A.SUBSTITUTIONS: SUBSTITUTION OF SPECIFIED EQUIPMENT WILL BE ALLOWED
THROUGH A PRIOR APPROVAL PROCESS INITIATED BY THE CONTRACTOR.
CONTRACTOR SHALL SUBMIT INTENDED SUBSTITUTION AT LEAST FIVE DAYS
PRIOR TO BID FOR APPROVAL FROM ENGINEER. SUBMITTAL SHALL INCLUDE
CAPACITIES, DIMENSIONS AND OPERATING INSTRUCTIONS FOR EACH PIECE OF
EQUIPMENT. SUBSTITUTION SHALL OCCUR AT NO COST TO THE OWNER.
CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF APPROVED SUBSTITUTION
AND SHALL INCUR ALL COSTS ASSOCIATED WITH THE SUBSTITUTION INCLUDING
STRUCTURAL MODIFICATIONS, SPACE LAYOUT AND REDESIGN COSTS. SEE ALSO
DIVISION I GENERAL REQUIREMENTS.
EXAMINATION OF SITE, DRAWINGS, SPECIFICATIONS:
A.EXAMINE CAREFULLY THE SITE AND CONDITIONS OF THE SITE. PROVIDE ALL
NECESSARY EQUIPMENT AND LABOR TO INSTALL A COMPLETE WORKING SYSTEM
WITHIN THE SITE CONDITIONS.
B.EXAMINE THE DRAWINGS AND SPECIFICATIONS AND 5 DAYS PRIOR TO
BIDDING REPORT ANY ERRORS, OMISSIONS, INCONSISTENCIES, AND CONFLICTS
TO THE ENGINEER TO BE REMEDIED IN AN ADDENDUM TO THE PROJECT PRIOR TO
BID TIME.
C.DRAWINGS ARE DIAGRAMMATIC AND CATALOG NUMBERS GIVEN ARE FOR
REFERENCE ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING
THE CAPACITY OF THE EQUIPMENT MEETS THE DRAWING REQUIREMENTS AND
SHALL NOT DIMENSION FROM THE MECHANICAL, PLUMBING, OR PIPING
DRAWINGS.
D.THE LATEST ADOPTED VERSIONS OF THE INTERNATIONAL BUILDING CODES
SHALL BE USED AS REQUIRED. THIS WILL ALSO INCLUDE THE LATEST ADOPTED
VERSIONS OF THE MECHANICAL, PLUMBING, AND ENERGY CONSERVATION
CODES. ALL METHODS AND MATERIALS REQUIRED BY THESE CODES SHALL BE
REQUIRED BY THESE SPECIFICATIONS UNLESS INDICATED OTHERWISE. OTHER
APPLICABLE LOCAL CODES AND ORDINANCES SHALL BE AS REQUIRED AND IT
SHALL BE THE CONTRACTOR’S RESPONSIBILITY TO BE KNOWLEDGEABLE OF
THESE REQUIREMENTS.
E.WHERE INSTALLATION PROCEDURES OR ANY PART THEREOF ARE REQUIRED
TO BE IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE MANUFACTURER
OF THE MATERIAL BEING INSTALLED, PRINTED COPIES OF THESE
RECOMMENDATIONS SHALL BE FURNISHED TO THE ENGINEER PRIOR TO
INSTALLATION. INSTALLATION OF THE ITEM WILL NOT BE ALLOWED TO PROCEED
UNTIL THE RECOMMENDATIONS ARE RECEIVED. FAILURE TO FURNISH THESE
RECOMMENDATIONS CAN BE CAUSE FOR REJECTION OF THE MATERIAL.
44”MOUNTING HEIGHT ABOVE
FINISHED FLOOR TO CENTER OF DEVICE
A AMPS
A.D.ACCESS DOOR
AAV AIR ADMITTANCE VALVE
ABV ABOVE
AC AIR CONDITIONING UNIT
AC ABOVE COUNTER
AD AREA DRAIN (SEE SYMBOLS)
A.F.C.ABOVE FINISHED CEILING
A.F.G.ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING
CAPACITY
AFCI ARC FAULT CIRCUIT
INTERRUPTERS
A.F.F.ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALUM ALUMINUM
AP ACCESS PANEL OR DOOR
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO / VIDEO
AVG AVERAGE
AWG AMERICAN WIRE GAGE
BAS BUILDING AUTOMATION SYSTEM
BB BASEBOARD
BD BACK DRAFT DAMPER
BFP BACK FLOW PREVENTOR
BL BOILER
BLDG BUILDING
BLW BELOW
BOB BOTTOM OF BEAM
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BSMT BASEMENT
BTU BRITISH THERMAL UNIT
C CHILLER
CAFCI COMBINATION ARC FAULT
CIRCUIT INTERRUPTERS
CAP CAPACITY
CB CIRCUIT BREAKER
CBV CIRCUIT BALANCING VALVE
CCT CORRELATED COLOR
TEMPERATURE
CKT CIRCUIT
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CI CAST IRON
CL CENTER LINE
CLG CEILING
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
COMP COMPRESSOR
CONC CONCRETE
COND CONDENSATE
CONN CONNECTION
CONT CONTINUATION
CONTR CONTRACTOR
CRI COLOR RENDERING INDEX
CT COOLING TOWER
CT CURRENT TRANSFORMER
CU CONDENSING UNIT
CU COPPER
CUH CABINET UNIT HEATER
CVB CONSTANT VOLUME BOX
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
DB DRY BULB
DEPT DEPARTMENT
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGRAM
DIFF DIFFERENTIAL
DISCH DISCHARGE
DIV DIVISION
DN DOWN
DS DUCT SILENCER
DWG DRAWING
DX DIRECT EXPANSION
(E) EXISTING
EA EXHAUST AIR GRILLE/REGISTER
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
ECC ECCENTRIC
EF EXHAUST FAN
EFF EFFICIENCY
EL ELEVATION
ELEC ELECTRIC
ELEV ELEVATOR
EM EMERGENCY FUNCTION
ENT ENTERING
EMT ELECTRIC METALLIC TUBE
EQ EQUAL
EQUIP EQUIPMENT
EQUIV EQUIVALENT
ES END SWITCH
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER
TEMPERATURE
EX EXHAUST
EXPAN EXPANSION
EXT EXTERNAL
F DEGREES FAHRENHEIT
FA FREE AREA
FC FAN COIL UNIT
FC FOOTCANDLE
FCV FLOW CONTROL VALVE
FD FIRE DAMPER
FD FLOOR DRAIN
FIN FINISHED
