 2:20 PM iitnrac - Residential &Light Commercial HVAC Loads M3A Desiqn Consulting, LLC G�� RQck,00A010.9 System 1 9st Floor Sytem Summary_ Loads Component— Descrip tion 3A-f-d: Glazing -Double pane low-e (e = 0.40), sliding glass door, insulated fiberglass frame, outdoor insect screen with 50% coverage, U-value 0.3, SHGC 0.56 11 F: Door -Wood - Solid Core With Metal Storm, U-value 0.28 12F-6sw: Wall -Frame, R-21 insulation in 2 x 6 stud cavity, R-6 board insulation, siding finish, wood studs, U-value 0.04 12F-6sw: Wall -Frame, R-21 insulation in 2 x 6 stud cavity, R-6 board insulation, siding finish, wood studs, U-value 0.048 12F-6sw: Part -Frame, R-21 insulation in 2 x 6 stud cavity, R-6 board insulation, siding finish, wood studs, U- value 0.048 Area Quan 590 18 906 1414 140 vaulted ceiling: Partition Roof/Ceiling (STD=15, 1201.4 WTD=15)-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, typ wood roof assembnly with R-49 Sprayed open cell insulation, U-value 0.02 typical roof assembl: Partition Roof/Ceiling (STD=15, WTD=15)-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, typical roof assembly wit R-49 spray open cell insulation, U-value 0.02 22C-10pl-over crawl-v: Partition FIoor (STD=O, WTD=25)- Slab on grade, Horizontal board insulation extends 4' under slab, vinyl covering, R-10 insulation, passive, light dry soil, U-value 0.937 Subtotals for structure: People: Equipment: Lighting: Ductwork: Infiltration: Winter CFM: 130, Summer CFM: 69 Ventilation: Winter CFM: 0, Summer CFM: 0 Return Misc. Gain: System 1 1 st Floor Sytem Load Totals: Check (Figures 400 499.2 15 3200 Elite Software Development, Inc.] Page 6 Sen Lat Sen Total Loss- , .. Gain Gain __Gain 13,279 0 18,133 18,133 378 0 121 121 2,718 0 340 340 5,091 0 637 637 100 0 100 100 360 0 360 360 119 0 119 119 11,694 0 0 0 33,739 0 19,810 19,810 3,000 3,450 6,450 161 1,025 1,186 10,912 10,912 0 0 0 0 7,800 -74 992 918 0 0 0 0 0 8,000 0 8,000 41,539 11,087 36,189 47,276 Supply CFM: 1,679 CFM Per Square ft.: 0.897 Square ft. of Room Area: 1,872 Square ft. Per Ton-.475 Volume (W): 22,982 L System loads Total Heating Required Including Ventilation Air: 41,539 Btuh 41.539 MBH Total Sensible Gain: 36,189 Btuh 77 % Total Latent Gain: 11,087 Btuh 23 % Total Cooling Required Including Ventilation Air: 47,276 Btuh 3.94 Tons (Based On Sensible + Latent) Notes Rhvac is an ACCA approved Manual J, D and S computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2.50, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:1 ...Aspen Glen _ ... _10-8-25.r10 Tuesday, October 7, 2025, 2:20 PM ti Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc. MDA Design Consulting, LLC Page 7 Castle Rock..C.0 80103 _ System _2 Upper Level Syfem Summary Loads Component Area Sen Lat Sen Total Description Quan _ Loss Gain Gain Gain 3A-f-d: Glazing -Double pane low-e (e = 0.40), sliding 115 2,588 0 4,445 4,445 glass door, insulated fiberglass frame, outdoor insect screen with 50% coverage, U-value 0.3, SHGC 0.56 12F-6sw: Wall -Frame, R-21 insulation in 2 x 6 stud 930.5 2,792 0 350 350 cavity, R-6 board insulation, siding finish, wood studs, U-value 0.04 12F-6sw: Wall -Frame, R-21 insulation in 2 x 6 stud 284 1,022 0 128 128 cavity, R-6 board insulation, siding finish, wood studs, U-value 0.048 vaulted ceiling: Roof/Ceiling-Roof Joists Between Roof 301.6 452 0 259 259 Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, typ wood roof assembnly with R-49 Sprayed open cell insulation, U-value 0.02 vaulted ceiling: Partition Roof/Ceiling (STD=15, 587.7 176 0 176 176 WTD=15)-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, typ wood roof assembnly with R-49 Sprayed open cell insulation, U-value 0.02 typical roof assembl: Partition Roof/Ceiling (STD=15, 223 67 0 67 67 WTD=15)-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, typical roof assembly wit R-49 spray open cell insulation, U-value 0.02 ceiling -attic