HomeMy WebLinkAboutBlower Door TestSummarylLI Schooner ADU �t�ecJ FanTestic version: 5.15.86 licensed to: Dexter Diagnostics Test date: 2026-01-02 By: Amanda Poindexter Customer: Building Lot Number: Building address: 79 Schooner Carbondale, Garfield CO USA 81623 Building and Test Information Test file name: IqSchooner ADU Building volume [cu ft]: 17,530 Envelope Area [sq ft]: 4,501 Floor Area [sq ft]: 1,380 Building Height (from ground to top) [ft]: 30 Altitude [ft]: 7,080 Results CFM at 50 Pa: 1013.0 Leakage Area (EgLA) [sg in]: 99.43 Leakage Area (EfLA) [sq in]: 51.33 Air Changes per hour ACH50: 3.47 Compliance Per the 2021 IECC (R402.4.1.2), the exemption for buildings under 1500 sf is the following: "Exception: When testing individual dwelling units, an air leakage rate not exceeding 0.30 cubic feet per minute per square foot of the dwelling unit enclosure area, tested in accordance with ANSI/RESNET/ICC 380, ASTM E779 or ASTM E1827 and reported at a pressure of 50 Pa, shall be permitted in all climate zones for: 1. Attached single and multiple -family building dwelling units. 2. Buildings or dwelling units that are 1,500 square feet (139.4 m2) or smaller." This building has a enclosure area of 4,501 sf. At 0.30 cfm/sf, this results in an allowed cfm of 1,350. This unit passes at 1,013 cfm. 1/5/2026 Air Leakage Test Report In compliance with ASTM E-779 (2019) Dexter Diagnostics Building Address: -11 Schooner Carbondale, Garfield CO USA 81623 Performed for: Performed by: Amanda Poindexter Test date: 2026-01-02 Associated Test file: q Schooner ADU Report Number: Unique Property ID Number: 1/5/2026