FLA FULL LOAD AMPS
FLEX FLEXIBLE
FLR FLOOR
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FP FIRE PROTECTION
FP FIRE PUMP
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOW SWITCH
FSD FIRE/SMOKE DAMPER
FT FEET
FXC FLEXIBLE CONNECTION
GND GROUND
GA GAUGE
GAL GALLON
GALV GALVANIZED
GEC GROUND ELECTRODE
CONDUCTOR
GFCI / GFI GROUND FAULT CIRCUIT
INTERRUPTER
GC GENERAL CONTRACTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GRS/LB GRAINS PER POUND
H 2O WATER
HB HOSE BIBB
HD HEAD (SEE SCHEDULES)
HP HEAT PUMP
HP HORSEPOWER
HR HOUR
HT HEIGHT
HTR HEATER
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HX HEAT EXCHANGER
HZ HERTZ
ID INSIDE DIAMETER
IG ISOLATED GROUND
IN INCHES
INV INVERT
JBOX JUNCTION BOX
K KELVIN
KW KILOWATT
KVA KILO VOLT - AMPS
L LENGTH
LAT LEAVING AIR TEMPERATURE
LV LAVATORY
LB POUND
LD LINEAR DIFFUSER
LF LINEAR FEET
LIN LINEAR
LIQ LIQUID
LM LUMEN
LRA LOCKED ROTOR AMPS
LV LOUVER
LVG LEAVING
LWT LEAVING WATER TEMPERATURE
MBH THOUSANDS OF BTU PER HOUR
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MD MOTORIZED DAMPER
MDP MAIN DISTRIBUTION PANEL
MED MEDIUM
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUG ONLY
MOCP MAXIMUM OVERCURRENT
PROTECTION
MTD MOUNTED
MUA MAKE-UP AIR UNIT
N NEUTRAL
NC NORMALLY CLOSED
NEG NEGATIVE
NIC NOT IN CONTRACT
NL NIGHT / SECURITY LIGHT - DO
NOT SWITCH
NO NORMALLY OPEN
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
OC ON CENTER
OCC OCCUPIED
OCP OVER CURRENT PROTECTION
OD OUTSIDE DIAMETER
OL OVERLOAD
ORD OVERFLOW ROOF DRAIN
OZ OUNCE
PBD PARALLEL BLADE DAMPER
PD PRESSURE DROP
PH PHASE
POS POSITIVE PRESSURE
POS POINT OF SALES
PRV PRESSURE REDUCING VALVE
PS PRESSURE SWITCH
PSI POUNDS PER SQUARE INCH
PT PRESSURE TRANSMITTER
PTAC PACKAGED TERMINAL AIR
CONDITIONER
PV PLUG VALVE
PVC POLYVINYL CHLORIDE
QTY QUANTITY
RA RETURN AIR GRILLE / REGISTER
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REL RELIEF
REQD REQUIRED
RF RETURN FAN
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RLA RATED LOAD AMPS
RM ROOM
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR GRILLE / REGISTER
SC SHORT CIRCUIT
SCA SHORT CIRCUIT AVAILABLE
SCCR SHORT CIRCUIT CURRENT
RATING
SCH SCHEDULE
SD SMOKE DAMPER
SEF SMOKE EXHAUST FAN
SF SUPPLY FAN
SH SENSIBLE HEAT
SH SHOWER
SP STATIC PRESSURE
SPD SURGE PROTECTION DEVICE
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STEEL
SS SAFETY SHOWER
STD STANDARD
STL STEEL
SYS SYSTEM
TEMP TEMPERATURE
TR TRANSFER GRILLE / REGISTER
TR TAMPER RESISTANT
TT TEMPERATURE TRANSMITTER
TTB TELECOMMUNICATIONS
TERMINAL BACKBOARD
TYP TYPICAL
TX TRANSFORMER
UC UNDERCUT DOOR
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UNOCC UNOCCUPIED
UR URINAL
V VOLTS
VA VOLT AMPERE
VA VALVE
VAV VARIABLE AIR VOLUME UNIT
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
VOLT VOLTAGE
VTR VENT THROUGH ROOF
W WIDTH
W WATTS
W/ WITH
W/O WITHOUT
WB WET BULB
WC WATER COLUMN
WC WATER CLOSET
WG WATER GAUGE
WP WEATHERPROOF
WPIU WEATHERPROOF IN-USE
WSR WITHSTAND RATING
XFMR TRANSFORMER
SUBSTITUTIONS:RESPONSIBLE DIVISION:
UNLESS OTHERWISE INDICATED ALL HEATING, VENTILATING, AIR CONDITIONING, PLUMBING,
AND OTHER MECHANICAL EQUIPMENT, MOTORS, AND CONTROLS SHALL BE FURNISHED, SET
IN PLACE AND WIRED AS FOLLOWS:
ITEM FURNISHED SET POWER CONTROL
WIRED WIRED
EQUIPMENT 23 23 26 --
COMBINATION MAGNETIC
MOTOR STARTERS, MAGNETIC
MOTOR STARTERS, VFD'S AND
CONTACTORS 23(1)26 26(2)23
FUSED AND UNFUSED
DISCONNECT SWITCHES,
THERMAL OVERLOAD SWITCHES
AND HEATERS, MANUAL MOTOR
STARTERS 26 26 26 --
MANUAL-OPERATING AND
MULTI-SPEED SWITCHES 23 26 26 26
CONTROLS, RELAYS,
TRANSFORMERS 23 23 26 23
THERMOSTATS (LOW VOLTAGE)
AND TIME SWITCHES 23 23 26 23
THERMOSTATS (LINE VOLTAGE) 23 23 26 26
TEMPERATURE CONTROL PANELS 23 23 26 23
MOTOR AND SOLENOID VALVES,
DAMPER MOTORS, PE & EP
SWITCHES 23 23(2)--23(2)
PUSH-BUTTON STATIONS
AND PILOT LIGHTS 23 23(2)-- 23(2)
HEATING, COOLING,
VENTILATION AND AIR
CONDITIONING CONTROLS 23 23 26 23
EXHAUST FAN SWITCHES 23 26 26 23(2)
SUBSCRIPT FOOTNOTES:
1.MOTOR STARTER TO INCLUDE CONTROL TRANSFORMER, HOA SWITCH, (1) NO AND (1)NC
AUXILIARY CONTACT, AND “ON” AND “OFF” PILOT LIGHTS.
2.IF ITEM IS FOR LINE VOLTAGE, SET IN PLACE AND CONNECT UNDER DIVISION 26. WHERE
FACTORY MOUNTED ON EQUIPMENT OR ATTACHED TO PIPING OR DUCTS AND USING LINE
VOLTAGE FURNISH AND SET UNDER DIVISION 23, CONNECT UNDER DIVISION 26.