above: Roof/Ceiling-Roof Joists Between 372 558 0 320 320 Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, typ wood roof assembnly with R-49 Sprayed open cell insulation, U-value 0.02 Subtotals for structure: 7,655 0 5,745 5,745 People: 6 1,200 1,380 2,580 Equipment: 0 342 342 Lighting: 2000 6,820 6,820 Ductwork: 0 0 0 0 Infiltration: Winter CFM: 84, Summer CFM: 45 5,051 -48 653 605 Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0 Return Misc. Gain: 0 4,000 0 4,000 System 2 Upper Level Sytem Load Totals: 12,706 5,152 14,940 20,092 Check Figures Supply CFM: 748 CFM Per Square ft.: 0.577 Square ft. of Room Area: 1,298 Square ft. Per Ton: 775 Volume (fP): 12,975 System Loads Total Heating Required Including Ventilation Air: 12,706 Btuh 12.706 MBH Total Sensible Gain: 14,940 Btuh 74 % Total Latent Gain: 5,152 Btuh 26 % i Total Cooling Required Including Ventilation Air: 20,092 Btuh 1.67 Tons (Based On Sensible + Latent) Notes Rhvac is an ACCA approved Manual J, D and S computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2.50, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at i your design conditions. C:\ ...\Aspen Glen_. ... _10-8-25.r10 Tuesday, October 7, 2025, 2:20 PM Rhvac -Residential & Light Commercial WAC Loads li P6 Deslan Consulting, LLC * C .Q1i79 _ -__ __ 5 stem 3 Lower_ Level System_ Summa Loads r Component _ Area Quan 3A-f-d: Glazing -Double pane low-e (e = 0.40), sliding 75 glass door, insulated fiberglass frame, outdoor insect screen with 50% coverage, in partition wall, U-value 0.3, SHGC 0.56 12F-6sw: Part -Frame, R-21 insulation in 2 x 6 stud cavity, 1745 R-6 board insulation, siding finish, wood studs, U- value 0.048 19B-5sp-slab: Partition Floor (STD=O, WTD=25)-Over 1445.5 enclosed crawl space, R-4 insulation on exposed walls, sealed crawl space, passive, R-5 or R-6 board, U-value 0.125 Subtotals for structure: People: 16 Equipment: Lighting: 3000 Ductwork: Infiltration: Winter CFM: 94, Summer CFM: 51 Ventilation: Winter CFM: 0, Summer CFM: 0 Return Misc. Gain: System 3 Lower Level System Load Totals: Check Figures Supply CFM: 853 Square ft. of Room Area: 1,446 Volume (ft'): 14,456 S rystem Loads Total Heating Required Including Ventilation Air: Total Sensible Gain. - Total Latent Gain: Total Cooling Required Including Ventilation Air: Elite Software Development, Inc. Sen Lat _ Loss Gain _ 564 0 2,094 0 4,517 0 Page a Sen Total Gain Gain, 0 0 0 0 0 0 7,175 0 0 0 3,200 3,680 6,880 0 2,391 2,391 10,230 10,230 0 0 0 0 5,629 -53 728 675 0 0 0 0 0 2,000 0 2,000 12,804 5,147 17,029 22,176 CFM Per Square ft.: Square ft. Per Ton: 0.590 782 MBH Tons (Based On Sensible + Latent) Notes Rhvac is an ACCA approved Manual J, D and S computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2.50, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. 12,804 Btuh 12.804 17,029 Btuh 77 5,147 Btuh 23 22,176 Btuh 1.85 C:\ ...\Aspen Glen _ ... _10-8-25.r10 Tuesday, October 7, 2025, 2:20 PM Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc 1I MDA Desiqn Consultinq, LLC I Castle Rock, COW 09 Manual S Performance Data - System�I - 1st Floor Sylem Loads and-D_Qsigg Conditions Cooling: Outdoor Dry Bulb: 88 Sensible Gain: 36.189 Outdoor Wet Bulb: 62 Latent Gain: 11.087 Indoor Dry Bulb: 70 Total Gain: 47.276 Indoor RH: 50 Load SHR: 0.77 Supply Airflow: 1,220 Entering Dry Bulb: 72 Entering Wet Bulb: 60 Heating: Outdoor Dry Bulb: -5 Sensible Loss: 41.539 Indoor Dry Bulb: 70 Entering Dry Bulb: 70.0 Indoor RH.- 30 Supply Airflow: 1,156 Equipment Performance Data at System De ign Conomon, This system's equipment was selected in accordance with ACCA Manual S. Cooling: Model Type: Standard Air Conditioner, Model: RA15AY48 Nominal Capacity: 48.000, Manufacturer: RUUD Interpolation Results: Percent Load of Load Sensible Capacity: 36.000 36.189 99% Latent Capacity: 12.000 11.087 108% Total Capacity: 48.000 47.276 102% Heating: Model Type: Natural Gas Furnace, Model: R951 V0855, Nominal Capacity: 71.000, Manufacturer: RUUD Results: Heating Capacity: Percent Load ofLoad 71.000 41.539 171 % C:\ ...