HomeMy WebLinkAboutPlansM0-1 A.SUBSTITUTIONS: SUBSTITUTION OF SPECIFIED EQUIPMENT WILL BE ALLOWED THROUGH A PRIOR APPROVAL PROCESS INITIATED BY THE CONTRACTOR. CONTRACTOR SHALL SUBMIT INTENDED SUBSTITUTION AT LEAST FIVE DAYS PRIOR TO BID FOR APPROVAL FROM ENGINEER. SUBMITTAL SHALL INCLUDE CAPACITIES, DIMENSIONS AND OPERATING INSTRUCTIONS FOR EACH PIECE OF EQUIPMENT. SUBSTITUTION SHALL OCCUR AT NO COST TO THE OWNER. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF APPROVED SUBSTITUTION AND SHALL INCUR ALL COSTS ASSOCIATED WITH THE SUBSTITUTION INCLUDING STRUCTURAL MODIFICATIONS, SPACE LAYOUT AND REDESIGN COSTS. SEE ALSO DIVISION I GENERAL REQUIREMENTS. EXAMINATION OF SITE, DRAWINGS, SPECIFICATIONS: A.EXAMINE CAREFULLY THE SITE AND CONDITIONS OF THE SITE. PROVIDE ALL NECESSARY EQUIPMENT AND LABOR TO INSTALL A COMPLETE WORKING SYSTEM WITHIN THE SITE CONDITIONS. B.EXAMINE THE DRAWINGS AND SPECIFICATIONS AND 5 DAYS PRIOR TO BIDDING REPORT ANY ERRORS, OMISSIONS, INCONSISTENCIES, AND CONFLICTS TO THE ENGINEER TO BE REMEDIED IN AN ADDENDUM TO THE PROJECT PRIOR TO BID TIME. C.DRAWINGS ARE DIAGRAMMATIC AND CATALOG NUMBERS GIVEN ARE FOR REFERENCE ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE CAPACITY OF THE EQUIPMENT MEETS THE DRAWING REQUIREMENTS AND SHALL NOT DIMENSION FROM THE MECHANICAL, PLUMBING, OR PIPING DRAWINGS. D.THE LATEST ADOPTED VERSIONS OF THE INTERNATIONAL BUILDING CODES SHALL BE USED AS REQUIRED. THIS WILL ALSO INCLUDE THE LATEST ADOPTED VERSIONS OF THE MECHANICAL, PLUMBING, AND ENERGY CONSERVATION CODES. ALL METHODS AND MATERIALS REQUIRED BY THESE CODES SHALL BE REQUIRED BY THESE SPECIFICATIONS UNLESS INDICATED OTHERWISE. OTHER APPLICABLE LOCAL CODES AND ORDINANCES SHALL BE AS REQUIRED AND IT SHALL BE THE CONTRACTOR’S RESPONSIBILITY TO BE KNOWLEDGEABLE OF THESE REQUIREMENTS. E.WHERE INSTALLATION PROCEDURES OR ANY PART THEREOF ARE REQUIRED TO BE IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE MANUFACTURER OF THE MATERIAL BEING INSTALLED, PRINTED COPIES OF THESE RECOMMENDATIONS SHALL BE FURNISHED TO THE ENGINEER PRIOR TO INSTALLATION. INSTALLATION OF THE ITEM WILL NOT BE ALLOWED TO PROCEED UNTIL THE RECOMMENDATIONS ARE RECEIVED. FAILURE TO FURNISH THESE RECOMMENDATIONS CAN BE CAUSE FOR REJECTION OF THE MATERIAL. 44”MOUNTING HEIGHT ABOVE FINISHED FLOOR TO CENTER OF DEVICE A AMPS A.D.ACCESS DOOR AAV AIR ADMITTANCE VALVE ABV ABOVE AC AIR CONDITIONING UNIT AC ABOVE COUNTER AD AREA DRAIN (SEE SYMBOLS) A.F.C.ABOVE FINISHED CEILING A.F.G.ABOVE FINISHED GRADE AIC AMPERE INTERRUPTING CAPACITY AFCI ARC FAULT CIRCUIT INTERRUPTERS A.F.F.ABOVE FINISHED FLOOR AHU AIR HANDLING UNIT ALUM ALUMINUM AP ACCESS PANEL OR DOOR ATS AUTOMATIC TRANSFER SWITCH AV AUDIO / VIDEO AVG AVERAGE AWG AMERICAN WIRE GAGE BAS BUILDING AUTOMATION SYSTEM BB BASEBOARD BD BACK DRAFT DAMPER BFP BACK FLOW PREVENTOR BL BOILER BLDG BUILDING BLW BELOW BOB BOTTOM OF BEAM BOD BOTTOM OF DUCT BOP BOTTOM OF PIPE BSMT BASEMENT BTU BRITISH THERMAL UNIT C CHILLER CAFCI COMBINATION ARC FAULT CIRCUIT INTERRUPTERS CAP CAPACITY CB CIRCUIT BREAKER CBV CIRCUIT BALANCING VALVE CCT CORRELATED COLOR TEMPERATURE CKT CIRCUIT CFH CUBIC FEET PER HOUR CFM CUBIC FEET PER MINUTE CHWR CHILLED WATER RETURN CHWS CHILLED WATER SUPPLY CI CAST IRON CL CENTER LINE CLG CEILING CMU CONCRETE MASONRY UNIT CO CLEAN OUT COL COLUMN COMP COMPRESSOR CONC CONCRETE COND CONDENSATE CONN CONNECTION CONT CONTINUATION CONTR CONTRACTOR CRI COLOR RENDERING INDEX CT COOLING TOWER CT CURRENT TRANSFORMER CU CONDENSING UNIT CU COPPER CUH CABINET UNIT HEATER CVB CONSTANT VOLUME BOX CWR CONDENSER WATER RETURN CWS CONDENSER WATER SUPPLY DB DRY BULB DEPT DEPARTMENT DF DRINKING FOUNTAIN DIA DIAMETER DIAG DIAGRAM DIFF DIFFERENTIAL DISCH DISCHARGE DIV DIVISION DN DOWN DS DUCT SILENCER DWG DRAWING DX DIRECT EXPANSION (E) EXISTING EA EXHAUST AIR GRILLE/REGISTER EAT ENTERING AIR TEMPERATURE EC ELECTRICAL CONTRACTOR ECC ECCENTRIC EF EXHAUST FAN EFF EFFICIENCY EL ELEVATION ELEC ELECTRIC ELEV ELEVATOR EM