ABBREVIATIONS:
SECTION THROUGH RETURN DUCT
SECTION THROUGH SUPPLY OR OUTSIDE AIR DUCT
SUPPLY OR OUTSIDE AIR DUCT
ACCESS DOOR (BOTTOM OR SIDE)
ACOUSTICALLY LINED DUCT
FIRE DAMPER, SMOKE DAMPER, FIRE/SMOKE DAMPER
MANUAL VOLUME DAMPER
INCLINED DROP IN DIRECTION OF ARROW
INCLINED RISE IN DIRECTION OF ARROW
TRANSITION, RECTANGULAR TO ROUND
FLEXIBLE DUCT
IN-LINE FAN
TRANSITION, RECTANGULAR
SPIN-IN COLLAR INTO ADAPTER ON TOP OF DUCT
CEILING SUPPLY AIR REGISTER/GRILLE
SIDEWALL SUPPLY AIR REGISTER (SR)
ELBOW TURNED DOWN
ELBOW TURNED UP
ELBOW, RADIUS TYPE
ELBOW, SQUARE OR RECTANGULAR TYPE
WITH AIRFOIL TURNING VANES
CEILING RETURN AIR REGISTER (RR)
OPEN END DUCT
FLEXIBLE CONNECTION
SIDEWALL RETURN AIR REGISTER (RR)
VD
FXC
RR
DD
PIPE DROPPING DOWN
PIPE RISING UP
DIRECTION OF FLOW
RELIEF/SAFETY VALVE
FLOW METER-VENTURI
FLOW METER-ORIFICE
AUTOMATIC AIR VENT (EXTEND
AUTOMATIC FILL VALVE
DISCHARGE TO DRAIN)
MANUAL AIR VENT
CONCENTRIC REDUCER
ECCENTRIC REDUCER
STEAM LEAK DETECTOR
TPV
S
CBV
R D
STRAINER
MV
AV
GAS COCK
AQUASTAT
VB VACUUM BREAKER
EXPANSION LOOP
GAS PRESSURE
STEAM TRAP
ANCHOR
EJ
TT
FS
TH
PT/PS
G
PRESSURE SWITCH
& SYPHON (STEAM)
GAUGE COCK
TRANSMITTER OR
THERMOMETER
EXPANSION JOINT
TEMPERATURE
FLOW SWITCH
GUIDE
A
DIRECTION OF PITCH-RISE OR
DROP
STRAINER WITH BLOW
OFF VALVE
UNION - SCREWED OR FLANGED
FLOAT OPERATED
CO
CD
T
CARBON MONOXIDE
CARBON DIOXIDE
THERMOSTAT
CONTROL VALVE
REGULATOR
TRANSMITTER
PRESSURE
GAUGE WITH
FSD FIRE SMOKE DAMPER
RELIEF VALVE
SOLENOID VALVE
TEMPERATURE/PRESSURE
DIAPHRAGM VALVE
BALANCING VALVE
BALL VALVE
GLOBE VALVE, ANGLE
GATE VALVE, ANGLE
LIFT CHECK VALVE
SWING CHECK VALVE
GATE VALVE
BUTTERFLY VALVE
PLUG VALVE
GLOBE VALVE
CIRCUIT SETTING
BALANCING VALVE
THREE WAY CONTROL VALVE
TWO WAY CONTROL VALVE
PRESSURE REDUCING
VALVE (PRV)
EXISTING EQUIPMENT OR
PIPE TO BE REMOVED.
CS CONDENSER WATER SUPPLY
CR CONDENSER WATER RETURN
R REFRIGERANT LIQUID AND VAPOR LINE
RS REFRIGERANT SUCTION / VAPOR
HWS HOT WATER SUPPLY
HWR HOT WATER RETURN
HPS HEAT PUMP SUPPLY
HPR HEAT PUMP RETURN
V VENT PIPING
D DRAIN
G NATURAL GAS
SMS SNOWMELT SUPPLY
SMR SNOWMELT RETURN
CHWS CHILLED WATER SUPPLY
CHWR CHILLED WATER RETURN
LINE DESIGNATION SYMBOLS
MECHANICAL ELEMENTS / VALVING
SMOKE DAMPER
FIRE / SMOKE DAMPERFSD
SD
RH REFRIGERANT HIGH PRESSURE VAPOR
CA COMPRESSED AIR
FD - SD
- FSD
SECTION THROUGH EXHAUST AIR DUCT
HX
S
AIR VENT
HYDRAULIC SEPARATOR AIR SEPARATOR
HEAT EXCHANGER
DIGITAL SENSOR
OR PUMP
HVAC & DUCTWORK SYMBOLS
POINT OF CONNECTION OF NEW TO EXISTING
ME
C
H
A
N
I
C
A
L
-
CO
V
E
R
S
H
E
E
T
DATE:ISSUED FOR:
SHEET NUMBER:
February 21, 2025 - 1:02:50pm
DO NOT REPRODUCE THESE DRAWINGS AND
SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN
PERMISSION OF THE DESIGNER. THE DRAWINGS AND
SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND
SHALL REMAIN THE PROPERTY OF THE DESIGNER
WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS
EXECUTED OR NOT. THESE DRAWINGS AND
SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON
ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT
BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN
PERMISSION OF THE DESIGNER.
Bi
g
h
o
r
n
C
o
n
s
u
l
t
i
n
g
E
n
g
i
n
e
e
r
s
,
I
n
c
.
Me
c
h
a
n
i
c
a
l
&
E
l
e
c
t
r
i
c
a
l
E
n
g
i
n
e
e
r
s
38
6
I
n
d
i
a
n
R
o
a
d
Gr
a
n
d
J
u
n
c
t
i
o
n
,
C
O
8
1
5
0
1
Ph
o
n
e
:
(
9
7
0
)
2
4
1
-
8
7
0
9
DATE:
CHECKED BY:
JOB NO:
DRAWN BY:
SCALE:
TH
U
N
D
E
R
R
I
V
E
R
M
A
R
K
E
T
68
1
8
U
S
-
8
2
BRS/GW
MH
02/21/2025
24-305
GL
E
N
W
O
O
D
S
P
R
I
N
G
,
C
O
10/07/2024 DESIGN DEVELOPMENT
02/21/2025 100% CD
3 COMPARTMENT SINK
DEEP FRYER
HAND WASH SINK
PIZZA OVEN
HOOD & FIRE SUPPRESSION SYSTEM
GRILL
DEEP FRYER
WOMEN'S
RESTROOM
MEN'S
RESTROOM
EXISTING TO REMAIN
NO WORK
MECHANICAL
ROOM
COOLER
22
"
x
1
6
"
MAU
1
16
"
Ø
12" Ø
12" Ø
12" Ø
12" Ø
22
"
x
1
6
"
22"x16"
UP TO
MAU-1
EF
1
GH
1
20"X20"
UP TO
EF-1
18
"
Ø
DATE:ISSUED FOR:
SHEET NUMBER:
February 21, 2025 - 1:02:50pm
DO NOT REPRODUCE THESE DRAWINGS AND
SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN
PERMISSION OF THE DESIGNER. THE DRAWINGS AND
SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND
SHALL REMAIN THE PROPERTY OF THE DESIGNER
WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS
EXECUTED OR NOT. THESE DRAWINGS AND
SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON
ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT
BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN
PERMISSION OF THE DESIGNER.