\Aspen Glen—... _10-8-25.r10 Tuesday, October 7, 2025, 2:20 PM Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, inn. j MDA Design Consulting, LLC 4 Xastle *_ Manual S Performance Data - Sysfem 2 - Upper Level S em _ 1 Loads and Design Condmoni Cooling: Outdoor Dry Bulb: 88 Sensible Gain: 14.940 Outdoor Wet Bulb: 62 Latent Gain: 5.152 Indoor Dry Bulb.- 70 Total Gain: 20.092 Indoor RH: 50 Load SHR: 0.74 Supply Airflow: 1,220 Entering Dry Bulb: 72 Entering Wet Bulb: 60 Heating: Outdoor Dry Bulb: -5 Sensible Loss: 12.706 Indoor Dry Bulb: 70 Entering Dry Bulb: 70.0 Indoor RH: 30 Supply Airflow: 530 I Equipment F—erbrrttalltO ta Daat System Design Conditions This system's equipment was selected in accordance with ACCA Manual S. Cooling: Model Type: Standard Air Conditioner, Model: RA15AY24 Nominal Capacity: 24.000, Manufacturer: RUUD Interpolation Results: Percent Load of Load Sensible Capacity: 18.000 14.940 120% Latent Capacity: 6.000 5.152 116% Total Capacity: 24.000 20.092 119% Heating: Model Type: Natural Gas Furnace, Model: R951V0603, Nominal Capacity: 47.000, Manufacturer: RUUD Results: Heating Capacity: Percent LQad of Load 47.000 12.706 370% C:1... Wspen Glen _ ... _10-8-25.r10 Tuesday, October 7, 2025, 2:20 PM Rhvac - Residential & Light Commercial HVAC Loads MOA Design Consulting. r..LC Castle Rock, CO 80109 _ Manual S Performance Data - System 3 - Lower Level System Loads:and Design Conditions Elite Software Development, Inc. Page 11 J Cooling: Outdoor Dry Bulb: 88 Sensible Gain: 17.029 Outdoor Wet Bulb: 62 Latent Gain: 5.147 Indoor Dry Bulb: 70 Total Gain: 22.176 Indoor RH: 50 Load SHR: 0.77 Supply Airflow: 1,220 Entering Dry Bulb: 72 Entering Wet Bulb: 60 Heating: Outdoor Dry Bulb: -5 Sensible Loss: 12.804 Indoor Dry Bulb: 70 Entering Dry Bulb: 70.0 Indoor RH: 30 Supply Airflow: 534 Equipment Performance Data at System Design Conditions This system's equipment was selected in accordance with ACCA Manual S. Cooling: Model Type: Standard Air Conditioner, Model: RA15AY24 Nominal Capacity: 24.000, Manufacturer: RUUD Interpolation Results: Percent Load of Load Sensible Capacity: 18.000 17.029 106% Latent Capacity: 6.000 5.147 117% Total Capacity: 24.000 22.176 108% Heating: Model Type: Natural Gas Furnace, Model: R951V0603, Nominal Capacity: 47.000, Manufacturer: RUUD Results: Heating Capacity: Percent Load of Load 47.000 12.804 367% C:\ ...\Aspen Glen _ ... _10-8-25.r10 Tuesday, October 7, 2025, 2:20 PM -Residential & Light Commercial HVAC Loads Elite Software LNRh'ac DA Design ConsuRing, LLC Development, Inc. astle Rock,. QU0109 _ _ Page 1.2 �qgfem 1-Room Load Summary__ Htg Min Run Run Clg Clg Min Act Room Area Sens Htg Duct Duct Sens Lat Clg Sys L Nc Name SF Btuh CFM Size Vel _ _ Btuh Btuh CFM CFM ---Zone 1--- 1 Main 372 4,443 124 2-0 0 3,962 185 184 184 Level -foyer -1st FI Level 2 Laundry Rm 85 578 16 1-0 0 1,210 198 56 56 3 Master Bath 121 3,912 109 1-0 0 1,364 -3 63 63 4 Master Bdrm 272 13,177 367 3-0 0 5,931 384 275 275 5 Great Room 361 8,255 230 6-0 0 12,060 787 559 559 6 Dining Rm 195 3,187 89 2-0 0 4,348 793 202 202 7 Kitchen 180 1,448 40 2-0 0 2,416 357 112 112 8 Pantry 25 314 9 1-0 0 387 -1 18 18 9 Office-Bdrm #1 156 3,309 92 2-0 0 3,683 391 171 171 10 Mud Room 70 1,868 52 1-0 0 414 -2 19 19 11 Closet 35 1,048 29 1-0 0 414 -2 19 19 Misc Return Gain 0 8,000 System 1 total 1,872 41,539 1,156 36,189 11,087 1,679 1,679 Cooling. System Summary Cooling Sensible/Latent Sensible Latent Total Tons _ _ _ _ Split_ Btuh u Btuh Btuh Net Required: 3.94 77%/23% 36,189 11,087 47,276 Actual: 4.00 75% / 25% 36,000 12,000 48,000 Equipment Data Heating System CoD mg System Type: Natural Gas Furnace Standard Air Conditioner Model: R951 VO855 Indoor Model: Brand: RUUD RUUD Efficiency: 95 AFUE 13.8 SEER2 Sound: 30 30 Capacity: 71,000 Btuh 48,000 Btuh Sensible Capacity: n/a 36,000 Btuh Latent Capacity: n/a 12,000 Btuh This system's equipment was selected in accordance with ACCA Manual S_ Manual S equipment sizing data: SODB: 88F, SOWB: 62F, WODB: -5F, SIDB: 70F, SIRH: 50%n, WIDB: 70F, Sen. gain: 36,189 Btuh, Lat. gain: 11,087 Btuh, Sen. loss: 41,539 Btuh, Entering clg. coil DB: 70F, Entering clg. coil WB: 57F, Entering htg. coil DB: 70F, Clg. coil TD: 27F, Htg. coil TD: 45F, Req. clg. airflow: 1679 CFM, Req. htg. airflow: 1156 CFM C:\ ...