SUBSOIL STUDY
FOR FOUNDATION DESIGN
PROPOSED RESIDENCE
LOT F-19, ASPEN GLEN
DIAMOND A RANCH ROAD
GARFIELD COUNTY, COLORADO
PROJECT NO. 21-7-232
APRIL 19, 2021
PREPARED FOR:
WHITNEY WARD
918 BROOKIE
CARBONDALE, COLORADO 81623
woward@me.com
Kumar & Associates, Inc. ® Project No. 21-7-232
TABLE OF CONTENTS
PURPOSE AND SCOPE OF STUDY ....................................................................................... - 1 -
PROPOSED CONSTRUCTION ................................................................................................ - 1 -
SITE CONDITIONS ................................................................................................................... - 1 -
SUBSIDENCE POTENTIAL ..................................................................................................... - 2 -
FIELD EXPLORATION ............................................................................................................ - 2 -
SUBSURFACE CONDITIONS ................................................................................................. - 3 -
FOUNDATION BEARING CONDITIONS .............................................................................. - 3 -
DESIGN RECOMMENDATIONS ............................................................................................ - 4 -
FOUNDATIONS .................................................................................................................... - 4 -
FOUNDATION AND RETAINING WALLS ....................................................................... - 5 -
FLOOR SLABS ...................................................................................................................... - 6 -
UNDERDRAIN SYSTEM ..................................................................................................... - 6 -
SURFACE DRAINAGE ......................................................................................................... - 7 -
LIMITATIONS ........................................................................................................................... - 8 -
FIGURE 1 - LOCATION OF EXPLORATORY BORINGS
FIGURE 2 - LOGS OF EXPLORATORY BORINGS
FIGURE 3 - LEGEND AND NOTES
FIGURE 4 - SWELL-CONSOLIDATION TEST RESULTS
FIGURES 5 and 6 - GRADATION TEST RESULTS
TABLE 1- SUMMARY OF LABORATORY TEST RESULTS
Kumar & Associates, Inc. ® Project No. 21-7-232
PURPOSE AND SCOPE OF STUDY
This report presents the results of a subsoil study for a proposed residence to be located on
Lot F-19, Aspen Glen, Diamond A Ranch Road, Garfield County, Colorado. The project site is
shown on Figure 1. The purpose of the study was to develop recommendations for the
foundation design. The study was conducted in accordance with our agreement for geotechnical
engineering services to Whitney Ward dated March 2, 2021.
A field exploration program consisting of exploratory borings was conducted to obtain
information on the subsurface conditions. Samples of the subsoils obtained during the field
exploration were tested in the laboratory to determine their classification, compressibility or
swell and other engineering characteristics. The results of the field exploration and laboratory
testing were analyzed to develop recommendations for foundation types, depths and allowable
pressures for the proposed building foundation. This report summarizes the data obtained during
this study and presents our conclusions, design recommendations and other geotechnical
engineering considerations based on the proposed construction and the subsurface conditions
encountered.
PROPOSED CONSTRUCTION
Design plans for the proposed residence were not available at the time of our study. The
proposed residence is assumed to be a one or two story wood frame structure with attached
garage possibly over a basement level. Ground floors could be slab-on-grade or structural over
crawlspace. Grading for the structure is assumed to be relatively minor with cut depths between
about 2 to 10 feet. We assume relatively light foundation loadings, typical of the proposed type
of construction.
If building loadings, location or grading plans change significantly from those described above,
we should be notified to re-evaluate the recommendations contained in this report.
SITE CONDITIONS
The subject site was vacant at the time of our field exploration. The ground surface is relatively
flat with about 1 to 2 feet of elevation difference across the building envelope. Vegetation
- 2 -
Kumar & Associates, Inc. ® Project No. 21-7-232
consists of grass. An artificial pond is located across the golf course to the northwest. A
subsidence area was previously mapped in the northeast part of the lot just outside of the
building envelope as shown on Figure 1. Site grading as part of the original subdivision
development placed fill material in the subsidence area to level the lot.
SUBSIDENCE POTENTIAL
Bedrock of the Pennsylvanian age Eagle Valley Evaporite underlies the Aspen Glen Subdivision.