EMERGENCY FUNCTION ENT ENTERING EMT ELECTRIC METALLIC TUBE EQ EQUAL EQUIP EQUIPMENT EQUIV EQUIVALENT ES END SWITCH ESP EXTERNAL STATIC PRESSURE ET EXPANSION TANK EWC ELECTRIC WATER COOLER EWT ENTERING WATER TEMPERATURE EX EXHAUST EXPAN EXPANSION EXT EXTERNAL F DEGREES FAHRENHEIT FA FREE AREA FC FAN COIL UNIT FC FOOTCANDLE FCV FLOW CONTROL VALVE FD FIRE DAMPER FD FLOOR DRAIN FIN FINISHED FLA FULL LOAD AMPS FLEX FLEXIBLE FLR FLOOR FOB FLAT ON BOTTOM FOT FLAT ON TOP FP FIRE PROTECTION FP FIRE PUMP FPM FEET PER MINUTE FPS FEET PER SECOND FS FLOW SWITCH FSD FIRE/SMOKE DAMPER FT FEET FXC FLEXIBLE CONNECTION GND GROUND GA GAUGE GAL GALLON GALV GALVANIZED GEC GROUND ELECTRODE CONDUCTOR GFCI / GFI GROUND FAULT CIRCUIT INTERRUPTER GC GENERAL CONTRACTOR GPH GALLONS PER HOUR GPM GALLONS PER MINUTE GRS/LB GRAINS PER POUND H 2O WATER HB HOSE BIBB HD HEAD (SEE SCHEDULES) HP HEAT PUMP HP HORSEPOWER HR HOUR HT HEIGHT HTR HEATER HWR HEATING WATER RETURN HWS HEATING WATER SUPPLY HX HEAT EXCHANGER HZ HERTZ ID INSIDE DIAMETER IG ISOLATED GROUND IN INCHES INV INVERT JBOX JUNCTION BOX K KELVIN KW KILOWATT KVA KILO VOLT - AMPS L LENGTH LAT LEAVING AIR TEMPERATURE LV LAVATORY LB POUND LD LINEAR DIFFUSER LF LINEAR FEET LIN LINEAR LIQ LIQUID LM LUMEN LRA LOCKED ROTOR AMPS LV LOUVER LVG LEAVING LWT LEAVING WATER TEMPERATURE MBH THOUSANDS OF BTU PER HOUR MC MECHANICAL CONTRACTOR MCA MINIMUM CIRCUIT AMPACITY MCB MAIN CIRCUIT BREAKER MD MOTORIZED DAMPER MDP MAIN DISTRIBUTION PANEL MED MEDIUM MFR MANUFACTURER MIN MINIMUM MISC MISCELLANEOUS MLO MAIN LUG ONLY MOCP MAXIMUM OVERCURRENT PROTECTION MTD MOUNTED MUA MAKE-UP AIR UNIT N NEUTRAL NC NORMALLY CLOSED NEG NEGATIVE NIC NOT IN CONTRACT NL NIGHT / SECURITY LIGHT - DO NOT SWITCH NO NORMALLY OPEN NOM NOMINAL NTS NOT TO SCALE OA OUTSIDE AIR OBD OPPOSED BLADE DAMPER OC ON CENTER OCC OCCUPIED OCP OVER CURRENT PROTECTION OD OUTSIDE DIAMETER OL OVERLOAD ORD OVERFLOW ROOF DRAIN OZ OUNCE PBD PARALLEL BLADE DAMPER PD PRESSURE DROP PH PHASE POS POSITIVE PRESSURE POS POINT OF SALES PRV PRESSURE REDUCING VALVE PS PRESSURE SWITCH PSI POUNDS PER SQUARE INCH PT PRESSURE TRANSMITTER PTAC PACKAGED TERMINAL AIR CONDITIONER PV PLUG VALVE PVC POLYVINYL CHLORIDE QTY QUANTITY RA RETURN AIR GRILLE / REGISTER RCP REFLECTED CEILING PLAN RD ROOF DRAIN REL RELIEF REQD REQUIRED RF RETURN FAN RH RELATIVE HUMIDITY RHC REHEAT COIL RLA RATED LOAD AMPS RM ROOM RPM REVOLUTIONS PER MINUTE SA SUPPLY AIR GRILLE / REGISTER SC SHORT CIRCUIT SCA SHORT CIRCUIT AVAILABLE SCCR SHORT CIRCUIT CURRENT RATING SCH SCHEDULE SD SMOKE DAMPER SEF SMOKE EXHAUST FAN SF SUPPLY FAN SH SENSIBLE HEAT SH SHOWER SP STATIC PRESSURE SPD SURGE PROTECTION DEVICE SPEC SPECIFICATION SQ SQUARE SS STAINLESS STEEL SS SAFETY SHOWER STD STANDARD STL STEEL SYS SYSTEM TEMP TEMPERATURE TR TRANSFER GRILLE / REGISTER TR TAMPER RESISTANT TT TEMPERATURE TRANSMITTER TTB TELECOMMUNICATIONS TERMINAL BACKBOARD TYP TYPICAL TX TRANSFORMER UC UNDERCUT DOOR UH UNIT HEATER UNO UNLESS NOTED OTHERWISE UNOCC UNOCCUPIED UR URINAL V VOLTS VA VOLT AMPERE VA VALVE VAV VARIABLE AIR VOLUME UNIT VFD VARIABLE FREQUENCY DRIVE VRF VARIABLE REFRIGERANT FLOW VOLT VOLTAGE VTR VENT THROUGH ROOF W WIDTH W WATTS W/ WITH W/O WITHOUT WB WET BULB WC WATER COLUMN WC WATER CLOSET WG WATER GAUGE WP WEATHERPROOF WPIU WEATHERPROOF IN-USE WSR WITHSTAND RATING XFMR TRANSFORMER SUBSTITUTIONS:RESPONSIBLE DIVISION: UNLESS OTHERWISE INDICATED ALL HEATING, VENTILATING, AIR CONDITIONING, PLUMBING, AND OTHER MECHANICAL EQUIPMENT, MOTORS, AND CONTROLS SHALL BE FURNISHED, SET IN PLACE AND WIRED AS FOLLOWS: ITEM FURNISHED SET POWER CONTROL WIRED WIRED EQUIPMENT 23 23 26 -- COMBINATION MAGNETIC MOTOR STARTERS, MAGNETIC MOTOR STARTERS, VFD'S AND CONTACTORS 23(1)26 26(2)23 FUSED AND UNFUSED DISCONNECT SWITCHES, THERMAL OVERLOAD SWITCHES AND HEATERS, MANUAL MOTOR STARTERS 26 26 26 -- MANUAL-OPERATING AND MULTI-SPEED SWITCHES 23 26 26 26 CONTROLS, RELAYS, TRANSFORMERS 23 23 26 23 THERMOSTATS (LOW VOLTAGE) AND TIME SWITCHES 23 23 26 23 THERMOSTATS (LINE VOLTAGE) 23 23 26 26 TEMPERATURE CONTROL PANELS 23 23 26 23 MOTOR AND SOLENOID VALVES, DAMPER MOTORS, PE & EP SWITCHES 23 23(2)--23(2) PUSH-BUTTON STATIONS AND PILOT LIGHTS 23 23(2)-- 23(2) HEATING, COOLING, VENTILATION AND AIR CONDITIONING CONTROLS 23 23 26 23 EXHAUST FAN SWITCHES 23 26 26 23(2) SUBSCRIPT FOOTNOTES: 1.MOTOR STARTER TO INCLUDE CONTROL TRANSFORMER, HOA SWITCH, (1) NO AND (1)NC AUXILIARY CONTACT, AND “ON” AND “OFF” PILOT LIGHTS. 