\Aspen Glen - ... _10-8-25.0 0 Tuesday, October 7, 2025, 2:20 PM R vac - Residential & Light Commercial HVAC Loads MDA Design Consulting, LLC L Castle ROCK -CO 80109 [ System 2 Room Load Summary ' Ht9 Room Area Sens No Name _ _ SF Btuh --'Zone 2--- 12 Upper Level -Loft 275 1,777 13 Upper Level-Bdrm 176 1,219 #3 14 Upper Level -Bath 140 1,993 #3 & Closet 15 Upper Level- 231 3,852 Bdrm #2 16 Upper Level- Bath 104 809 #2 & Closet 17 Foyer 2nd A 372 3,056 Level Misc Return Gain System 2 total 1,298 12,706 Cooling^System Summary r90 Min Run Run Clg Htg Duct Duct Sens CFM Size Vel Btuh 74 2-0 0 2,477 51 2-0 0 2,462 83 1-0 0 1,267 161 2-0 0 3,763 34 1-0 0 1,748 128 2-0 0 3,223 530 Cooling Sensible/Latent Tons Split Elit6 '—fare Development, Inc.1 Page_-13_, Clg Min Act Lat Clg Sys Btuh CFM CFM 195 124 124 395 123 123 -9 63 63 385 188 188 -3 88 88 189 161 161 0 4,000 14,940 5,152 748 748 Sensible Latent Total Btuh Btuh Btuh Net Required: 1.67 74% / 26% 14,940 5,152 20,092 Actual: 2.00 75% / 25% 18,000 6,000 24,000 Equipnlent ❑ata -� ��eati�S-y�tem Cooling 5v_ stem Type: Natural Gas Furnace Standard Air Conditioner Model: R951 VO603 Indoor Model: Brand: RUUD RUUD Efficiency: 95 AFUE 0 SEER Sound: 30 30 Capacity: 47,000 Btuh 24,000 Btuh Sensible Capacity: n/a 18,000 Btuh Latent Capacity: n/a 6,000 Btuh This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODB: 88F, SOWB: 62F, WODB: -5F, SIDB: 70F, SIRH: 50%, WIDB: 70F, Sen. gain: 14,940 Btuh, Lat. gain: 5,152 Btuh, Sen. loss: 12,706 Btuh, Entering clg. coil DB: 70F, Entering clg. coil WB: 57F, Entering htg. coil DB: 70F, Clg. coil TD: 25F, Htg. coil TD: 30F, Req. clg. airflow: 748 CFM, Req. htg. airflow: 530 CFM C:\ ...\Aspen Glen _ ... _10-8-25.0 0 Tuesday, October 7, 2025, 2:20 PM Rhvac - Residential & Light Commercial HVAC Loads MDA Design - - - 1 Elite Software Development, Inc. Consulting, LLC Lcastle Rock, CO 80109 [System 3 Room Load S«mn7a/y Page 14 , Htg Min Run Run Clg Clg Min Act Room Area Sens Htg Duct Duct Sens Lat Clg Sys No Nance SF Btuh CFM Size Vel Btuh Btuh CFM CFM --Zone 3--- -- — 18 Lower Level Bath 47 790 33 2-0 0 4,391 796 220 220 #4 19 Lower Level Bdrm 216 2,121 89 1-0 0 1,774 391 89 89 #4 20 Lower Level 920 6,982 291 3-0 0 4,699 773 235 235 Entertainmenr % Room 21 Lower Level Bath 47 790 33 2-0 0 4,391 796 220 220 #4 22 Lower Level Bdrm 216 2,121 89 1-0 0 1,774 391 89 89 #4 Misc Return Gain 0 2,000 System 3 total 1,446 12,804 534 17,029 5,147 853 853 Cooling System Summary Cooling Sensible/Latent Sensible Latent Total' L _ Tons __ _ _,_ _SPlit _ _ Btuh Btuh Btuh Net Required: 1.85 77% / 23% 17,029 5,147 22,176 Actual: 2.00 75% / 25% 18,000 6,000 24,000 Equipment Data _. l iQating_Svstem Type: Natural Gas Furnace Cooling System Standard Air Conditioner Model: R951 VO603 Indoor Model: Brand: RUUD RUUD Efficiency: 95 AFUE 0 SEER Sound: 30 30 Capacity: 47,000 Btuh 24,000 Btuh Sensible Capacity: n/a 18,000 Btuh Latent Capacity: n/a 6,000 Btuh This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODS: 88F, SOWB: 62F, WODB: -5F, SIDE. 70F, SIRH: 50%, VVIDB: 70F, Sen. gain: 17,029 Btuh, Lat. gain: 5,147 Btuh, Sen. loss: 12,804 Btuh, Entering clg. coil DB: 70F, Entering clg. coil WB: 57F, Entering htg. coil DB: 70F, Cig. coil TD: 25F, Htg. coil TD: 30F, Req. clg. airflow: 853 CFM, Req. Mg. airflow: 534 CFM C:1... \Aspen Glen_... _10-8-25.0 0 Tuesday, October 7, 2025, 