These rocks are a sequence of gypsiferous shale, fine-grained sandstone and siltstone with some
massive beds of gypsum and limestone. There is a possibility that massive gypsum deposits
associated with the Eagle Valley Evaporite underlie portions of the lot. Dissolution of the
gypsum under certain conditions can cause sinkholes to develop and can produce areas of
localized subsidence. During previous work in the area, several sinkholes were observed
scattered throughout the Aspen Glen Development. These sinkholes appear similar to others
associated with the Eagle Valley Evaporite in areas of the lower Roaring Fork Valley.
A subsidence area was previously observed northeast of the subject lot. No evidence of cavities
was encountered in the subsurface materials; however, the exploratory borings were relatively
shallow, for foundation design only. Based on our present knowledge of the subsurface
conditions at the site, it cannot be said for certain that sinkholes will not develop or ground will
not subside in the unstable soil area. The risk of future ground subsidence within the designated
building envelope area of Lot F-19 throughout the service life of the proposed residence, in our
opinion, is low; however, the owner should be made aware of the potential for sinkhole
development and future ground subsidence especially in the northern area of the lot, outside of
the building envelope. If further investigation of possible cavities in the bedrock below the site
is desired, we should be contacted.
FIELD EXPLORATION
The field exploration for the project was conducted on March 23 and 24, 2021. Three
exploratory borings were drilled at the locations shown on Figure 1 to evaluate the subsurface
conditions. The borings were advanced with 4 inch diameter continuous flight augers powered
by a truck-mounted CME-45B drill rig. The borings were logged by a representative of Kumar
& Associates, Inc.
- 3 -
Kumar & Associates, Inc. ® Project No. 21-7-232
Samples of the subsoils were taken with 1⅜ inch and 2 inch I.D. spoon samplers. The samplers
were driven into the subsoils at various depths with blows from a 140 pound hammer falling 30
inches. This test is similar to the standard penetration test described by ASTM Method D-1586.
The penetration resistance values are an indication of the relative density or consistency of the
subsoils. Depths at which the samples were taken and the penetration resistance values are
shown on the Logs of Exploratory Borings, Figure 2. The samples were returned to our
laboratory for review by the project engineer and testing.
SUBSURFACE CONDITIONS
Graphic logs of the subsurface conditions encountered at the site are shown on Figure 2. The
subsoils were variable and below about ½ foot of topsoil consist of up to 6½ feet of granular fill
overlying very stiff, sandy clay with scattered gravel down to a depth of 4½ to 10 feet. Below
the clay, dense, silty sandy gravel with cobbles and probable boulders was encountered down to
the maximum explored depth of 14 feet. Drilling in the dense granular soils with auger
equipment was difficult due to the cobbles and boulders and drilling refusal was encountered in
Borings 2 and 3.
Laboratory testing performed on samples obtained from the borings included natural moisture
content and density, gradation analyses and Atterberg limits. Results of swell-consolidation
testing performed on a relatively undisturbed drive sample of the clay, presented on Figure 4,
indicate low to moderate compressibility under conditions of loading and wetting. Results of
gradation analyses performed on small diameter drive samples (minus 1½-inch fraction) of the
coarse granular subsoils are shown on Figures 5 and 6. The laboratory testing is summarized in
Table 1.
No free water was encountered in the borings at the time of drilling and the subsoils were
slightly moist to moist.
FOUNDATION BEARING CONDITIONS
The upper fill and clay soils encountered in the borings down to depths of about 5 to 10 feet
possess a low bearing capacity and typically low to moderate settlement potential when under
loading. The dense gravel soils encountered in the borings below 5 to 10 feet possess moderate
bearing capacity and typically low settlement potential. Spread footings placed on the upper
- 4 -
Kumar & Associates, Inc. ® Project No. 21-7-232
soils will have a risk of foundation movement possibly resulting in distress to the proposed
residence. We recommend removal of the upper fill and natural clay soils and placing spread
footings or compacted structural fill on the underlying gravel soils for support of the proposed
residence.