Bi
g
h
o
r
n
C
o
n
s
u
l
t
i
n
g
E
n
g
i
n
e
e
r
s
,
I
n
c
.
Me
c
h
a
n
i
c
a
l
&
E
l
e
c
t
r
i
c
a
l
E
n
g
i
n
e
e
r
s
38
6
I
n
d
i
a
n
R
o
a
d
Gr
a
n
d
J
u
n
c
t
i
o
n
,
C
O
8
1
5
0
1
Ph
o
n
e
:
(
9
7
0
)
2
4
1
-
8
7
0
9
DATE:
CHECKED BY:
JOB NO:
DRAWN BY:
SCALE:
M1-1
ME
C
H
A
N
I
C
A
L
-
FL
O
O
R
P
L
A
N
TH
U
N
D
E
R
R
I
V
E
R
M
A
R
K
E
T
68
1
8
U
S
-
8
2
GL
E
N
W
O
O
D
S
P
R
I
N
G
,
C
O
MECHANICAL - FLOOR PLAN
SCALE:
NORTH
SCALE:1/4" = 1'-0"
10/07/2024 DESIGN DEVELOPMENT
BRS/GW
MH
02/21/2025
24-305
AS SHOWN
MECHANICAL GENERAL NOTES:
1.DRAWING IS DIAGRAMMATIC IN NATURE. LOCATIONS AND SIZES MAY VARY DURING FIELD COORDINATION & INSTALLATION OF MECHANICAL, PLUMBING, &
ELECTRICAL. DRAWINGS DO NOT NECESSARILY INDICATE EVERY REQUIRED OFFSET, FITTING, ETC. DRAWINGS ARE NOT TO BE SCALED FOR DIMENSIONS. TAKE
ALL DIMENSIONS FROM ARCHITECTURAL DRAWINGS, CERTIFIED EQUIPMENT DRAWINGS AND FROM THE STRUCTURE ITSELF BEFORE FABRICATING ANY WORK,
VERIFY ALL SPACE REQUIREMENTS COORDINATING WITH OTHER TRADES, AND INSTALL THE SYSTEMS IN THE SPACE PROVIDED WITHOUT EXTRA CHARGES TO
THE OWNER.
2.DUCT DIMENSIONS DO NOT REFLECT ADDITIONAL DIMENSIONS FOR INSULATION. ALL DUCTING SHALL BE INSULATED PER 2021 IECC CODE REQUIREMENTS.
(SUPPLY AND RETURN AIR DUCTS AND PLENUMS SHALL BE INSULATED WITH NOT LESS THAN R-6 INSULATION WHERE LOCATED IN UNCONDITIONED SPACES
AND WHERE LOCATED OUTSIDE THE BUILDING WITH NOT LESS THAN R-8 INSULATION IN CLIMATE ZONES 0 THROUGH 4 AND NOT LESS THAN R-12 INSULATION IN
CLIMATE ZONES 5 THROUGH 8. DUCTS LOCATED UNDERGROUND BENEATH BUILDINGS SHALL BE INSULATED AS REQUIRED IN THIS SECTION OR HAVE AN
EQUIVALENT THERMAL DISTRIBUTION EFFICIENCY. WHERE LOCATED WITHIN A BUILDING ENVELOPE ASSEMBLY, THE DUCT OR PLENUM SHALL BE SEPARATED
FROM THE BUILDING EXTERIOR OR UNCONDITIONED OR EXEMPT SPACES BY NOT LESS THAN R-8 INSULATION IN CLIMATE ZONES 0 THROUGH 4 AND NOT LESS
THAN R-12 INSULATION IN CLIMATE ZONES 5 THROUGH 8. GARFIELD COUNTY IS CLIMATE ZONE 5B)
3.COORDINATE FINAL LOCATION OF THERMOSTAT WITH OWNER PRIOR TO INSTALLATION. IF THERMOSTAT IS LOCATED ON EXTERIOR WALL PROVIDE
THERMOSTAT WITH INSULATED BACKING.
4.ALL MOTORIZED DAMPERS ON OUTDOOR AIR INTAKES AND EXHAUST SHALL BE PROVIDED WITH CLASS IA MOTORIZED DAMPERS WITH A MAXIMUM LEAKAGE
RATE OF 4 CFM/FT² AT 1.0 INCH WATER GAUGE WHEN TESTED IN ACCORDANCE WITH AMCA 500D. (PER 2021 IECC)
5.MECHANICAL CONTRACTOR SHALL FIELD LOCATE EXISTING DUCTWORK PRIOR TO CONSTRUCTION. MECHANICAL CONTRACTOR SHALL COORDINATE TIE IN
CONNECTION POINTS OF NEW SUPPLY DIFFUSERS WITH EXISTING DUCTWORK AS NECESSARY.
6.MECHANICAL EQUIPMENT MANUFACTURERS AS SCHEDULED ON MECHANICAL DRAWINGS ARE SUGGESTED MANUFACTURER'S. UNLESS NOTED OTHERWISE
DUE TO OWNER/CLIENT REQUIREMENTS AND PREFERENCES. MECHANICAL CONTRACTOR CAN SUBMIT EQUIVALENT EQUIPMENT FROM MANUFACTURERS THAT
DIFFER FROM SCHEDULED MECHANICAL EQUIPMENT. ALTERNATE MANUFACTURERS OF MECHANICAL EQUIPMENT WILL BE REVIEWED FOR EQUIVALENCE OF
PERFORMANCE AND FUNCTIONALITY BY ENGINEER.
7.WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A BUILDING SUCH THAT PERSONNEL
WILL HAVE TO CLIMB HIGHER THAN 16 FEET ABOVE GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS OF ACCESS
SHALL BE PROVIDED. SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES IN HEIGHT OR WALKING ON ROOFS
HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL. SUCH ACCESS SHALL NOT REQUIRE THE USE OF PORTABLE LADDERS. WHERE
ACCESS INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE PARAPET WALL. PERMANENT LADDERS SHALL
COMPLY WITH REQUIREMENTS LISTED IN SECTION 306.5 OF THE 2018 INTERNATIONAL MECHANICAL CODE.
8.CONTRACTOR TO COORDINATE MAKE UP AIR UNIT AND EF LOCATIONS TO MAINTAIN SEPARATIONS FROM EACH OTHER AND ALL OTHER EXISTING ROOF TOP
EQUIPMENT ACCORDING TO IMC 501.3
02/21/2025 100% CD
DATE:ISSUED FOR:
SHEET NUMBER:
February 21, 2025 - 1:02:50pm
DO NOT REPRODUCE THESE DRAWINGS AND
SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN
PERMISSION OF THE DESIGNER. THE DRAWINGS AND
SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND
SHALL REMAIN THE PROPERTY OF THE DESIGNER
WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS
EXECUTED OR NOT. THESE DRAWINGS AND
SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON
ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT
BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN
PERMISSION OF THE DESIGNER.