2:20 PM her Coo is o 7Comrafors of A—o Contractor Mechanical License # Building Plan # County, Town, Municipality, Jurisdiction Header Information REQUIRED ATTACHMENTS' Manual J1 Form (and supporting worksheets): Yes❑X or MJ1AE Form' (and supporting worksheets): Yes[] OEM performance data (heating, cooling, blower):Yes❑x Sys. 1 Manual D Friction Rate Worksheets Yes❑ Duct distribution system sketch: Yes[] Form RPER 1.01 8 Mar 10 ATTACHED No❑ Non No❑ Non Non Home Address (Street or Lot#, Block, Subdivision) HVAC LOAD CALCULATION (IRC M1401.3) Design Conditions Winter Design Conditions Building Outdoor temperature `fir -F Orientation (Front door faces) Indoor temperature 70 ,F North, East, West, South, Northeast, N wesi, So asi, Southwest Number of bedrooms Total heat loss 41539 Btu/h Conditioned floor area q Ft Summer Design Conditions Outdoor temperature 88 o f Number of occupants Indoor temperature 70 'F Windows Roof Grains difference -2 A Gr @ % % Rh Eave overhang depth Q Ft Sensible heat gain 361 8A Btulh Internal shade Eave Latent heat gain 11087 Btu/h Blinds, drapes, etc Depth Window Total heat gain Btu/h Number of skylights EQUIPMENT• '0 Data Hamatinq Fnl iinment Data GoAling Fqul:.nment Data- Blower Equipment type Natural Gas Furnace Equipment type Standard Air Conditioner Heating CFM nn CFM Furnace, Heat pump, Boiler, etc. Air Conditioner, Heat pump, etc Model R951VO855 Model _ RA15AY48 Cooling CFM 11679 CFM Heating output capacity 71 000 Btu/h Sensible cooling capacity 3600n Btu/h Heat pumps - capacity at winter design outdoor conditions Latent cooling capacity 1 goon Btu/h Auxiliary heat output capacity Btu/h Total cooling capacity 48000 Btu/h DISTRIBUTIONHVAC DUCT •0 Design airflow CFM Longest supply duct: Ft Duct Materials Used (circle) Trunk Duct: Duct board, Flex, Sheet metal, External Static Pressure (ESP) IWC Longest return duct: Ft Lined sheet metal, Other (specify) Component Pressure Losses (CPL) IWC Total Effective Length (TEL) Ft Branch Duct: Duct board, Flex, Sheet metal, Available Static Pressure (ASP) IWC Friction Rate: IWC Lined sheet metal, Other (specify) ASP=ESP - CPI Friction Rate = (ASP x 100) -. TEL Contractor's Printed Name Date Contractor's Signature Reserved for use by County, Town, Municipality. or Authority having jurisdiction. ' The AHJ shall have the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions. If abridged version of Manual J is used for load calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions. Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program. ACCK. : rCt% —,3 CoM,v rg of A—— County, Town, Municipality, Jurisdiction Header Information Contractor Mechanical License # Building Plan # Home Address (Street or Lot#, Block, Subdivision) REQUIRED ATTACHMENTS' Manual J1 Form (and supporting worksheets): Yes❑X or MJ1AE Forrnz (and supporting worksheets): Yes[] OEM performance data (heating, cooling, blower):Yesm Sys_ 2 Manual D Friction Rate Worksheet: Yes[] - Duct distribution system sketch: Yes[] Form RPER 1.01 8 Mar 10 ATTACHED No❑ No❑X No ❑ No❑X No❑X Design C.onditLOIlS Bu Winter Design Conditions Building Outdoor temperature °F Orientation (Front door faces) 4 Indoor temperature 7a o f North, East, west, South, Northeast, est. S ast, Southwest Total heat loss _ /'�� ��7i.1S.Z Btu/h Number of bedrooms Summer Design Conditions Conditioned floor area Sq Outdoor temperature �,�_ of Number of occupants Indoor temperature 70- 'F Windows Grains difference 2 A Gr % Rh @�_ Roof Eave overhang depth U f1 Ft Sensible heat gain Z 4�_0 Btu/h Internal shade Eave Latent heat gain fj 1 _52 Btu/h Blinds, drapes, etc Depth Window Total heat gain 2 0 (LC)2 Btu/h Number of skylights n HVAC EQUIPMENT SELECTION - 4, heating-EquipmenLiData Blower Data Equipment type Natural Gas Furnace Equipment type Standard Air Conditioner Furnace, Heat pump, Boiler, etc. Air Conditioner, Heat pump, etc Heating CFM r&a CFM Model