2.IF ITEM IS FOR LINE VOLTAGE, SET IN PLACE AND CONNECT UNDER DIVISION 26. WHERE FACTORY MOUNTED ON EQUIPMENT OR ATTACHED TO PIPING OR DUCTS AND USING LINE VOLTAGE FURNISH AND SET UNDER DIVISION 23, CONNECT UNDER DIVISION 26. ABBREVIATIONS: SECTION THROUGH RETURN DUCT SECTION THROUGH SUPPLY OR OUTSIDE AIR DUCT SUPPLY OR OUTSIDE AIR DUCT ACCESS DOOR (BOTTOM OR SIDE) ACOUSTICALLY LINED DUCT FIRE DAMPER, SMOKE DAMPER, FIRE/SMOKE DAMPER MANUAL VOLUME DAMPER INCLINED DROP IN DIRECTION OF ARROW INCLINED RISE IN DIRECTION OF ARROW TRANSITION, RECTANGULAR TO ROUND FLEXIBLE DUCT IN-LINE FAN TRANSITION, RECTANGULAR SPIN-IN COLLAR INTO ADAPTER ON TOP OF DUCT CEILING SUPPLY AIR REGISTER/GRILLE SIDEWALL SUPPLY AIR REGISTER (SR) ELBOW TURNED DOWN ELBOW TURNED UP ELBOW, RADIUS TYPE ELBOW, SQUARE OR RECTANGULAR TYPE WITH AIRFOIL TURNING VANES CEILING RETURN AIR REGISTER (RR) OPEN END DUCT FLEXIBLE CONNECTION SIDEWALL RETURN AIR REGISTER (RR) VD FXC RR DD PIPE DROPPING DOWN PIPE RISING UP DIRECTION OF FLOW RELIEF/SAFETY VALVE FLOW METER-VENTURI FLOW METER-ORIFICE AUTOMATIC AIR VENT (EXTEND AUTOMATIC FILL VALVE DISCHARGE TO DRAIN) MANUAL AIR VENT CONCENTRIC REDUCER ECCENTRIC REDUCER STEAM LEAK DETECTOR TPV S CBV R D STRAINER MV AV GAS COCK AQUASTAT VB VACUUM BREAKER EXPANSION LOOP GAS PRESSURE STEAM TRAP ANCHOR EJ TT FS TH PT/PS G PRESSURE SWITCH & SYPHON (STEAM) GAUGE COCK TRANSMITTER OR THERMOMETER EXPANSION JOINT TEMPERATURE FLOW SWITCH GUIDE A DIRECTION OF PITCH-RISE OR DROP STRAINER WITH BLOW OFF VALVE UNION - SCREWED OR FLANGED FLOAT OPERATED CO CD T CARBON MONOXIDE CARBON DIOXIDE THERMOSTAT CONTROL VALVE REGULATOR TRANSMITTER PRESSURE GAUGE WITH FSD FIRE SMOKE DAMPER RELIEF VALVE SOLENOID VALVE TEMPERATURE/PRESSURE DIAPHRAGM VALVE BALANCING VALVE BALL VALVE GLOBE VALVE, ANGLE GATE VALVE, ANGLE LIFT CHECK VALVE SWING CHECK VALVE GATE VALVE BUTTERFLY VALVE PLUG VALVE GLOBE VALVE CIRCUIT SETTING BALANCING VALVE THREE WAY CONTROL VALVE TWO WAY CONTROL VALVE PRESSURE REDUCING VALVE (PRV) EXISTING EQUIPMENT OR PIPE TO BE REMOVED. CS CONDENSER WATER SUPPLY CR CONDENSER WATER RETURN R REFRIGERANT LIQUID AND VAPOR LINE RS REFRIGERANT SUCTION / VAPOR HWS HOT WATER SUPPLY HWR HOT WATER RETURN HPS HEAT PUMP SUPPLY HPR HEAT PUMP RETURN V VENT PIPING D DRAIN G NATURAL GAS SMS SNOWMELT SUPPLY SMR SNOWMELT RETURN CHWS CHILLED WATER SUPPLY CHWR CHILLED WATER RETURN LINE DESIGNATION SYMBOLS MECHANICAL ELEMENTS / VALVING SMOKE DAMPER FIRE / SMOKE DAMPERFSD SD RH REFRIGERANT HIGH PRESSURE VAPOR CA COMPRESSED AIR FD - SD - FSD SECTION THROUGH EXHAUST AIR DUCT HX S AIR VENT HYDRAULIC SEPARATOR AIR SEPARATOR HEAT EXCHANGER DIGITAL SENSOR OR PUMP HVAC & DUCTWORK SYMBOLS POINT OF CONNECTION OF NEW TO EXISTING ME C H A N I C A L - CO V E R S H E E T DATE:ISSUED FOR: SHEET NUMBER: February 21, 2025 - 1:02:50pm DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 DATE: CHECKED BY: JOB NO: DRAWN BY: SCALE: TH U N D E R R I V E R M A R K E T 68 1 8 U S - 8 2 BRS/GW MH 02/21/2025 24-305 GL E N W O O D S P R I N G , C O 10/07/2024 DESIGN DEVELOPMENT 02/21/2025 100% CD 3 COMPARTMENT SINK DEEP FRYER HAND WASH SINK PIZZA OVEN HOOD & FIRE SUPPRESSION SYSTEM GRILL DEEP FRYER WOMEN'S RESTROOM MEN'S RESTROOM EXISTING TO REMAIN NO WORK MECHANICAL ROOM COOLER 22 " x 1 6 " MAU 1 16 " Ø 12" Ø 12" Ø 12" Ø 12" Ø 22 " x 1 6 " 22"x16" UP TO MAU-1 EF 1 GH 1 20"X20" UP TO EF-1 18 " Ø DATE:ISSUED FOR: SHEET NUMBER: February 21, 2025 - 1:02:50pm DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 DATE: CHECKED BY: JOB