Exemption Request #1 — Hand Hose Stations
DATE: December 19, 2025
PROJECT: Vantage Aviation RIL (Building A2)
ADDRESS: 375 County Road 352, A2
Rifle, Colorado 81650
Garfield County Permit* BLCO-06-25-9329
ARCHITECT: Hauser Architects, P.C.
3780 East 15'h Street, Suite 201
Loveland, Colorado 80538
REQUEST:
We understand the fire division & building department are open to exempting the requirement for hand
hose stations in the hangar. Per Contractor consultation with a Senior Engineering Technician (SET), our
request is as follows:
"For the Vantage Aviation Hangar (A2 Building) project, it is proposed to
exempt/eliminate the installation of the 1 %" hand hose stations required by the
2016 edition of NFPA 409.
These fire hose stations are typically underutilized due to the risks to non -fire
department staff in the event of a fire, and due to the fire department's standard
operational procedure to use their dedicated equipment -
This requirement was removed in the 2022 edition of NFPA 409 citing these and
other concems.
A copy of the NFPA 409 technical committee's notes is attached for reference
(see pages 30 & 31)."
END OF REQUEST
We respectfully request a written response regarding your decision. To indicate your acceptance, please
sign in the space provided below or submit a separate letter of confirmation.
Orrin D. Moon (Prevention Division Chief/Fire Marshal)
Colorado River Fire Rescue
Date:
John Plano (Chief Building Official)
Garfield County Bu' ' Department
Date:
(Z-3B -2S
Vantage Aviation RIL — A2:
3780 East I5th Street > Suite 201 ) Loveland, Colorado > 80538 Exemption Request#1
p > 970.669.8220 e > info@hauserarchitectspc.com w > HauserArchitectspc.com page 1 of 1
W HACJSER
A H C H I i E C i S
Exemption Request #1 - Hand Hose Stations
DATE: December 19, 2025
PROJECT: Vantage Aviation RIL (Building A5/6)
ADDRESS. 375 County Road 352, A5/6
Rifle, Colorado 81650
Garfield County Permit #: BLCO-06-25-9330
ARCHITECT: Hauser Architects, P.C.
3780 East 15'h Street, Suite 201
Loveland, Colorado 80538
REQUEST:
We understand the fire division & building department are open to exempting the requirement for hand
hose stations in the hangar. Per Contractor consultation with a Senior Engineering Technician (SET), our
request is as follows:
"For the Vantage Aviation Hangar (A5/6 Building) project, it is proposed to
exempt/eliminate the installation of the 1 %" hand hose stations required by the
2016 edition of NFPA 409.
These fire hose stations are typically underutilized due to the risks to non -fire
department staff in the event of a fire, and due to the fire department's standard
operational procedure to use their dedicated equipment.
This requirement was removed in the 2022 edition of NFPA 409 citing these and
other concerns.
A copy of the NFPA 409 technical committee's notes is attached for reference
(see pages 30 & 31)."
END OF REQUEST
We respectfully request a written response regarding your decision. To indicate your acceptance, please
sign in the space provided below or submit a separate letter of confirmation.
Orrin D. Moon (Prevention Division Chief/Fire Marshal)
Colorado River Fire Rescue
(,a A-- Date: `3z9- 2S
John Plano (Chief Building Official)
Garfield County Building Department
Date:
(?--3 0 -25
Vantage Aviation RIL - A5/6:
3780 East 15th Street > Suite 201 , Loveland, Colorado ) 80538 Exemption Request#1
p ) 970.669.8220 e infoQhauserarchitectspc.com w ) HauserArchitectspc.com page 1 of 1