The borings drilled on the site do not indicate influence from the sinkhole and subsidence area
mapped northeast of the building envelope. If deeper than anticipated clay soils or soft areas are
encountered during construction, we should be contacted to further evaluate the bearing
conditions. Future ground subsidence in the unstable soil area shown on Figure 1 could indicate
sinkhole reactivation and the need for mitigation such as deep compaction grouting.
DESIGN RECOMMENDATIONS
FOUNDATIONS
Considering the subsurface conditions encountered in the exploratory borings and the nature of
the proposed construction, we recommend the building be founded with spread footings placed
on the natural dense gravel soils or compacted structural fill bearing on the natural granular soils.
The design and construction criteria presented below should be observed for a spread footing
foundation system.
1) Footings placed entirely on the undisturbed natural granular soils should be
designed for an allowable bearing pressure of 3,000 psf. Footings placed on
compacted structural fill should be designed for an allowable bearing pressure of
2,000 psf. Based on experience, we expect settlement of footings designed and
constructed as discussed in this section will be about 1 inch or less.
2) The footings should have a minimum width of 16 inches for continuous walls and
2 feet for isolated pads.
3) Exterior footings and footings beneath unheated areas should be provided with
adequate soil cover above their bearing elevation for frost protection. Placement
of foundations at least 36 inches below exterior grade is typically used in this
area.
4) Continuous foundation walls should be heavily reinforced top and bottom to span
local anomalies such as by assuming an unsupported length of at least 12 feet.
- 5 -
Kumar & Associates, Inc. ® Project No. 21-7-232
Foundation walls acting as retaining structures should also be designed to resist
lateral earth pressures as discussed in the "Foundation and Retaining Walls"
section of this report.
5) All existing fill, clay soils and any loose or disturbed soils should be removed and
the footing bearing level extended down to the relatively dense natural granular
soils. The exposed soils in footing area should then be moistened and compacted.
Structural fill placed to reestablish design bearing level should be compacted to at
least 98% of standard Proctor density.
6) A representative of the geotechnical engineer should observe all footing
excavations prior to concrete placement to evaluate bearing conditions.
FOUNDATION AND RETAINING WALLS
Foundation walls and retaining structures which are laterally supported and can be expected to
undergo only a slight amount of deflection should be designed for a lateral earth pressure
computed on the basis of an equivalent fluid unit weight of at least 50 pcf for backfill consisting
of the on-site soils. Cantilevered retaining structures which are separate from the residence and
can be expected to deflect sufficiently to mobilize the full active earth pressure condition should
be designed for a lateral earth pressure computed on the basis of an equivalent fluid unit weight
of at least 40 pcf for backfill consisting of the on-site soils. Backfill should be a predominantly
granular soil devoid of organics, clay soils and rock large than 6 inches.
All foundation and retaining structures should be designed for appropriate hydrostatic and
surcharge pressures such as adjacent footings, traffic, construction materials and equipment. The
pressures recommended above assume drained conditions behind the walls and a horizontal
backfill surface. The buildup of water behind a wall or an upward sloping backfill surface will
increase the lateral pressure imposed on a foundation wall or retaining structure. An underdrain
should be provided to prevent hydrostatic pressure buildup behind walls.
Backfill should be placed in uniform lifts and compacted to at least 90% of the maximum
standard Proctor density at a moisture content near optimum. Backfill in pavement and walkway
areas should be compacted to at least 95% of the maximum standard Proctor density. Care
should be taken not to overcompact the backfill or use large equipment near the wall, since this
- 6 -
Kumar & Associates, Inc. ® Project No. 21-7-232
could cause excessive lateral pressure on the wall. Some settlement of deep foundation wall
backfill should be expected, even if the material is placed correctly, and could result in distress to
facilities constructed on the backfill.
The lateral resistance of foundation or retaining wall footings will be a combination of the
sliding resistance of the footing on the foundation materials and passive earth pressure against
the side of the footing. Resistance to sliding at the bottoms of the footings can be calculated
based on a coefficient of friction of 0.45. Passive pressure of compacted backfill against the
sides of the footings can be calculated using an equivalent fluid unit weight of 400 pcf. The
coefficient of friction and passive pressure values recommended above assume ultimate soil
strength. Suitable factors of safety should be included in the design to limit the strain which will
occur at the ultimate strength, particularly in the case of passive resistance. Fill placed against
the sides of the footings to resist lateral loads should be a granular material compacted to at least
95% of the maximum standard Proctor density at a moisture content near optimum.