R951 VO603 Model Heating output capacity 47000 Btu Sensible cooling capacity Heat pumps - capacity at winter design outdoor conditions Latent cooling capacity Auxiliary heat output capacity Btu/h Total cooling capacity Design airflow CFM Longest supply duct: External Static Pressure (ESP) IWC Longest return duct: Component Pressure Losses (CPL) IWC Available Static Pressure (ASP) ASP = ESP - CPL Contractor's Printed Name Total Effective Length (TEL) IWC Friction Rate: Friction Rate = (ASP x 100) +TEL RA15AY24 __ 8 0 0 Q Btu/h 6DM Btu/h 24000 Btu/h Cooling CFM ao CFM Ft Duct Materials Used (circle) Trunk Duct: Duct board, Flex, Sheet metal, Ft Lined sheet metal, Other (specify) Ft Branch Duct: Duct board, Flex, Sheet metal, IWC Lined sheet metal, Other (specify) Date Contractor's Signature Reserved for use by County, Town, Municipality, or Authority having jurisdiction, The AHJ shall have the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions. ' If abridged version of Manual J is used for load calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions. Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program. /� ACCk County, Town, Municipality, Jurisdiction Header Information Contractor Mechanical License # Building Plan # Home Address (Street or Lot#, Block, Subdivision) REQUIRED ATTACHMENTS' Manual J1 Form (and supporting worksheets)_ Yesm or MJ1AE Fomt' (and supporting worksheets): Yes❑ OEM performance data (heating, cooling, blower):Yesm Sys. 3 Manual D Friction Rate Worksheet: Yes❑ Duct distribution system sketch: Yes❑ Form RPER 1.01 8 Mar 10 ATTACHED No ❑ No❑X No❑ No❑X No❑X HVAC •.D CALCULATION (IRC M1401.3) D sign Cortditions Rtlilding Conctritrtion Information Winter Design Conditions Building Outdoor temperature _5 °F Orientation (Front door faces) °F North, East, West, South, Northeast, Nort head, Southwest Indoor temperature 70 Number of bedrooms Total heat loss 12804 Btu/h Conditioned floor area Sq Ft Summer Design Conditions Outdoor temperature A_a °F Number of occupants Indoor temperature __7Q_ °F Windows Roof Grains difference -2 A Gr @_,% % Rh Eave overhang depth Ft Sensible heat gain 1 7099 Btu/h Internal shade Eave Latent heat gain � 47 Btu/h Blinds, drapes, etc Depth Window Total heat gain 29 176 Btu/h Number of skylights EQUIPMENTHVAC • '0 Equipment type Natural Gas Furnace Con]ing Fgliinment Equipment type Data Blower Data Standard Air Conditioner Heating CFM 56n CFM Furnace, Heat pump, Boiler, etc Air Conditioner, Heat pump, etc Model R951 VO603 Model RA15AY24 Cooling CFM Rnn CFM Heating output capacity 470_0()L Btu/h Sensible cooling capacity 80M Btu/h Heat pumps - capacity at winter design outdoor conditions Latent cooling capacity 6000 Btu/h Auxiliary heat output capacity Btu/h Total cooling capacity 240_W Btu/h HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601.1) Design airflow CFM Longest supply duct: Ft Duct Materials Used (circle) Trunk Duct: Duct board, Flex, Sheet metal, External Static Pressure (ESP) IWC Longest return duct: Ft Lined sheet metal, Other (specify) Component Pressure Losses (CPL) IWC Total Effective Length (TEL) Ft Branch Duct: Duct board, Flex, Sheet metal, Available Static Pressure (ASP) IWC Friction Rate: IWC Lined sheet metal, Other (specify) ASP = ESP - CPL Friction Rate = (ASP x 100) — TEL Contractors Printed Name Date Contractors Signature Reserved for use by County, Town, Municlipality, or Authority having jurisdiction. ' The AHJ shall have the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions. If abridged version of Manual J is used for load calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions. Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program. ACCK. �0— oM County, Town, Municipality, Jurisdiction Header Information Contractor Mechanical License # Building Plan # Home Address (Street or Lot#, Block, Subdivision) REQUIRED ATTACHMENTS' Manual J1 Form (and supporting worksheets): Yeso or MAAE Form' (and supporting worksheets): Yes[] OEM performance data (heating, cooling, blower):Yes X❑ Sys. 1 Manual D Friction Rate Worksheet: Yes[] Duct distribution system sketch: Yes❑ Form RPER 1.01 8 Mar 10 ATTACHED No ❑ No0 No❑ Noo No m HVAC LOAD CALCULATION (UMC 1106.1) L7l-S1gn Conditions Ruildinq C onctruction Info matiIIaL Winter Design Conditions Building Outdoor temperature —5 °F Orientation (Front door faces) 2 Indoor temperature _M of North, East, West, South, Northeast, Northwest, Southeast, Southwest Number of bedrooms 2 Total heat loss 4'� �� Btu/h Summer Design Conditions Conditioned floor area _ 1 872 Sci Ft Outdoor temperature- - 8.8- of Number of occupants Indoor temperature 70 'F Windows Grains difference —� A Gr % Rh @_� Eave overhang depth Q Ft Roof Sensible heat gain '16 1 RA Btu/h Internal shade Eave Latent heat gain 11087 Btu/h Blinds, drapes, etc Depth Window Total heat gain 47976 Btu/h Number of skylights n HVAC EQUIPMENT SELECTION Equipment type Natural Gas Furnace Equipment type Standard Air Conditioner Blower Data 11 nn CFM Heating Furnace, Heat pump, Boiler, etc. Air Conditioner, Heat pump, etc CFM Model R951 VO855 Model RA15AY48 Cooling CFM 1 CZ CFM Heating output capacity 71 000 Btu/h Sensible cooling capacity 36jaM Btu/h Heat pumps - capacity at winter design outdoor conditions Latent cooling capacity 20M Btu/h Auxiliary heat output capacity Btu/h Total cooling capacity 48000 Btu/h .HVAC DUCT DISTRIBUTION•1 Design airflow CFM Longest supply duct: Ft Duct Materials Used (circle) Trunk Duct: Duct board, Flex, Sheet metal, External Static Pressure (ESP) IWC Longest return duct: Ft Lined sheet metal, Other (specify) Component Pressure Losses (CPL) Available Static Pressure (ASP) ASP = ESP - CPL Contractor's Printed Name IWC Total Effective Length (TEL) IWC Friction Rate: Friction Rate = (ASP • 100) =TEL Ft Branch Duct: Duct board, Flex, Sheet metal, IWC Lined sheet metal, Other (specify) Date Contractor's Signature Reserved for use by County, Town, Municlipality, or Authority having jurisdiction. ' The AHJ shall have the discretion to accept Required At+. =.chmcnts nnriterl from approved ACCA software vendors, see list on page 2 of instructions. ' If abridged version of Manual J is used for load calculation, then vel ify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions. Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program. ACCK , Contractor Mechanical License # Building Plan # County, Town, Municipality, Jurisdiction Header Information Sys. 2 REQUIRED ATTACHMENTS' Manual J1 Form (and supporting worksheets): Yes or MJ1AE Form' (and supporting worksheets): Yes❑ OEM performance data (heating, cooling, blower):Yeso Manual D Friction Rate Worksheets Yes[] Duct distribution system sketch: Yes[] Form RPER 1.01 8 Mar 10 ATTACHED No❑ No ❑X No❑ No❑X No0 Home Address (Street or Lot#, Block, Subdivision) HVAC LOAD CALCULATION Design Conditions Winter Design Conditions Building Outdoor temperature of Orientation (Front door faces) ,F North, East, West, South, Northeast, Northwest, Southeast, Southwest Indoor temperature _ Number of bedrooms 2 Total heat loss 19706 Btu/h Summer Design Conditions Conditioned floor area '� 29$ Sq Ft Outdoor temperature 88 o f Number of occupants . Indoor temperature 70 o f Windows Roof Grains difference _2 A Gr @ % % Rh Eave overhang depth O Ft �— Sensible heat gain 14940 Btu/h Internal shade Eave Latent heat gain 5159 Btu/h Blinds, drapes, etc Depth Window Total heat gain 9009 Btu/h Number of skylights EQUIPMENTHVAC • Heatinrr Fnttinment Data Blower Data ----� Equipment type Natural Gas Fumace Equipment type Standard Air Conditioner Heating CFM 560 CFM Furnace, Heat pump, Boiler, etc. Air Conditioner, Heat pump, etc Model R951VO603 Model RA15AY24 Cooling CFM CFM Heating output capacity 47O00 Btu/h Sensible cooling capacity 1 g()()O Btu/h Heat pumps - capacity at