Bi
g
h
o
r
n
C
o
n
s
u
l
t
i
n
g
E
n
g
i
n
e
e
r
s
,
I
n
c
.
Me
c
h
a
n
i
c
a
l
&
E
l
e
c
t
r
i
c
a
l
E
n
g
i
n
e
e
r
s
38
6
I
n
d
i
a
n
R
o
a
d
Gr
a
n
d
J
u
n
c
t
i
o
n
,
C
O
8
1
5
0
1
Ph
o
n
e
:
(
9
7
0
)
2
4
1
-
8
7
0
9
DATE:
CHECKED BY:
JOB NO:
DRAWN BY:
SCALE:
M3-1
ME
C
H
A
N
I
C
A
L
-
DE
T
A
I
L
S
TH
U
N
D
E
R
R
I
V
E
R
M
A
R
K
E
T
68
1
8
U
S
-
8
2
BRS/GW
MH
02/21/2025
24-305
GL
E
N
W
O
O
D
S
P
R
I
N
G
,
C
O
10/07/2024 DESIGN DEVELOPMENT
OUTDOOR GAS FIRED MAKE-UP AIR UNIT SCHEDULE
EQUIPMENT NO.SERVICE SUPPLY AIR (CFM)EXTERNAL STATIC
PRESS. (IN. W.G.)INPUT (MBH)OUTPUT (MBH)EFFICIENCY
A.F.U.E.
GAS RATE
(CFH)
ELECTRIC
MANUFACTURER & MODEL OPTIONS/ACCESSORIES
HP V/PH/HZ MCA (A)MOP (A)
MAU-1 KITCHEN 2656 0.26 145.3 133.7 92%180.7 1 208/1/60 8.3 15 GREENHECK DGX-P112-H12-MF
(OR EQUIVALENT)NOTE-1
NOTE:
1. PROVIDE HIGH ALTITUDE KIT SIZED PER LOCATION ELEVATION. CORRDINATE FAN CONTROLS WITH EF AND KITCHEN HOOD.
EXHAUST FAN SCHEDULE
EQUIPMENT NO.SERVICE LOCATION CFM EXTERNAL STATIC PRESS (IN.
W.G.)
MOTOR
MANUFACTURER & MODEL OPTIONS/ACCESSORIES
WATTS HP RPM VOLT/PH/HZ FLA
EF-1 KITCHEN HOOD ROOF 2,944 0.925 1471.00 2.00 1397 208/1/60 13.2 GREENHECK CUE-160-VG (OR
EQUIVALENT)NOTE-1
NOTES:
1. PROVIDE WITH MOTOR STARTER, POWER DISCONNECT, AND DIRECT DRIVEN MOTOR WITH SPEED CONTROLLER. COORDINATE FAN CONTROLS WITH MAU AND KITCHEN HOOD.
SUPPLY PLENUM INFORMATION
POS.HOOD
NO.MARK TYPEL
COLLARS
W L DIA.CFMINSULATEDDAMPER(S)VEL.
LED LIGHT(S)
W H
SIZE (IN.)TYPE MOUNTING QTYQTYSUPPLIED
TOTAL
CFM
TOTAL
S.P.
1 GH-1 FRONT MUA 12 26 5890.01 272FACTORY278NOYESNO144ASP1178
2 GH-1 FRONT MUA 12 26 5890.01 272FACTORY278NOYESNO144ASP1178
MODEL LENGTH WIDTH HEIGHT
HOOD DIMENSIONS (IN.)
MARK
WIDTH LENGTH DIA.CFM S.P.
COLLAR(S)
EXHAUST
HOOD INFORMATION
HOOD
NO.
COOKING
LOAD /
DUTY
RATING
HOOD
CONSTR.MUA
CFM
AC
CFM
HANGING
WEIGHT
LBS.
SECTION
LOCATIONTOTAL
CFM
SUPPLY
9 16 0.675166317848 LEFT24GXEW-78-S GH-1 1663 1178 272HEAVY
430 SS
WHERE
EXPOSED
10 12 0.487128127848 RIGHT24GXEW-78-S GH-1 1281 1178 272HEAVY
430 SS
WHERE
EXPOSED
LIGHTING DETAILS
QTY L
GREASE FILTRATION DETAILS
QTY H LOCATION
UTILITY CABINET(S)
CONTROLS
HOOD INFORMATION
MARK FIXTURE TYPE
BULB / LAMP INFO
FOOT
CANDLES
TYPE / MODEL
MATERIAL
SIZE (IN.)HOOD
NO.FIRE SYSTEM
MODELTYPESIZE INTERFACE
46.14 3 201
20
161INCANDESCENT (GLOBE)
100W A19 (BULBS NOT INCL.)
X-TRACTOR (SPARK
ARRESTOR INCL.)
STAINLESS STEEL
GH-1 4
46.14 3 201
20
162INCANDESCENT (GLOBE)
100W A19 (BULBS NOT INCL.)
X-TRACTOR (SPARK
ARRESTOR INCL.)
STAINLESS STEEL
GH-1 4
HOOD OPTIONS
UL 710 LISTED W/ OUT EXHAUST FIRE DAMPER - UL #MH11726
HOOD TOP INSULATED FOR ZERO CLEARANCE TO COMBUSTIBLES
BACK INTEGRAL AIR SPACE - 3 IN WIDE
CONTINUOUS CAPTURE
FACTORY MOUNTED EXHAUST COLLAR(S)
PERFORMANCE ENHANCING LIP (PEL) TECHNOLOGY
STANDING SEAM CONSTRUCTION FOR SUPERIOR STRENGTH
MECHANICAL PROVISIONS:
1. SCOPE OF WORK
A.THE CONTRACTOR IS RESPONSIBLE FOR ALL WORK, MATERIALS,
AND LABOR TO SATISFY A COMPLETE WORKING SYSTEM WHETHER
SPECIFIED OR IMPLIED.
B.ALL WORK IS TO BE PERFORMED IN STRICT COMPLIANCE WITH ALL
LOCAL CODES AND ALL OTHER REGULATION GOVERNING WORK OF
THIS NATURE.
C.THE CONTRACTOR SHALL, BEFORE SUBMITTING ANY PROPOSAL,
EXAMINE THE PROPOSED SITE AND SHALL DETERMINE FOR HIMSELF
THE CONDITIONS THAT MAY EFFECT THE WORK. NO ALLOWANCE
SHALL BE MADE IF THE CONTRACTOR FAILS TO MAKE SUCH
EXAMINATIONS.