FLOOR SLABS
The natural on-site soils, exclusive of topsoil, are suitable to support lightly loaded slab-on-grade
construction. To reduce the effects of some differential movement, floor slabs should be
separated from all bearing walls and columns with expansion joints which allow unrestrained
vertical movement. Floor slab control joints should be used to reduce damage due to shrinkage
cracking. The requirements for joint spacing and slab reinforcement should be established by the
designer based on experience and the intended slab use. A minimum 4 inch layer of free-
draining gravel should be placed beneath basement level slabs to facilitate drainage. This
material should consist of minus 2 inch aggregate with at least 50% retained on the No. 4 sieve
and less than 2% passing the No. 200 sieve.
All fill materials for support of floor slabs should be compacted to at least 95% of maximum
standard Proctor density at a moisture content near optimum. Required fill can consist of the on-
site granular soils devoid of vegetation, topsoil and oversized rock.
UNDERDRAIN SYSTEM
Although free water was not encountered during our exploration, it has been our experience in
the area that local perched groundwater can develop during times of heavy precipitation or
- 7 -
Kumar & Associates, Inc. ® Project No. 21-7-232
seasonal runoff. Frozen ground during spring runoff can create a perched condition. We
recommend below-grade construction, such as retaining walls, crawlspace and basement areas,
be protected from wetting and hydrostatic pressure buildup by an underdrain system.
The drains should consist of drainpipe placed in the bottom of the wall backfill surrounded above
the invert level with free-draining granular material. The drain should be placed at each level of
excavation and at least 1 foot below lowest adjacent finish grade and sloped at a minimum 1% to
a suitable gravity outlet or drywell. Free-draining granular material used in the underdrain
system should contain less than 2% passing the No. 200 sieve, less than 50% passing the No. 4
sieve and have a maximum size of 2 inches. The drain gravel backfill should be at least 1½ feet
deep.
SURFACE DRAINAGE
The following drainage precautions should be observed during construction and maintained at all
times after the residence has been completed:
1) Inundation of the foundation excavations and underslab areas should be avoided
during construction.
2) Exterior backfill should be adjusted to near optimum moisture and compacted to
at least 95% of the maximum standard Proctor density in pavement and slab areas
and to at least 90% of the maximum standard Proctor density in landscape areas.
3) The ground surface surrounding the exterior of the building should be sloped to
drain away from the foundation in all directions. We recommend a minimum
slope of 6 inches in the first 10 feet in unpaved areas and a minimum slope of
3 inches in the first 10 feet in paved areas. Free-draining wall backfill should be
covered with filter fabric and capped with about 2 feet of the on-site finer graded
soils to reduce surface water infiltration.
4) Roof downspouts and drains should discharge well beyond the limits of all
backfill.
5) Landscaping which requires regular heavy irrigation should be located at least
5 feet from foundation walls.
Kumar & Associates
Kumar & Associates
Kumar & Associates
Kumar & Associates
Kumar & Associates
Kumar & Associates
TABLE 1
SUMMARY OF LABORATORY TEST RESULTS
Project No. 21-7-232
SAMPLE LOCATION NATURAL MOISTURE CONTENT
NATURAL DRY DENSITY
GRADATION
PERCENT
PASSING NO. 200 SIEVE
ATTERBERG LIMITS UNCONFINED COMPRESSIVE STRENGTH SOIL TYPE BORING DEPTH GRAVEL SAND LIQUID LIMIT PLASTIC INDEX (%) (%)
(ft) (%) (pcf) (%) (%) (psf)
1 7 & 10
combined 1.9 42 43 15 Silty Sand and Gravel
2 4 2.1 51 32 17 Silty Sand and Gravel (Fill)
7 17.7 90 38 21 Slightly Sandy Clay
3 6 15.7 110 Slightly Sandy Clay
7½ 17.4 113 90 Slightly Sandy Clay
10 3.9 43 39 18 Silty Sand and Gravel