winter design outdoor conditions Latent cooling capacity 6000 Btu/h Auxiliary heat output capacity Btu/h Total cooling capacity Btu/h .HVAC DUCT DISTRIBUTION SYSTEM DESIGN (UMC •0 Design airflow CFM Longest supply duct: Ft Duct Materials Used (circle) Trunk Duct: Duct board, Flex, Sheet metal, External Static Pressure (ESP) IWC Longest return dud: Ft Lined sheet metal, Other (specify) Component Pressure Losses (CPL)_ IWC Total Effective Length (TEL) _ Ft Branch Dud: Duct board, Flex, Sheet metal, Available Static Pressure (ASP) IWC Friction Rate: IWC Lined sheet metal, Other (specify) ASP = ESP - CPL Friction Rate = (ASP x 100) = TEL Contractors Printed Name Date Contractor's Signature Reserved for use by County,Town,p ' The AHJ shall have the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions. If abridged version of Manual J is used for load calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions. Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program. ACCK. Av Ga ,-.-g Cod,a-OAny County, Town, Municipality, Jurisdiction Header Information Contractor Mechanical License # Building Plan # Home Address (Street or Lot#, Block, Subdivision) Sys. 3 REQUIRED ATTACHMENTS' Manual A Form (and supporting worksheets): Yes❑X or MJ1AE Form' (and supporting worksheets): Yes❑ OEM performance data (heating, cooling, blower):Yes X❑ Manual D Friction Rate Worksheet: Yes❑ Duct distribution system sketch: Yes❑ Form RPER 1.01 8Mar 10 ATTACHED No ❑ NorXi No❑ No0 Noo HVAC LOAD CALCULATION0• Desiarl__CDnditians Bij lcW nstruC'finn Infacmatian Winter Design Conditions Building Outdoor temperature °F Orientation (Front door faces) 2 Indoor temperature r ► r °F North, East, west, South, Northeast, Northwest, Southeast, Southwest Total heat loss 12804 Btu/h Number of bedrooms Summer Design Conditions op op Conditioned floor area —1446 Sq Ft RR Outdoor temperature - o f Number of occupants Indoor temperature —0 'F Windows Roof Grains difference —2 A Gr @ K % Rh Eave overhang depth Ft Sensible heat gain 17029 Btu/h Internal shade _ Eave Latent heat gain 5147 Btu/h Blinds, drapes, etc Depth Window Total heat gain 92 176 Btu/h Number of skylights 0 EQUIPMENTSELECTION H_eafJng-Egt.ttpmpntData meting--E-q ipmeat-Data Blower Data Equipment type Natural Gas Furnace Equipment type Standard Air Conditioner Furnace, Heat pump, Boiler, etc. Air Con ail ioner, Heat pump, etc Heating CFM _56_0 CFM Model R951 VO603 Model RA15AY24 Cooling CFM Rnn CFM Heating output capacity 47nnn Btu/h Sensible cooling capacity _ _$QDQ Btu/h Heat pumps - capacity at winter design outdoor conditions Latent cooling capacity _ --600G Btu/h Auxiliary heat output capacity Btu/h Total cooling capacity 240OQ Btu/h HVAC DUCT DISTRIBUTION SYSTEM DESIGN (UMC •0 Design airflow CFM Longest supply duct: Ft Duct Materials Used (circle) Trunk Duct: Duct board, Flex, Sheet metal, External Static Pressure (ESP) IWC Longest return duct: _ Ft Lined sheet metal, Other (specify) Component Pressure Losses (CPL) IWC Total Effective Length (TEL) Ft — Branch Duct: Duct board, Flex, Sheet metal, Available Static Pressure (ASP) IWC Friction Rate: IWC Lined sheet metal, Other (specify) ASP = ESP - CPL Friction Rate = (ASP x 100) _ TEL I declare the load calculation, equipment selection, and duct system design were rigorously performed based on the building plan listed above,. I understand.the claims made on - forms will be subiect to review and verification Contractor's Printed Name Date Contractor's Signature Reserved for use by •Town,._ or • • jurisdiction. ' The AHJ shall have the discretion to accept Required Attachments printed From approved ACCA software vendors, see fist on page 2 of instructions. ' If abridged version of Manual J is used for load calculation, then verify residence mMs. requirements, see Abridged Edition Check isl on page 13 of instructions. Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program.