NO: DRAWN BY: SCALE: M1-1 ME C H A N I C A L - FL O O R P L A N TH U N D E R R I V E R M A R K E T 68 1 8 U S - 8 2 GL E N W O O D S P R I N G , C O MECHANICAL - FLOOR PLAN SCALE: NORTH SCALE:1/4" = 1'-0" 10/07/2024 DESIGN DEVELOPMENT BRS/GW MH 02/21/2025 24-305 AS SHOWN MECHANICAL GENERAL NOTES: 1.DRAWING IS DIAGRAMMATIC IN NATURE. LOCATIONS AND SIZES MAY VARY DURING FIELD COORDINATION & INSTALLATION OF MECHANICAL, PLUMBING, & ELECTRICAL. DRAWINGS DO NOT NECESSARILY INDICATE EVERY REQUIRED OFFSET, FITTING, ETC. DRAWINGS ARE NOT TO BE SCALED FOR DIMENSIONS. TAKE ALL DIMENSIONS FROM ARCHITECTURAL DRAWINGS, CERTIFIED EQUIPMENT DRAWINGS AND FROM THE STRUCTURE ITSELF BEFORE FABRICATING ANY WORK, VERIFY ALL SPACE REQUIREMENTS COORDINATING WITH OTHER TRADES, AND INSTALL THE SYSTEMS IN THE SPACE PROVIDED WITHOUT EXTRA CHARGES TO THE OWNER. 2.DUCT DIMENSIONS DO NOT REFLECT ADDITIONAL DIMENSIONS FOR INSULATION. ALL DUCTING SHALL BE INSULATED PER 2021 IECC CODE REQUIREMENTS. (SUPPLY AND RETURN AIR DUCTS AND PLENUMS SHALL BE INSULATED WITH NOT LESS THAN R-6 INSULATION WHERE LOCATED IN UNCONDITIONED SPACES AND WHERE LOCATED OUTSIDE THE BUILDING WITH NOT LESS THAN R-8 INSULATION IN CLIMATE ZONES 0 THROUGH 4 AND NOT LESS THAN R-12 INSULATION IN CLIMATE ZONES 5 THROUGH 8. DUCTS LOCATED UNDERGROUND BENEATH BUILDINGS SHALL BE INSULATED AS REQUIRED IN THIS SECTION OR HAVE AN EQUIVALENT THERMAL DISTRIBUTION EFFICIENCY. WHERE LOCATED WITHIN A BUILDING ENVELOPE ASSEMBLY, THE DUCT OR PLENUM SHALL BE SEPARATED FROM THE BUILDING EXTERIOR OR UNCONDITIONED OR EXEMPT SPACES BY NOT LESS THAN R-8 INSULATION IN CLIMATE ZONES 0 THROUGH 4 AND NOT LESS THAN R-12 INSULATION IN CLIMATE ZONES 5 THROUGH 8. GARFIELD COUNTY IS CLIMATE ZONE 5B) 3.COORDINATE FINAL LOCATION OF THERMOSTAT WITH OWNER PRIOR TO INSTALLATION. IF THERMOSTAT IS LOCATED ON EXTERIOR WALL PROVIDE THERMOSTAT WITH INSULATED BACKING. 4.ALL MOTORIZED DAMPERS ON OUTDOOR AIR INTAKES AND EXHAUST SHALL BE PROVIDED WITH CLASS IA MOTORIZED DAMPERS WITH A MAXIMUM LEAKAGE RATE OF 4 CFM/FT² AT 1.0 INCH WATER GAUGE WHEN TESTED IN ACCORDANCE WITH AMCA 500D. (PER 2021 IECC) 5.MECHANICAL CONTRACTOR SHALL FIELD LOCATE EXISTING DUCTWORK PRIOR TO CONSTRUCTION. MECHANICAL CONTRACTOR SHALL COORDINATE TIE IN CONNECTION POINTS OF NEW SUPPLY DIFFUSERS WITH EXISTING DUCTWORK AS NECESSARY. 6.MECHANICAL EQUIPMENT MANUFACTURERS AS SCHEDULED ON MECHANICAL DRAWINGS ARE SUGGESTED MANUFACTURER'S. UNLESS NOTED OTHERWISE DUE TO OWNER/CLIENT REQUIREMENTS AND PREFERENCES. MECHANICAL CONTRACTOR CAN SUBMIT EQUIVALENT EQUIPMENT FROM MANUFACTURERS THAT DIFFER FROM SCHEDULED MECHANICAL EQUIPMENT. ALTERNATE MANUFACTURERS OF MECHANICAL EQUIPMENT WILL BE REVIEWED FOR EQUIVALENCE OF PERFORMANCE AND FUNCTIONALITY BY ENGINEER. 7.WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A BUILDING SUCH THAT PERSONNEL WILL HAVE TO CLIMB HIGHER THAN 16 FEET ABOVE GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES IN HEIGHT OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL. SUCH ACCESS SHALL NOT REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE PARAPET WALL. PERMANENT LADDERS SHALL COMPLY WITH REQUIREMENTS LISTED IN SECTION 306.5 OF THE 2018 INTERNATIONAL MECHANICAL CODE. 8.CONTRACTOR TO COORDINATE MAKE UP AIR UNIT AND EF LOCATIONS TO MAINTAIN SEPARATIONS FROM EACH OTHER AND ALL OTHER EXISTING ROOF TOP EQUIPMENT ACCORDING TO IMC 501.3 02/21/2025 100% CD DATE:ISSUED FOR: SHEET NUMBER: February 21, 2025 - 1:02:50pm DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 DATE: CHECKED BY: JOB NO: DRAWN BY: SCALE: M3-1 ME C H A N I C A L - DE T A I L S TH U N D E R R I V E R M A R K E T 68 1 8 U S - 8 2 BRS/GW MH 02/21/2025 24-305 GL E N W O O D S P R I N G , C O 10/07/2024 DESIGN DEVELOPMENT OUTDOOR GAS FIRED MAKE-UP AIR UNIT SCHEDULE EQUIPMENT NO.SERVICE SUPPLY AIR (CFM)EXTERNAL STATIC PRESS. (IN. W.G.)INPUT (MBH)OUTPUT (MBH)EFFICIENCY A.F.U.E. GAS RATE (CFH) ELECTRIC MANUFACTURER & MODEL OPTIONS/ACCESSORIES HP V/PH/HZ MCA (A)MOP (A) MAU-1 KITCHEN 2656 0.26 145.3 133.7 92%180.7 1 208/1/60 8.3 15 GREENHECK DGX-P112-H12-MF (OR EQUIVALENT)NOTE-1 NOTE: 1. PROVIDE HIGH ALTITUDE KIT SIZED PER LOCATION ELEVATION. CORRDINATE FAN CONTROLS WITH EF AND KITCHEN HOOD. EXHAUST FAN SCHEDULE EQUIPMENT NO.SERVICE LOCATION CFM EXTERNAL STATIC PRESS (IN. W.G.) MOTOR MANUFACTURER & MODEL OPTIONS/ACCESSORIES WATTS HP RPM VOLT/PH/HZ FLA EF-1 KITCHEN HOOD ROOF 2,944 0.925 1471.00 2.00 1397 208/1/60 13.2 GREENHECK CUE-160-VG (OR EQUIVALENT)NOTE-1 NOTES: 1. PROVIDE WITH MOTOR STARTER, POWER DISCONNECT, AND DIRECT DRIVEN MOTOR WITH SPEED CONTROLLER. COORDINATE FAN CONTROLS WITH MAU AND KITCHEN HOOD. SUPPLY PLENUM INFORMATION POS.HOOD NO.MARK TYPEL COLLARS W L DIA.CFMINSULATEDDAMPER(S)VEL. LED LIGHT(S) W H SIZE (IN.)TYPE MOUNTING QTYQTYSUPPLIED TOTAL CFM TOTAL S.P. 1 GH-1 FRONT MUA 12 26 5890.01 272FACTORY278NOYESNO144ASP1178 2 GH-1 FRONT MUA 12 26 5890.01 272FACTORY278NOYESNO144ASP1178 MODEL LENGTH WIDTH HEIGHT HOOD DIMENSIONS (IN.) MARK WIDTH LENGTH DIA.CFM S.P. COLLAR(S) EXHAUST HOOD INFORMATION HOOD NO. COOKING LOAD / DUTY RATING HOOD CONSTR.MUA CFM AC CFM HANGING WEIGHT LBS. SECTION LOCATIONTOTAL CFM SUPPLY 9 16 0.675166317848 LEFT24GXEW-78-S GH-1 1663 1178 272HEAVY 430 SS WHERE EXPOSED 10 12 0.487128127848 RIGHT24GXEW-78-S GH-1 1281 1178 272HEAVY 430 SS WHERE EXPOSED LIGHTING DETAILS QTY L GREASE FILTRATION DETAILS QTY H LOCATION UTILITY CABINET(S) CONTROLS HOOD INFORMATION MARK FIXTURE TYPE BULB / LAMP INFO FOOT CANDLES TYPE / MODEL MATERIAL SIZE (IN.)HOOD NO.FIRE SYSTEM MODELTYPESIZE INTERFACE 46.14 3 201 20 161INCANDESCENT (GLOBE) 100W A19 (BULBS NOT INCL.) X-TRACTOR (SPARK ARRESTOR INCL.) STAINLESS STEEL GH-1 4 46.14 3 201 20 162INCANDESCENT (GLOBE) 100W A19 (BULBS NOT INCL.) X-TRACTOR (SPARK ARRESTOR INCL.) STAINLESS STEEL GH-1 4 HOOD OPTIONS UL 710 LISTED W/ OUT EXHAUST FIRE DAMPER - UL #MH11726 HOOD TOP INSULATED FOR ZERO CLEARANCE TO COMBUSTIBLES BACK INTEGRAL AIR SPACE - 3 IN WIDE CONTINUOUS CAPTURE FACTORY MOUNTED EXHAUST COLLAR(S) PERFORMANCE ENHANCING LIP (PEL) TECHNOLOGY STANDING SEAM CONSTRUCTION FOR SUPERIOR STRENGTH MECHANICAL PROVISIONS: 1. SCOPE OF WORK A.THE CONTRACTOR IS RESPONSIBLE FOR ALL WORK, MATERIALS, AND LABOR TO SATISFY A COMPLETE WORKING SYSTEM WHETHER SPECIFIED OR IMPLIED. B.ALL WORK IS TO BE PERFORMED IN STRICT COMPLIANCE WITH ALL LOCAL CODES AND ALL OTHER REGULATION GOVERNING WORK OF THIS NATURE. C.THE CONTRACTOR SHALL, BEFORE SUBMITTING ANY PROPOSAL, EXAMINE THE PROPOSED SITE AND SHALL DETERMINE FOR HIMSELF THE CONDITIONS THAT MAY EFFECT THE WORK. NO ALLOWANCE SHALL BE MADE IF THE CONTRACTOR FAILS TO MAKE SUCH EXAMINATIONS. D.ALL EQUIPMENT AND MATERIALS SHALL BE AS SPECIFIED OR "APPROVED EQUAL" BY THE ENGINEER OR ARCHITECT. 2. PERMITS A.THE CONTRACTOR SHALL SECURE ALL PERMITS OR APPLICATIONS AND PAY ANY AND ALL FEES. 3. SHOP DRAWINGS A.SUBMIT MATERIAL LIST AND SHOP DRAWINGS FOR MAJOR EQUIPMENT TO THE ARCHITECT/ENGINEER FOR APPROVAL. THE CONTRACTOR SHALL SUBMIT FIVE SETS OF SHOP DRAWINGS AND THEY SHALL BE CLEARLY LABELED. 4. FLEXIBLE DUCT WORK A.FLEXIBLE TYPE DUCT SHALL BE OF TWO ELEMENT SPIRAL CONSTRUCTION COMPOSED OF A CORROSION RESISTANT METAL SUPPORTING SPIRAL AND COATED FABRIC WITH A MINERAL BASE. FLEXIBLE DUCT CONNECTORS SHALL BE LISTED BY U.L., CLASS 1 DUCTS, AND SHALL HAVE A FLAME SPREAD RATING NOT EXCEEDING 25 AND A SMOKE DEVELOPED RATING NOT EXCEEDING 50. B.USE OF FLEXIBLE DUCTWORK SHALL BE LIMITED TO NO MORE THAN 6 LINEAR FEET PER RUN. C.CONTRACTOR SHALL BE CAREFUL SO AS NOT TO KINK OR COLLAPSE FLEXIBLE DUCT. 5. REFRIGERANT A. PIPING CONTRACTOR SHALL PROVIDE AND INSTALL REFRIGERANT PIPING IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND IN SUCH A WAY AS TO BE INCONSPICUOUS AND FREE FROM ANY POSSIBLE CONDENSATION. B. INSULATE REFRIGERANT LINES WITH ARMOUR-FLEX TYPE INSULATION, SHALL BE TYPE "K" COPPER TUBING, WITH WROUGHT COPPER SOLDER TYPE FITTINGS SUITABLE FOR CONNECTION WITH SILVER SOLDER. 