D.ALL EQUIPMENT AND MATERIALS SHALL BE AS SPECIFIED OR
"APPROVED EQUAL" BY THE ENGINEER OR ARCHITECT.
2. PERMITS
A.THE CONTRACTOR SHALL SECURE ALL PERMITS OR APPLICATIONS
AND PAY ANY AND ALL FEES.
3. SHOP DRAWINGS
A.SUBMIT MATERIAL LIST AND SHOP DRAWINGS FOR MAJOR
EQUIPMENT TO THE ARCHITECT/ENGINEER FOR APPROVAL. THE
CONTRACTOR SHALL SUBMIT FIVE SETS OF SHOP DRAWINGS AND
THEY SHALL BE CLEARLY LABELED.
4. FLEXIBLE DUCT WORK
A.FLEXIBLE TYPE DUCT SHALL BE OF TWO ELEMENT SPIRAL
CONSTRUCTION COMPOSED OF A CORROSION RESISTANT METAL
SUPPORTING SPIRAL AND COATED FABRIC WITH A MINERAL BASE.
FLEXIBLE DUCT CONNECTORS SHALL BE LISTED BY U.L., CLASS 1
DUCTS, AND SHALL HAVE A FLAME SPREAD RATING NOT EXCEEDING
25 AND A SMOKE DEVELOPED RATING NOT EXCEEDING 50.
B.USE OF FLEXIBLE DUCTWORK SHALL BE LIMITED TO NO MORE THAN
6 LINEAR FEET PER RUN.
C.CONTRACTOR SHALL BE CAREFUL SO AS NOT TO KINK OR
COLLAPSE FLEXIBLE DUCT.
5. REFRIGERANT
A. PIPING CONTRACTOR SHALL PROVIDE AND INSTALL REFRIGERANT
PIPING IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS AND IN SUCH A WAY AS TO BE INCONSPICUOUS
AND FREE FROM ANY POSSIBLE CONDENSATION.
B. INSULATE REFRIGERANT LINES WITH ARMOUR-FLEX TYPE
INSULATION, SHALL BE TYPE "K" COPPER TUBING, WITH WROUGHT
COPPER SOLDER TYPE FITTINGS SUITABLE FOR CONNECTION WITH
SILVER SOLDER.
6. DUCTWORK
A.THE DUCTWORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH
THE "SMACNA" APPLICABLE MANUALS.
B.ALL DUCTWORK SHALL BE THE LOW VELOCITY TYPE, UNLESS
SPECIFIED OTHERWISE.
C.CONTRACTOR SHALL PROVIDE AND INSTALL APPROVED FIRE
DAMPERS AND ACCESS PANELS IN ANY AND ALL DUCTWORK WHICH
PENETRATES A HORIZONTAL OR VERTICAL FIRE PARTITION, OR AS
OTHERWISE SHOWN ON DRAWINGS.
D.ALL BRANCH DUCTS TO HAVE VOLUME DAMPERS, SMOOTH TURN
RADIUS DUCTWORK OR TURNING VANES SHALL BE USED
THROUGHOUT WHERE FLOW EXCEEDS 150 CFM.
E.ALL DUCT JOINTS TO BE SEALED IN ACCORDANCE WITH
"SMACNA"STANDARDS AND ACCEPTED GOOD PRACTICE.
F.ALL DUCT DIMENSIONS SHOWN ARE NET INSIDE
VALUES.DIMENSIONS MAY BE CHANGED SO LONG AS THE NET FREE
FACE AREA IS MAINTAINED.
G.ALL CONCEALED DUCTWORK SHALL BE INSULATED WITH 1-1/2"
FIBERGLASS INSULATING BLANKET WITH ALUMINUM FOIL FACING.
H.ALL SUPPLY AND RETURN DUCTWORK 15 FEET DOWNSTREAM OF
THE HVAC UNIT SHALL BE INTERNALLY LINED WITH A 1/2"
ACOUSTICAL DUCT LINER UNLESS OTHERWISE NOTED ON THE
DRAWINGS.
7. DRAINAGE PIPING
A.(CONDENSATE) SHALL BE SCHEDULE 40 PVC PIPE WITH SOLVENT
JOINTS.PITCH HORIZONTAL LINES 1" IN 10'-0". CONDENSATE DRAINS
SHALL BE ROUTED TO FLOOR DRAIN, ROOF DRAIN OR INDIRECT
WASTE DRAIN.
8. HVAC CONTROLS
A.CONTRACTOR TO SUPPLY AND INSTALL ALL CONTROL WIRING AND
THERMOSTATS AS REQUIRED.
9. ELECTRICAL
A.CONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR
FOR LOCATION OF WIRING FOR EACH HVAC UNIT.
10. PIPE SUPPORTS
A.ALL PIPE SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE IN
A NEAT AND WORKMANLIKE MANNER. THE USE OF WIRE OR METAL
STRAP TOSUPPORT PIPES WILL NOT BE PERMITTED. SPACING OF
PIPE SUPPORTS SHALL NOT EXCEED 8 FEET FOR ALL PIPING.
PLASTIC PIPING TO BE SUPPORTED EVERY 4 FEET.
11. GAS PIPING
A.PIPING SHALL BE SCHEDULE 40 BLACK STEEL PIPE WITH MALLEABLE
IRON FITTINGS. WHERE GAS PIPE CONNECTS TO EQUIPMENT, IT
SHALL BE PROVIDED WITH A DRIP LEG THE FULL SIZE OF THE
RUNOUT, A 100% SHUT-OFF VALVE AND A UNION. GAS PIPING
CONTAINING PRESSURE GREATER THAN 9" W.G. SHALL BE
SCHEDULE 40 BLACK STEEL PIPE WITH WELDED JOINTS.
12. MISCELLANEOUS
A.ALL EXTERIOR OPENINGS TO BE PROPERLY CAULKED AND SEALED
WITH A SEALANT OF HIGH QUALITY AND LONG LIFE, TO PREVENT
INFILTRATION OF OUTSIDE AIR INTO CONDITIONED
SPACE.COORDINATE INSTALLATION OF ALL ROOF FLASHING AT
ROOF PENETRATION.
B.DO NOT SCALE THIS DRAWING FOR EXACT DIMENSIONS.
C.VERIFY ALL FIGURES, CONDITIONS, AND DIMENSIONS AT THE JOB
SITE.
D.THE MECHANICAL PLANS ARE INTENDED TO BE DIAGRAMMATIC AND
ARE BASED ON ONE MANUFACTURE'S EQUIPMENT. THEY ARE NOT
INTENDED TO SHOW EVERY ITEM IN ITS EXACT LOCATION, THE
EXACT DIMENSIONS, OR ALL THE DETAILS OF THE EQUIPMENT.
