HomeMy WebLinkAboutRescheck ReportCNJ/ REScheck*Web TM Compliance Certificate Project Information Project Title: Energy Code: Location: Construction Type: Project Type: Project Sub Type: Climate Zone: Project No: All Electric: Is Renewable: Has Battery: Has Charger: Has Heat Pump Construction Site, 318 Midland Ave Carbondale , CO 81623 Project Notes: Czechowicz Mechanical 2018 IECC Carbondale, Colorado Single Family Alteration None 5b (7313 HDD) 1789817 true true true true true Owner/Agent: Joe Czechowicz 318 Midland Ave Carbondale , CO 81623 970.948.0458 Interior Alteration to existing building only. This Rescheck is for Mechanical only. Designer/Contractor: Robert Thorpe 1980 Lazy O Rd Thorpe Architects Carbondale , CO 81623 970.394.4406 bob@thorpeforce.com Report Title: Czechowicz Mechanical Report Date: 11/13/25, 1:19 PM 1 of 9 Envelope Assemblies Prop. Req. Assembly Gross Area or Cavity Cont. U- U- Prop. Req. Perimeter R-Value R-Value Factor/ Factor/ UA UA F-Factor F-Factor Compliance::. Slab -on -grade tradeoffs are no longer considered in the UA or performance compliance path in REScheck. Each slab -on -grade assembly in the specified climate zone must meet the minimum energy code insulation R-value and depth requirements. Report Title: Czechowicz Mechanical Report Date: 11/13/25, 1:19 PM 2 of 9 r�(, Inspection Checklist Energy Code: 2018 IECC Requirements: 44% were addressed directly in the RESCheCk software Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Pre-Inspection/Plan Review Section Plans i # Verified & Req.ID Pre-Inspection/Plan Review Value 103.1, Construction drawings and 103.2, documentation demonstrate 403.7 energy code compliance for [PR3]1 lighting and mechanical Systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. 1 302.1, Heating and [aaling equipment is ACCA Manual 5 Heating: Btu/hr 403.7 sized per i [PR2]2 based on loads calculated per ACCA Manual 1 or other methods ` approved by the code official. Cooll ng: I Btu.._ 1hr Additional Comments/Assumptions: Field Verified Value Heating: Btu/hr .i Cooling: Btu hr Complies? Comments/Assumptions Complies PDoes Not omply Not servable Not pplicable Complies Does Not omply Not servable Not pplicable 1 I High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Report Title: Czechowicz Mechanical Report Date: 11/13/25, 1:19 PM 3 of 9 Foundation Inspection Section & Req.ID Foundation Inspection Complies? 403.9 Snow- and ice -melting system controls Complies [FO12]2 installed. o Does Not Umply Not servable PNot licable Additional Comments/Assumptions: Comments/Assumptions 1 1 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3) Report Title: Czechowicz Mechanical Report Date: 11/13/25, 1:19 PM 4 of 9 Framing / Rough -in Inspection Section Plans Field # Framing /Rough -In Verified Verified I & Req.ID Inspection Value Value Complies? Comments/Assumptions 403.3.1 Supply and return ducts in attics I insulated >= R-8 where duct is Complies [FR12]1 >= 3 inches in diameter and Does Not >= R-6 where < 3 inches. omply Supply .and return ducts in other building Not portions of the insulated R-5 for diameter servable >= >= 3 inches and R-4.2 for < 3 Not inches in diameter. pplicable 403.3.2 Ducts, air handlers and filter Q Complies + [FR13]1 boxes are sealed with joints/seams compliant with Does Not Jll International Mechanical Code omply or International Residential Not Code, as applicable. servable Not Applicable 403.3.5 Building cavities are not used as Complies [FR15]3 ducts or plenums. Does Not ` omply a Not Observable Not pplicable 403.3.6(1, Ducts partially or completely Complies 2) [FR26]3 buried in ceiling insulation have Does Not an insulation R•value not. less omply than R-8, the sum cf the ceiling insulation R-value against and ❑ Not above the top of the duct, and Observable against and below the bottom of Not the duct, is >— than R-19, excluding the R-value of the pplicable duct insulation. 403.4 HVAC piping conveying fluids RR L ❑ Complies [FR17]� above 105 -F or chilled fluids below 55 °F are insulated to >_R- ! Does Not 1 3 omply Not I Observable l Not pplicable 403.4.1 Protection of insulation on HVAC { ❑ Complies [FR24]1 iplping• ❑ Does Not Comply Not servable Not pplicable 403.5.3 Hot water pipes are insulated to R f1 R f� Complies [FR18]2 >_R-3. Q Does Not Comply o Not Observable PANot pplicable Additional Comments/Assumptions: 1 1 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3) Report Title: Czechowicz Mechanical Report Date: 11/13/25, 1:19 PM 5 of 9 Insulation inspection Section # & Req.ID Insulation Inspection Additional Comments/Assumptions: Complies? Comments/Assumptions 1 Hiah Impact (Tier 1) 2 I Medium Impact 13 I Low Impact (Tier 3) Report Title: Czechowi¢ Mechanical Report Date: 11/13/25, 1:19 PM 6 of 9 Final Inspection Provisions Section & Rea.ID [FI10]z 403.5.1 [FI11]z Plans Verified Final Inspection Provisions Value Heat pump thermostat installed on heat pumps. Circulating service hot water systems have automatic or accessible manual controls. 