6. DUCTWORK A.THE DUCTWORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE "SMACNA" APPLICABLE MANUALS. B.ALL DUCTWORK SHALL BE THE LOW VELOCITY TYPE, UNLESS SPECIFIED OTHERWISE. C.CONTRACTOR SHALL PROVIDE AND INSTALL APPROVED FIRE DAMPERS AND ACCESS PANELS IN ANY AND ALL DUCTWORK WHICH PENETRATES A HORIZONTAL OR VERTICAL FIRE PARTITION, OR AS OTHERWISE SHOWN ON DRAWINGS. D.ALL BRANCH DUCTS TO HAVE VOLUME DAMPERS, SMOOTH TURN RADIUS DUCTWORK OR TURNING VANES SHALL BE USED THROUGHOUT WHERE FLOW EXCEEDS 150 CFM. E.ALL DUCT JOINTS TO BE SEALED IN ACCORDANCE WITH "SMACNA"STANDARDS AND ACCEPTED GOOD PRACTICE. F.ALL DUCT DIMENSIONS SHOWN ARE NET INSIDE VALUES.DIMENSIONS MAY BE CHANGED SO LONG AS THE NET FREE FACE AREA IS MAINTAINED. G.ALL CONCEALED DUCTWORK SHALL BE INSULATED WITH 1-1/2" FIBERGLASS INSULATING BLANKET WITH ALUMINUM FOIL FACING. H.ALL SUPPLY AND RETURN DUCTWORK 15 FEET DOWNSTREAM OF THE HVAC UNIT SHALL BE INTERNALLY LINED WITH A 1/2" ACOUSTICAL DUCT LINER UNLESS OTHERWISE NOTED ON THE DRAWINGS. 7. DRAINAGE PIPING A.(CONDENSATE) SHALL BE SCHEDULE 40 PVC PIPE WITH SOLVENT JOINTS.PITCH HORIZONTAL LINES 1" IN 10'-0". CONDENSATE DRAINS SHALL BE ROUTED TO FLOOR DRAIN, ROOF DRAIN OR INDIRECT WASTE DRAIN. 8. HVAC CONTROLS A.CONTRACTOR TO SUPPLY AND INSTALL ALL CONTROL WIRING AND THERMOSTATS AS REQUIRED. 9. ELECTRICAL A.CONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR LOCATION OF WIRING FOR EACH HVAC UNIT. 10. PIPE SUPPORTS A.ALL PIPE SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE IN A NEAT AND WORKMANLIKE MANNER. THE USE OF WIRE OR METAL STRAP TOSUPPORT PIPES WILL NOT BE PERMITTED. SPACING OF PIPE SUPPORTS SHALL NOT EXCEED 8 FEET FOR ALL PIPING. PLASTIC PIPING TO BE SUPPORTED EVERY 4 FEET. 11. GAS PIPING A.PIPING SHALL BE SCHEDULE 40 BLACK STEEL PIPE WITH MALLEABLE IRON FITTINGS. WHERE GAS PIPE CONNECTS TO EQUIPMENT, IT SHALL BE PROVIDED WITH A DRIP LEG THE FULL SIZE OF THE RUNOUT, A 100% SHUT-OFF VALVE AND A UNION. GAS PIPING CONTAINING PRESSURE GREATER THAN 9" W.G. SHALL BE SCHEDULE 40 BLACK STEEL PIPE WITH WELDED JOINTS. 12. MISCELLANEOUS A.ALL EXTERIOR OPENINGS TO BE PROPERLY CAULKED AND SEALED WITH A SEALANT OF HIGH QUALITY AND LONG LIFE, TO PREVENT INFILTRATION OF OUTSIDE AIR INTO CONDITIONED SPACE.COORDINATE INSTALLATION OF ALL ROOF FLASHING AT ROOF PENETRATION. B.DO NOT SCALE THIS DRAWING FOR EXACT DIMENSIONS. C.VERIFY ALL FIGURES, CONDITIONS, AND DIMENSIONS AT THE JOB SITE. D.THE MECHANICAL PLANS ARE INTENDED TO BE DIAGRAMMATIC AND ARE BASED ON ONE MANUFACTURE'S EQUIPMENT. THEY ARE NOT INTENDED TO SHOW EVERY ITEM IN ITS EXACT LOCATION, THE EXACT DIMENSIONS, OR ALL THE DETAILS OF THE EQUIPMENT. E.THE CONTRACTOR SHALL VERIFY THE ACTUAL DIMENSIONS OF THE EQUIPMENT PROPOSED TO ENSURE THAT THE EQUIPMENT WILL FIT IN THE AVAILABLE SPACE. F.PEX TUBING, IF PEX TUBING IS USED AS AN APPROVED ALTERNATE FOR APPLICATIONS WHERE METALLIC PIPING IS THE BASIS OF DESIGN. THE PEX MANUFACTURER SHALL SUBMIT SHOP DRAWINGS CLEARLY INDICATING THAT THE DESIGN HAS BEEN ANALYZED AND MODIFIED, AS REQUIRED TO MAINTAIN SCHEDULED HYDRONIC SYSTEM PARAMETERS. ANY DESIGN RESULTING IN INCREASED SYSTEM PRESSURE DROP AS A RESULT OF IMPROPER PEX SIZING OR DESIGN SHALL NOT BE PERMITTED. 13. TESTING AND BALANCING A.THE HVAC SYSTEM SHALL BE TESTED AND AND BALANCED BY AN INDEPENDENT AGENCY, UNDER THE SUPERVISION OF A LICENSED PROFESSIONAL ENGINEER. A SEALED TYPE WRITTEN REPORT SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER FOR REVIEW AND APPROVAL. 14. GUARANTEE A.MATERIALS, EQUIPMENT AND INSTALLATION SHALL BE GUARANTEED FOR A PERIOD OF ONE(1) YEAR FROM DATE OF ACCEPTANCE. DEFECTS WHICH APPEAR DURING THAT PERIOD SHALL BE CORRECTED AT THIS CONTRACTOR'S EXPENSE. B.FOR THE SAME PERIOD, THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO PREMISES CAUSED BY DEFECTS IN WORKMANSHIP OR IN THE WORK OR EQUIPMENT FURNISHED AND/OR INSTALLED BY HIM. KITCHEN APPLIANCES GENERAL NOTES: 1.INSTALL GREASE DUCT PER IMC CODE. INSULATE GREASE DUCT PER IMC CODE. GREASE DUCT TO MAINTAIN MINIMUM CLEARANCES TO COMBUSTIBLES PER IMC CODE. 2.CLEANOUTS SHALL BE LOCATED ON BOTTOM ONLY WHERE OTHER LOCATIONS ARE NOT AVAILABLE AND SHALL BE PROVIDED WITH INTERNAL DAMMING OF THE OPENING SUCH THAT GREASE WILL FLOW PAST THE OPENING WITHOUT POOLING. BOTTOM CLEANOUTS AND OPENINGS SHALL BE APPROVED FOR THE APPLICATION AND INSTALLED LIQUID-TIGHT. 