Manual S Report
Dexter Diagnostics Manual S Compliance Re ort Job: � � Date: Nov 71, 2026 Entire House s)rDo Bob Schneider Project Information For. 3426 Elk Springs Drive Glenwood Springs, CO 81601 Cooling Equipment Design . Outdoor design DB: 92.7°F Sensible gain: 36188 Btuh Entering coil DB: 75.4°F Outdoor design WB: 58A'F Latent gain: 0 Btuh Entering coil WB: 61.3°F Indoor design DB: 75.0°F Total gain: 36188 Btuh Indoor RH: 50% Estimated airflow: 1517 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: SplitAC Manufacturer: York Model: YXV48B21+JHWC48HE3C2N1++CC Actual airflow: 1517 cfrn Sensible capacity: 36400 Bhuh 101%of load Latent capacity: 9100 Btuh 0% of load Total capacity. 45500 Btuh 126% of load SHR 80% Heating Equipment Design. Outdoor design DB: -2.0°F Heat loss: 75062 Btuh Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Gas furnace Manufacturer: York Actual airflow: 1517 ctrn Output capacity. 96000 Btuh Meets all requirements ofACCA Manual S. Model: TM9Y100C16MP11 128% of load Entering coil DB: 68.4°F Temp. rise: 50 OF wrigtrtso t- 2025-Nov-1719:07:56 RightWteS Universal 2025 25.0.03 RSU56586 Page 1 AM Sdmider)\9426Elk SprirgsDrive_MamelJnp Cale=MJB Frort Door faoes: NW Dexter Diagnostics 100"o Load Short Form Entire House Bob Schneider Project Information For: 3426 Elk Springs Drive Glenwood Springs, CO 81601 Job: Date: Nov 11, 2026 By: Design Information Hta CIO Infiltration Outside db (OF) -2 93 Method Blower door Inside db (OF) 70 75 Shielding / stories 3 (partial) / 1 Design TD (OF) 72 18 Pressure /AVF 50 Pa / 3456 cfm Daily range - H Inside humidity (°A) 30 50 Moisture difference (grAb) 37 -44 HEATING EQUIPMENT Make York Trade YORK BY JOHNSON CONTROLS Model TM9Y100C16MP11 AHRI ref 8412960 Efficiency 96 AFUE Heating input 100000 Btuh Heating output 96000 Btuh Temperature rise 74 OF Actual airflow 1517 cfm Air flow factor 0.021 drn/Btuh Static pressure 0 in H2O Space thermostat COOLING EQUIPMENT Make York Trade YORK Cond YXV48621 Coil JHWC48HE3C2N1++CC AHRI ref 211004028 Efficiency 12.5 EER2, 20 SEER2 Sensible cooling 36400 Btuh Latentcooling 9100 Btuh Total cooling 45500 Btuh Actual airflow 1517 cfm Airflowfactor 0.042 cfrn/Btuh Static pressure 0 in H2O Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load HtgAVF ClgAVF (ft2) (Btuh) (Btuh) (ctm) (drn) Master Suite 240 4383 2661 91 113 Kitchen + Dining 513 4967 5097 103 217 Living Room 2941 39663 13208 823 561 Bed #2 240 3147 2494 65 106 Bath #2 55 0 0 0 0 Master Bath 183 2072 613 43 26 Hallway 142 2488 1905 52 81 Laundry 165 2170 1754 45 75 Entry Foyer 226 5182 3766 108 160 Dressing 164 3556 954 74 41 Hallway by Garage 145 0 0 0 0 Study 125 1810 1315 38 56 Bed #3 308 3654 1938 76 82 Bok taic vadies have been marruaiy ove►ridden Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -' P wrightsoft 2025-Nov-1719:07:56 A k-/ ... PighFSdte@LMwrml202525.0,03RSU56586 Pagel Sctmider)S426 Etk Springs Drive_Marual J.rup Catc= MJ8 Frort Door faces NW Entire House 5447 73091 35704 1517 1517 Other -equip loads 1970 484 Equip. @ 0.98 RSM 35356 Latent cooling 0 TA 1 ^ CAA7 7FM7 IgRlgRR 1 F17 1517 BoWiitaic values have been manually overridden Calculations approved byACCA to meet all requirements of Manual J 8th Ed. I wr ightsoti` RightSUL-@Uriwrsal202525.0.03RSU56586 