E.THE CONTRACTOR SHALL VERIFY THE ACTUAL DIMENSIONS OF THE
EQUIPMENT PROPOSED TO ENSURE THAT THE EQUIPMENT WILL FIT
IN THE AVAILABLE SPACE.
F.PEX TUBING, IF PEX TUBING IS USED AS AN APPROVED ALTERNATE
FOR APPLICATIONS WHERE METALLIC PIPING IS THE BASIS OF
DESIGN. THE PEX MANUFACTURER SHALL SUBMIT SHOP DRAWINGS
CLEARLY INDICATING THAT THE DESIGN HAS BEEN ANALYZED AND
MODIFIED, AS REQUIRED TO MAINTAIN SCHEDULED HYDRONIC
SYSTEM PARAMETERS. ANY DESIGN RESULTING IN INCREASED
SYSTEM PRESSURE DROP AS A RESULT OF IMPROPER PEX SIZING
OR DESIGN SHALL NOT BE PERMITTED.
13. TESTING AND BALANCING
A.THE HVAC SYSTEM SHALL BE TESTED AND AND BALANCED BY AN
INDEPENDENT AGENCY, UNDER THE SUPERVISION OF A LICENSED
PROFESSIONAL ENGINEER. A SEALED TYPE WRITTEN REPORT SHALL
BE SUBMITTED TO THE ARCHITECT/ENGINEER FOR REVIEW AND
APPROVAL.
14. GUARANTEE
A.MATERIALS, EQUIPMENT AND INSTALLATION SHALL BE GUARANTEED
FOR A PERIOD OF ONE(1) YEAR FROM DATE OF ACCEPTANCE.
DEFECTS WHICH APPEAR DURING THAT PERIOD SHALL BE
CORRECTED AT THIS CONTRACTOR'S EXPENSE.
B.FOR THE SAME PERIOD, THE MECHANICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY DAMAGE TO PREMISES CAUSED BY
DEFECTS IN WORKMANSHIP OR IN THE WORK OR EQUIPMENT
FURNISHED AND/OR INSTALLED BY HIM.
KITCHEN
APPLIANCES
GENERAL NOTES:
1.INSTALL GREASE DUCT PER IMC CODE. INSULATE GREASE DUCT PER
IMC CODE. GREASE DUCT TO MAINTAIN MINIMUM CLEARANCES TO
COMBUSTIBLES PER IMC CODE.
2.CLEANOUTS SHALL BE LOCATED ON BOTTOM ONLY WHERE OTHER
LOCATIONS ARE NOT AVAILABLE AND SHALL BE PROVIDED WITH
INTERNAL DAMMING OF THE OPENING SUCH THAT GREASE WILL FLOW
PAST THE OPENING WITHOUT POOLING. BOTTOM CLEANOUTS AND
OPENINGS SHALL BE APPROVED FOR THE APPLICATION AND
INSTALLED LIQUID-TIGHT.
3.CLEANOUTS ON OF DUCT SHALL HAVE DIMENSIONS NO LESS THAN
12"X12". CLEANOUTS SHALL BE LARGE ENOUGH TO PROVIDE ACCESS
FOR CLEANING AND MAINTENANCE.
4.DUCTWORK FOR THIS PROJECT SHALL BE UL 1978 LISTED. PREFERRED
DUCTWORK MAKE/MODEL SHALL BE SELKIRK: ZeroClear Z3.
CONTRACTOR SHALL INSTALL ALL GREASE DUCTWORK PER
MANUFACTURERS INSTALLATION INSTRUCTIONS.
TO MAU
ROOF
FLOOR
KITCHEN HOOD
NOT TO SCALE
GREASE DUCT, HOOD, EXHAUST FAN DETAIL
10' MIN.
KITCHEN HOOD SUPPLIED SHALL
HAVE INSULATION TO MAINTAIN
MINIMUM CLEARANCES TO
COMBUSTIBLES. PROVIDED FROM
MANUFACTURER FOR FRONT, BACK,
TOP, AND SIDES. CONTRACTOR SHALL
INSTALL PER MANUFACTURER'S
INSTRUCTIONS TO MAINTAIN UL
LISTING.
CEILING
UTILITY UPBLAST GREASE EXHAUST FAN
PROVIDE WITH:
-REMOVABLE GREASE CUP
-BELT DRIVEN
-UL 762 LISTING
-POWER DISCONNECT
-VENTED CURB
-HINGED CURB
-STAINLESS STEEL
-MOTOR STARTER
-INTERLOCK WITH KITCHEN HOOD &
MAKE UP AIR UNIT
KITCHEN HOOD TO BE INSTALLED PER
MANUFACTURERS INSTRUCTIONS. ALL
CLEARANCES SHALL BE FIELD
COORDINATED TO MAINTAIN UL
LISTINGS. KITCHEN HOOD SHALL BE
INSTALLED PER IMC/IFGC CODE
REQUIREMENTS.
40
"
M
I
N
.
MAU MAKE-UP
AIR UNIT
100% OUTSIDE
AIR
100% OUTSIDE
AIR INLET
HOOD
BLOWER
SECTION
FURNACE
SECTION
FLUE
CONDITIONED
SUPPLY AIR
VIBRATION ISOLATION ROOF CURB
ROOF
MAKE-UP AIR UNIT MOUNTED AT ROOF
NOT TO SCALE
EVAP
SECTION
02/21/2025 100% CD
MoTak MGF4-P-C Gas Fryer- (1) s0 rb Vat, Floor Moder, Liquid propane
Read { rcvrss KaTorn t;89S.cGF4Lp. Uel: U6ffbo
.=;*
.^..:. "ai:'
ii i tt
Thank you for vbiting KaTom. What
are you looking for today?
a
-
s lN STOCK: Shlpr ln 1 Buslnest Day
@ to0+ in stock
Selected Gas Type: Llqurd profrne
I Naturalcss @ UquidPropane
MoTak MGF4-P-C Description
oil and ruining food llavor.
ecessed handle eases opening. To make il easier for you to position and reposition this item in your commercila kitchen, it come with four casters.
Product Details
. 50-lb. tank cspacity. (4) 30,000€TU heattubes. Temperature range: 20F400 degrees F. Autorcsct, highlimft swhch helps prwent overheating
r Peened, stainless steel tank has smodrd |velds to facilitale cleaning. Cold zone is not heated to lhe same temperature as the rest of the tank enabling sediment to settle withoui buming in the oil. 2 nickel chrome wire baskets have red, plastic-coated handles
. Doubl+rod, stalnless steel hanger provides draining space for food ln baskets. Stainless steeldoor has an integrated llnerro simplify cleanlng
. Welded door magnet seals the door shut. Recessed door handle saves space. Slainless steel front top ledge, and header provide strenglh and rust re$istance
. Galvanized steel sides and backwithstand heavy use
. Casters
.120,0008TU
. Not suitable fc rcgldcotlal or othsr non-commerclal sse
Dimensions & Utilities
. 15.5 in. W r 30.3 in. D x 53.2 in. H
. HeatedbyLPgas
Product Features
Stainless Steel
Construction
Resists rusting
and
High-limit
Safety Switch
Prevents overheating
lnsulated
Basket Handles
Reduce risk of bums
Gasters
Mobile for convenient
maintenance and cleaning
FREE CASTERS INCLUDED
W ITH PURCHASE
From The Manufacturer
hanger. built in flue dellecto( ball type full port drain, 3/4' NPT male gas connection ln rear, stainless steel lronl galvanized sides & back, casters, 1 20,000 BTU
*tmage may not depicl product colot inclusions or accessories.