3.CLEANOUTS ON OF DUCT SHALL HAVE DIMENSIONS NO LESS THAN 12"X12". CLEANOUTS SHALL BE LARGE ENOUGH TO PROVIDE ACCESS FOR CLEANING AND MAINTENANCE. 4.DUCTWORK FOR THIS PROJECT SHALL BE UL 1978 LISTED. PREFERRED DUCTWORK MAKE/MODEL SHALL BE SELKIRK: ZeroClear Z3. CONTRACTOR SHALL INSTALL ALL GREASE DUCTWORK PER MANUFACTURERS INSTALLATION INSTRUCTIONS. TO MAU ROOF FLOOR KITCHEN HOOD NOT TO SCALE GREASE DUCT, HOOD, EXHAUST FAN DETAIL 10' MIN. KITCHEN HOOD SUPPLIED SHALL HAVE INSULATION TO MAINTAIN MINIMUM CLEARANCES TO COMBUSTIBLES. PROVIDED FROM MANUFACTURER FOR FRONT, BACK, TOP, AND SIDES. CONTRACTOR SHALL INSTALL PER MANUFACTURER'S INSTRUCTIONS TO MAINTAIN UL LISTING. CEILING UTILITY UPBLAST GREASE EXHAUST FAN PROVIDE WITH: -REMOVABLE GREASE CUP -BELT DRIVEN -UL 762 LISTING -POWER DISCONNECT -VENTED CURB -HINGED CURB -STAINLESS STEEL -MOTOR STARTER -INTERLOCK WITH KITCHEN HOOD & MAKE UP AIR UNIT KITCHEN HOOD TO BE INSTALLED PER MANUFACTURERS INSTRUCTIONS. ALL CLEARANCES SHALL BE FIELD COORDINATED TO MAINTAIN UL LISTINGS. KITCHEN HOOD SHALL BE INSTALLED PER IMC/IFGC CODE REQUIREMENTS. 40 " M I N . MAU MAKE-UP AIR UNIT 100% OUTSIDE AIR 100% OUTSIDE AIR INLET HOOD BLOWER SECTION FURNACE SECTION FLUE CONDITIONED SUPPLY AIR VIBRATION ISOLATION ROOF CURB ROOF MAKE-UP AIR UNIT MOUNTED AT ROOF NOT TO SCALE EVAP SECTION 02/21/2025 100% CD MoTak MGF4-P-C Gas Fryer- (1) s0 rb Vat, Floor Moder, Liquid propane Read { rcvrss KaTorn t;89S.cGF4Lp. Uel: U6ffbo .=;* .^..:. "ai:' ii i tt Thank you for vbiting KaTom. What are you looking for today? a - s lN STOCK: Shlpr ln 1 Buslnest Day @ to0+ in stock Selected Gas Type: Llqurd profrne I Naturalcss @ UquidPropane MoTak MGF4-P-C Description oil and ruining food llavor. ecessed handle eases opening. To make il easier for you to position and reposition this item in your commercila kitchen, it come with four casters. Product Details . 50-lb. tank cspacity. (4) 30,000€TU heattubes. Temperature range: 20F400 degrees F. Autorcsct, highlimft swhch helps prwent overheating r Peened, stainless steel tank has smodrd |velds to facilitale cleaning. Cold zone is not heated to lhe same temperature as the rest of the tank enabling sediment to settle withoui buming in the oil. 2 nickel chrome wire baskets have red, plastic-coated handles . Doubl+rod, stalnless steel hanger provides draining space for food ln baskets. Stainless steeldoor has an integrated llnerro simplify cleanlng . Welded door magnet seals the door shut. Recessed door handle saves space. Slainless steel front top ledge, and header provide strenglh and rust re$istance . Galvanized steel sides and backwithstand heavy use . Casters .120,0008TU . Not suitable fc rcgldcotlal or othsr non-commerclal sse Dimensions & Utilities . 15.5 in. W r 30.3 in. D x 53.2 in. H . HeatedbyLPgas Product Features Stainless Steel Construction Resists rusting and High-limit Safety Switch Prevents overheating lnsulated Basket Handles Reduce risk of bums Gasters Mobile for convenient maintenance and cleaning FREE CASTERS INCLUDED W ITH PURCHASE From The Manufacturer hanger. built in flue dellecto( ball type full port drain, 3/4' NPT male gas connection ln rear, stainless steel lronl galvanized sides & back, casters, 1 20,000 BTU *tmage may not depicl product colot inclusions or accessories. Resources m Commercral Deep Fryer lerms Conftlly Srzing Your Commcrcial Fr)€r '18 month parts & labor MCTAK MoTak MGF4-P€ Specifi cations Manufacturer Baskets C"p",*V frbt GasType Number of Fry Pots Type Wananty wia*r A"i-- Oil Capacity/Fryer 0b) Frypot Style tuType BTU per F4ar Number of Tubes Product Producl Type Weight MoTak 2 50 t"P I Roor Model 18 month parts & labor 15.5 50 TubeType Breaded r20000 I GTIry.. Coold.nS ECllgent 183.00 Documents Sp6 Snd Wrrry M$od producl failure or any damages/injuries. PDF PDFPDF Hood Builders lnc. 5925 E Evans Ave Suite 215 DENVER, CO 80222 +-13037777720 mai n.hoodbuilder@gmail.com z#{*.