403.6.1 All mechanical ventilation [FI25]2 system fans not part of tested and listed HVAC equipment meet efficacand air flow limits per Table R463.6.1. 403.2 Hot water boilers supplying heat [FI26]2 through one- I twa-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. I 403.5.1.1 Heated water circulation [FI28]2 systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravfty and thermos -syphon circulation systems are not present. Controls for circulating hot water system pumps start the within the occupancy demand Controls automatically turn off the pump when water Is in circulation loop is at set -point temperature and no demand for hot water exists. 1 403.5.1.2 Electric heat trace syYstems 1 11L [FI29]2 comply with IEEE 515 or 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. I i 403.5.2 Demand recirculation water [FI30]2 controls manage operation of the pump and limit the temperature of the water entering the cold water piping to <= 104°F. 403.5.4 Drain water heat recovery units [FI31]2 tested in accordance with CSA B55.1. Potable water -side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water -side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Field Verified Value Complies? Q Complies PoDoesNot omply Not servable PNot plicable Complies Does Not omply Not servable Not pplicable Complies Does Not Does Not servable Not pplicable Complies Does Not omply Not servable Not pplicable 0 Complies RDoes Not omply 9 Not servable PNot plicable Complies RDoes Not omply Not servable Not pplicable Complies Does Not omply Not servable Not Applicable 0 Complies Q Does Not Comply Not servable Not pplicable Comments/Assumptions Exception: Requirement is not applicable. Report Title: Czechowicz Mechanical Report Date: 11/13/25, 1:19 PM 7 of 9 Section 4t & Req.ln Plans Verified Final Inspection Provisions Value Field Verified value Complies? CornmentslAssumptions 404.1 90% or more of permanent Complies [FI611 fixtures have high efficacy Does Not lamps. ompfy ' Q Not servable I� 1� Not pplicable 404.1.1 Fuel gas lighting systems have Complies [FI2313 no continuous pilot light. [�J Does Not Comply PINot servable [� Not l pplicable 303.3 Manufacturer manuals for Complies [FI1813 mechanical and water heating Does Not systems have been provided. ompfy Not servable 0ppNot { licable 403.3.3 Ducts are pressure tested to Complies [FI2711 determine air leakage with either: Rough -in test: Total cfm/100 ft2 cfm/100 ft2 Does Not leakage measured with a omply pressure differential of 0.1 inch Not [� w.g. across the system including servable the manufacturer's air handler Not enclosure if installed at time of test. Postconstruction test: Total pplicable leakage measured with a pressure differential of 0.1 Inch w.g. across the entire system Including the manufacturer's air handler enclosure. 403.3.4 Duct tightness test result of n Complies [FI411 r=4 cfmi100 ft2 across the system or <=3 cfm/100 ft2 cfm/100 ft2 Does Not cfm/100 ft2 without air handler @ 25 Pa. For omply rough -in tests. verification may Not need to occur during Framing servable Inspection. Not pplicable 403.3.2.1 Air handler leakage designated i Q Complies [FI2411 by manufacturer at <=2 h of design air flow. Does Not omply Not servable PpNot plicable 403.1,1 Programmable thermostats 0 Complies [Flglr installed for control of primary heating and cooling systems Does Not and initially set b manufacturer ompfy to code specditatYons. Not servable Not pplicable Additional Comments/Assumptions: 1 1 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 3 I Low Impact (Tier 3) Report Title: Czechowicz Mechanical Report Date: 11/13/25, 1:19 PM 8 of 9 2018 IECC Energy Efficiency Certificate Above -Grade Wall Below -Grade Wall Floor Ceiling / Roof Ductwork (unconditioned spaces): Window Door Skylight Heating System: Cooling System: Water Heater: Name: Comments: 0.00 0.00 0.00 Date: 0.00 0.00 0.00 0.00 Report Title: Czechowicz Mechanical Report Date: 11/13/25, 1:19 PM 9 of 9