Duct Test
Testing Company: Name:EnergyPro Insulation Address:2892 I -70 B Grand Junction, CO 81501 Phone: 970-623-7327 Technician: Name:Dennis Patterson Credentials: Email:dennispatt27@gmail.com Building Information: Project ID:Integrity Homes Address:51 Boulder Ridge Dr Parachute, CO 81635 Year Built:2026 Geo-Tag Data:Latitude: Longitude: Timestamp: Customer Information: Name:Integrity Homes Address:1380 North Ave Grand Junction, CO 81501 Phone: 970 255 6520 Email: zaneb@intergrityhomesgj.com Measured Leakage:2.45 CFM25/100 ft² Leakage Target:3.00 CFM25/100 ft² Compliance with Leakage Target:Pass Test ID:51 Boulder Ridge Dr Purpose of Test:Duct Total (IECC) Measured CFM25:49.0 Conditioned Floor Area:2,001.0 ft²AH Flow: 0.0 cfm Coefficient (C):7.1 Exponent (n): 0.600 (assumed) Test Standard:RESNET 380 Total Duct Leakage Test Mode: Pressurize Test Characteristics:Time Average Period: 10 seconds Test Date and Time:2026-03-02 13:17:52 Duct Leakage Test Test Readings: Target (Pa)Duct (Pa)Fan (Pa)Flow (cfm)Config 25.0 24.9 -62.3 48.8 Ring 3 Test Equipment: Flow Device:Duct Blaster B Fan Pressure Gauge:DG1000 Serial #: 14229 Calibration Date: 2023-06-14 Deviations from Standard: None Comments: None Duct Leakage Test Page 2 of 2Report by TEC Auto Test 1.10.0 (238), © 2024 The Energy Conservatory, Inc.