Sdneider)\9426 Elk Springs Ddve_Marual Jnp Cak:= MJ8 FrortDoorfaces: NW 2025-Nov-1719:07:56 Page 2 Dexter Diagnostics Component Constructions JOb' p Date: Nov 11, 202& Entire House sy: 100�0 Bob Schneider Project Inf• • For: 3426 Elk Springs Drive Glenwood Springs, CO 81601 Design C• • • Location: Indoor: Heating Cooling Rifle Garfield CountyAP, CO, US Indoor temperature (T) 70 75 Elevation: 6897 ft Design TD (T) 72 18 Latitude: 40ON Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture differenoe (galb) 37.2 A4.0 Dry bulb (T) 2 93 Infiltration: Daily range (T) - 34 (H ) Method Blower door Wet bulb (T) - 58 Shielding / stories 3 (partial) / 1 Wind speed (mph) 15.0 7.5 Pressure /AVF 50 Pa / 3456 cfm Construction descriptions Or Area Uvalue Insul R Htg HTM Lass Clg HTM Gain V BktV F fP F/Bkh Bktff Bkh BMW Bhih Walls 15B-15sfa4: Bg wall, light dry soil, concrete wall, r-15 ins, 8" thk R20 Cavity Wall: Frm wall, wd ext. 1/2"wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, 2'56" wood frm, 16" o.c. stud Partitions 12F-0sw.. Frm wall, 5/8" gyp.bd ext, r-21 cav ins, 5/8" gypsum board int fnsh, 2'k6" wood firm, 16" o.c. stud Windows windows, 0.30 u-value and 0.38 SHGC: windows, 0.30 u value and 0.38 SHGC; 6.67 ft head ht windows, 0.30 uvalue and 0.38 SHGC: windows, 0.30 uvalue and 0.38 SHGC; 1 ft overhang (4.5 ft window ht, 4 ft sep.); 6.67 ft head ht windows, 0.30 uvalue and 0.38 SHGC: windows, 0.30 uvalue and 0.38 SHGC; 1 ft overhang (8 ft window ht, 9 ft sep.); 6.67 ft head ht windows, 0.30 u-value and 0.38 SHGC: windows, 0.30 uvalue and 0.38 SHGC; 1 ft overhang (4 ft window ht, 1 ft sep.); 6.67 ft head ht ne 270 0,041 15.0 3.94 1065 0.29 79 se 312 0.041 15.0 3.94 1230 0.29 91 sw 270 0.041 15.0 3.94 1065 0.29 79 nw 312 0.041 15.0 3.94 1230 0.29 91 all 1164 0.041 15.0 3.94 4590 0.29 339 ne 646 0.057 21.0 4.13 2668 0.64 413 se 465 0.057 21.0 4.13 1918 0.64 297 sw 280 0.057 21.0 4.13 1158 0.64 179 nw 557 0.057 21.0 4.13 2301 0.64 356 all 1949 0,057 21.0 4.13 8045 0.64 1246 285 0.065 21.0 2.47 704 0.65 185 ne 32 0.300 0 21.6 691 29.0 927 sw 21 0.300 0 21.6 454 35.1 738 nw 60 0.300 0 21.6 1296 29.0 1738 nw 77 0.300 0 21.6 1658 29.0 2223 nw 40 0.300 0 21.6 864 20.3 811 nw 44 0.300 0 21.6 950 29.0 1274 all 274 0.300 0 21.6 5913 28.2 7711 se 34 0.300 0 21.6 729 35.1 1186 se 120 0.300 0 21.6 2592 35.1 4217 se 28 0.300 0 21.6 612 33.7 956 t- wrightsnft" 2025-Nov-1719:07:56 .,,,. , ............,...,.._, Right-StiteSUriversal202525.0,03 RSU56586 Page 1 Schneider)\3426 Elk Sprirgs Ddve_Marual J.rup Calc= MA Frort Doorfaces: NW windows, 0.30 u-value and 0.38 SHGC: windows, 0.30 u-value and 0.38 se 24 0.300 0 21.6 518 34.4 827 SHGC; 1 ft overhang (8 ft window ht, 1 ft sep.); 6.67 ft head ht se 55 0.300 0 21.6 1195 34.4 1906 se 89 0.300 0 21.6 1915 34.4 3054 all 168 0.300 0 21.6 3629 34.4 5786 Doors 11DO: Door, wd sctype n 21 0.390 0 14.8 311 3.90 82 Ceilings 16i3-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 5/8" 2941 0.020 50.0 1.44 4235 0.92 2697 gypsum board int fnsh Floors 19A-0bstp: Part floor, frm fir, 6" thkns 2941 0.368 0 8.62 25356 2.12 6233 t +- wrightsoft' 2025-Nov-1719:07:56 RigWSL"Lkiversal202525.0.03RSU56586 Paget AMSdneider)\3426 Elk Springs Drive —Martial J rnp Calc = MJB Front Door faces: NW