Resources
m Commercral Deep Fryer lerms
Conftlly Srzing Your Commcrcial Fr)€r
'18 month parts & labor
MCTAK
MoTak MGF4-P€ Specifi cations
Manufacturer
Baskets
C"p",*V frbt
GasType
Number of Fry Pots
Type
Wananty
wia*r A"i--
Oil Capacity/Fryer 0b)
Frypot Style
tuType
BTU per F4ar
Number of Tubes
Product
Producl Type
Weight
MoTak
2
50
t"P
I
Roor Model
18 month parts & labor
15.5
50
TubeType
Breaded
r20000
I
GTIry..
Coold.nS ECllgent
183.00
Documents
Sp6 Snd Wrrry M$od
producl failure or any damages/injuries.
PDF PDFPDF
Hood Builders lnc.
5925 E Evans Ave Suite 215
DENVER, CO 80222
+-13037777720
mai n.hoodbuilder@gmail.com
z#{*.*-
]IoOdBUILDER
Estimate
family of Nationwide cornpanies
ADDRESS
THUNDER NVCN MARKET
6818 CO-82 GLENWOOD SPRINGS
co 81601
NATHAN 719-415-7278
NATHANJARELLANO@GMAr L.COM
zAcH@TCFUELS.COM
DATE
. SHIPTO
THUNDER RIVER MARKET
6818 CO-82 GLENWOOD SPRINGS
co 81601
NATHAN 719-415-7278
NATHANJAR ELLANO@GMAtL.COM
ZACH@TCFUELS.COM
QTY RATE
35,930.00Furnish
Exhaust Fan,
NFPA
1 9,500.00
5,000.00
3,630.00
2,000.00
550.00
'1 850.00
p$-
E$TIMATE #
HB82739A
EXPIRATION DATE
.Q4'"
SALES REP
JOEL - 720-372-6729
ITEM #
HB1.) HOOD,
EXHAUST FAN, AND
MAU PACKAGE
HB2.) DUCTWORK
HB3.) F|RE
SUPPRESSION
INSTALLATION
HB4.) ELECTRTCAL
INTERLOCKING
HB5.) ENGTNEERTNG
DRAWINGS AND
PERMIT PROCESS
HB6.) ROOFTNG
HB7.) FrRE WRAP
02/19t2025 ,0311912025
DESCRIPTION
Hoods, Exhaust Fans, and a MAU
and install 13' x 4' Stainless Steel
and a Heated Make Up Air Unit. (U
complaint)
Furnish and lnstall 1 Work, MUA Duct
work,2 flat pieces,
straight path to the
ffirturn!,
Furnish and lnstall Complete UL300 Compliant Fire
Suppression System lnstallation Chemical Bottle,
Control Head, CO2, Pull Station, Chemical Line, and
Fusible Link line
Furnish and installControl Panel. Electrical
Connections for Hood, MAU, Microswitch Assembly,
and all safety interlocks per NFPA and UL sequence
requirement (Not including the wiring to the units and
the Electrical Panel).
Mechanical, Electrical, and Fire System Drawings
including Permitting Process will be done by Customer
and the inspections will be done by Contractor.
Roof penetration and Roof patch (cold Patch) for ducts
penetration point.
Furnish and install Two layers of Fire Wrap for the
Grease Ducts.
Removal of existing 6'type 2 hood.
5 Sheets of stainless steelallflashing installed behind
the hood. Provided by the customer.
1
.00
.00
,540
,990
B1
1
AMOUNT
35,930.00
18,540.00
1 1,990.00
5,500.CI0
9,500.00
5,000.00
3,630.00
2,000.00
2,750.00
1 5,500.00
DEMO
HB8.) STATNLESS
STEEL WALL
FLASHING
AUTOMATIC GAS
VALVE SHUT OFF
5
Furnish and install the automatic gas shut off valve
a
850.00
Notes:This bid pertains to the items listed above only. This bid is pending local
authority's approval. AII additional work will be at extra cost.lTEMS NOT
INCLUDED UNLESS LISTED ABOVE:Wall Flashing ($), Skirring (g), cas
Piping, Air Balancing, Automatic Gas Shut-off Valve:up to 1.5 inch: (9750),
Structural Engineering, Electrical Drawings, Electrical wiring and connections
to the Exhaust Fan, MAU, Lights, Outlets and Microswitch Assembly, Other
Electrical, and Alarm. Asbestos testing and/or removal, any structural work or
penetration of walls, and repair of walls and ceilings. All drawings, Taxes,
Permit Fees, and all other fees.This bid is based on work being performed 8-
hours during daylight, Monday-Friday unless we decide othenarise.Customer
must always provide proper and safe access to the work area.Customer.must
provide proper toilet facilities for our workers. Terms: 50% down, 25/" due
upon equipment delivery, 20o/o due upon rough inspection,and 5% due at final.
Accepted By
TOTAL
Accepted Date
$95,690.00
I
I
THUNDER RIVER MARKET
KITCHEN LAYOUT
COOL€R
I
t
I
I
I
,{
1
I
.--,-{6:.t:
56
I
I
j
\. -,^ "i
\'
ii t--- -.' '
THUNDER RIVER MARKET
6818 CO-82
GLENWOOD SPRINGS
co 81601
DELI FLOOR PLAN
SCALE-1/8"=1'
-)t
,J9
I
I -.1
,|
,1 --i --.,
3 COMPARTMENT SINK
HAND WASH SINK
PIZZAOVEN
',;o.rxHnusr reN
EXISTING KITCHEN EQUIPMENT
THUNDER RIVER MARKET
6818 CO-82
GLENWOOD SPRINGS CO 81601
DELI FLOOR PLAN
SCALE -3132" = 1'
I
l
*t-.. )_"-. ___-__+.
'1.
l
I
F.l
-l
i4j
,i
ll
't
- 12'HOOD & F|RE
i:jSUPPRESS|ON SYSTEM
PROPOSED KITCHEN EQUIPMENT
THUNDER RIVER MARKET
6818 CO-82
GLENWOOD SPRINGS CO 81601
DELI FLOOR PLAN
SCALE -3132" = 1'
\. -t
. .- -/--.,. !