*- ]IoOdBUILDER Estimate family of Nationwide cornpanies ADDRESS THUNDER NVCN MARKET 6818 CO-82 GLENWOOD SPRINGS co 81601 NATHAN 719-415-7278 NATHANJARELLANO@GMAr L.COM zAcH@TCFUELS.COM DATE . SHIPTO THUNDER RIVER MARKET 6818 CO-82 GLENWOOD SPRINGS co 81601 NATHAN 719-415-7278 NATHANJAR ELLANO@GMAtL.COM ZACH@TCFUELS.COM QTY RATE 35,930.00Furnish Exhaust Fan, NFPA 1 9,500.00 5,000.00 3,630.00 2,000.00 550.00 '1 850.00 p$- E$TIMATE # HB82739A EXPIRATION DATE .Q4'" SALES REP JOEL - 720-372-6729 ITEM # HB1.) HOOD, EXHAUST FAN, AND MAU PACKAGE HB2.) DUCTWORK HB3.) F|RE SUPPRESSION INSTALLATION HB4.) ELECTRTCAL INTERLOCKING HB5.) ENGTNEERTNG DRAWINGS AND PERMIT PROCESS HB6.) ROOFTNG HB7.) FrRE WRAP 02/19t2025 ,0311912025 DESCRIPTION Hoods, Exhaust Fans, and a MAU and install 13' x 4' Stainless Steel and a Heated Make Up Air Unit. (U complaint) Furnish and lnstall 1 Work, MUA Duct work,2 flat pieces, straight path to the ffirturn!, Furnish and lnstall Complete UL300 Compliant Fire Suppression System lnstallation Chemical Bottle, Control Head, CO2, Pull Station, Chemical Line, and Fusible Link line Furnish and installControl Panel. Electrical Connections for Hood, MAU, Microswitch Assembly, and all safety interlocks per NFPA and UL sequence requirement (Not including the wiring to the units and the Electrical Panel). Mechanical, Electrical, and Fire System Drawings including Permitting Process will be done by Customer and the inspections will be done by Contractor. Roof penetration and Roof patch (cold Patch) for ducts penetration point. Furnish and install Two layers of Fire Wrap for the Grease Ducts. Removal of existing 6'type 2 hood. 5 Sheets of stainless steelallflashing installed behind the hood. Provided by the customer. 1 .00 .00 ,540 ,990 B1 1 AMOUNT 35,930.00 18,540.00 1 1,990.00 5,500.CI0 9,500.00 5,000.00 3,630.00 2,000.00 2,750.00 1 5,500.00 DEMO HB8.) STATNLESS STEEL WALL FLASHING AUTOMATIC GAS VALVE SHUT OFF 5 Furnish and install the automatic gas shut off valve a 850.00 Notes:This bid pertains to the items listed above only. This bid is pending local authority's approval. AII additional work will be at extra cost.lTEMS NOT INCLUDED UNLESS LISTED ABOVE:Wall Flashing ($), Skirring (g), cas Piping, Air Balancing, Automatic Gas Shut-off Valve:up to 1.5 inch: (9750), Structural Engineering, Electrical Drawings, Electrical wiring and connections to the Exhaust Fan, MAU, Lights, Outlets and Microswitch Assembly, Other Electrical, and Alarm. Asbestos testing and/or removal, any structural work or penetration of walls, and repair of walls and ceilings. All drawings, Taxes, Permit Fees, and all other fees.This bid is based on work being performed 8- hours during daylight, Monday-Friday unless we decide othenarise.Customer must always provide proper and safe access to the work area.Customer.must provide proper toilet facilities for our workers. Terms: 50% down, 25/" due upon equipment delivery, 20o/o due upon rough inspection,and 5% due at final. Accepted By TOTAL Accepted Date $95,690.00 I I THUNDER RIVER MARKET KITCHEN LAYOUT COOL€R I t I I I ,{ 1 I .--,-{6:.t: 56 I I j \. -,^ "i \' ii t--- -.' ' THUNDER RIVER MARKET 6818 CO-82 GLENWOOD SPRINGS co 81601 DELI FLOOR PLAN SCALE-1/8"=1' -)t ,J9 I I -.1 ,| ,1 --i --., 3 COMPARTMENT SINK HAND WASH SINK PIZZAOVEN ',;o.rxHnusr reN EXISTING KITCHEN EQUIPMENT THUNDER RIVER MARKET 6818 CO-82 GLENWOOD SPRINGS CO 81601 DELI FLOOR PLAN SCALE -3132" = 1' I l *t-.. )_"-. ___-__+. '1. l I F.l -l i4j ,i ll 't - 12'HOOD & F|RE i:jSUPPRESS|ON SYSTEM PROPOSED KITCHEN EQUIPMENT THUNDER RIVER MARKET 6818 CO-82 GLENWOOD SPRINGS CO 81601 DELI FLOOR PLAN SCALE -3132" = 1' \. -t . .- -/--.,. !