Loading...
HomeMy WebLinkAboutBlower Door TestTesting Company: Name: Address: Technician: Name:Brian Chesney Credentials:BPI Certified ID#5068969 Email:c5energygj@gmail.com Building Information: Project ID:318 eagle ridge battlement mesa Address:318 Eagle Ridge Drive Battlement Mesa, Colorado 81635 Geo-Tag Data:Latitude: 39.443614 Longitude: -108.032095 Timestamp: 2025-12-18 08:29:39 Customer Information: Name: Address: Measured Leakage:2.26 ACH50 Leakage Target:3.00 ACH50 Compliance with Leakage Target:Pass Test ID:Blower door Purpose of Test:Envelope (IECC) Measured CFM50:918.3 Effective Leakage Area: 50.5 in² Building Volume:24,397.0 ft³Enclosure Surface Area: 0.0 ft² Coefficient (C):72.2 Exponent (n): 0.650 (assumed) Test Standard:RESNET 380 One-Point Test Mode: Depressurize Test Characteristics:Indoor Temp: 42 °F Altitude: 5,318.0 ft Outdoor Temp: 35 °F Time Average Period: 10 seconds Test Date and Time:2025-12-18 08:46:22 10% Adjustment Applied: No Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline -0.8 -50.0 -49.5 -48.7 -233.8 905.1 Ring B Test Equipment: Flow Device:Model 3 110V Fan Pressure Gauge:DG1000 Serial #: 13229 Calibration Date: 2024-08-27 Deviations from Standard: None Comments: None Envelope Leakage Test Page 2 of 2Report by TEC Auto Test 1.10.2 (3), © 2025 The Energy Conservatory, Inc.