HomeMy WebLinkAboutCorrection Letter and 1st, 2nd Responses�i Q5T CoggF=00 t,r7e0— Garfield County Community Development Department 01 /16/2026 Owner: MMME WG LLC 6874 Highway 82 Glenwood Springs Co 81601 Guy Duplantier Architect: None Contractor: Gould Construction PO Box 130 Glenwood Springs, CO 81602 Re: Corrections and Conditions of Approval ,lob Address: 49893 Highway 6 &24 Dear Mr. Duplantier, The County Building Department has performed the review on the building permit application and plans for the new buildings proposed at the above address. There are items that need to be addressed prior to considering issuance of the building permit and items that can be addressed after the issuance of the building permit. Please provide a response letter addressing each item listed in the "Items to address prior to issuing a building permit". Response not required for the "Conditions to be addressed during construction" but please address if clarification is needed. Please provide 2 complete sets of corrected sheets, with clouded areas reflecting changes, for the resubmittal. 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (970)945-8212 Corrections to address prior to issuing a building permit: 1 Cover — The Code Summary is indicating the Snow Load as 40psf Ground Snow Load, the County's amendment is to accommodate 40psf Roof Snow Load. Please see the attached design criteria. Please change the drawings accordingly. 2 Cover — The Wind Speed is indicated as 105 mph; the county minimum is 115 mph. Please change the drawings accordingly. 3 B1.0 — The foundation is proposed without the required 36" of frost depth the County has adopted. Please change the drawings to accommodate the required frost depth. There is an allowance to utilize ASCE 32, which will require quite a bit of insulation to protect unheated buildings from frost heave. (2015 IBC 1809.5) 4 The IBC required 5% of the Self -Storage units to be accessible, 4 units in this phase. Please explain or show how that will be accommodated. (2015 IBC 1108.3) 5 A3.0 and 11.0 —The plans indicate an office enclosed by insulated walls. There is not enough detail to verify compliance with the 2018 International Energy Conservation Code. Please see the attached Insulation Table and indicate the following on the plans: • The type of insulation in the wall and R-Values • The type of insulation for the roof and R-Values • The U-Value for the door and window associated with the Office. • Provide details for the Slab Insulation with the type of insulation and R-Values. Also known as "Slab Edge Insulation" the IBC Commentary is included that explains the code and gives examples. If the Prescriptive Method of insulation cannot be achieved, then a ComCheck Report will be necessary to obtain compliance. 6 Please show on the plans the method of heating the office, please include the make a model of the heating appliance. (2015 IMC 303 and IECC C403) 7 Please explain or show how plumbing fixtures will be compliant. Please bear in mind that the restroom facilities are to be within 500'. (2015 IBC 2902 and 2902.3.2) 8 There is a letter in the submittal documents indicating that the City of Glenwood Springs will be providing water to the site. Please provide a "Will Serve Letter" from the City of Glenwood Springs. The city contact in the past has been Emery Ellingson in the Planning Department. (LUDC 7-104) 9 Please provide the CDOT Special Use/Utility Permit for the new water line in the right-of- way. 10 Please provide fence and gate details. (#6 of Resolution 2023-02) 11 Please provide a Geotech/Soils Report. (#7 of Resolution 2023-02) 12 Please submit the Landscape Plan. (#11 of Resolution 2023-02) 13 Please supply the Engineering Certification required in the Land Use Change Permit. (#14 of Resolution 2023-02) 14 Please have the engineer provide a statement of special inspection. (2015 IBC Chapter 7, 1704.2.3, 170511.2, 1705.12.3, and Table 1705.3) 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (970) 945-8212 15 Typically the code requires a Hazardous Materials Report be submitted. Compliance with this report is difficult as the storage for each tenant varies. A lease agreement has been submitted in past applications that limits/disallows hazardous material storage. Please submit a proposed lease agreement for verification. (2015 IBC 414) Conditions to be addressed during construction: The plans have been designed to the 2021 International Building Codes. The adopted codes in Garfield County are the 2015 International Codes except for the 2018 International Energy Conservation Code. The code analysis is to complies with the 2015 IBC. There could be conflicts in the different versions of the codes, I am not comparing codes during the review. The approved plans are to be on -site for inspections. Sanitary facilities are required to be provided for workers. A list of required inspections will be attached to the plans. The State is to permit and approve the electrical work. https://www.colorado.gov/pacific/dora/DPO Electrical Plumbing Permits Underground utility locates is the responsibility of the owner or contractor. 811 is the Colorado Utility Locate Hot Line. Separate Sign Permits are required for any external signs. Please see the County website for the application. Electrical Code compliance will be determined based on field inspections performed by the State Electrical Inspector, (303) 869-3458. Please have the inspector sign the building card or provide written documentation of the inspections. Any water supply that feeds a fire suppression systems or fire hydrants are to be inspected by the Fire Marshal prior to backfilling. Please provide special inspections reports to the Building Department as specified within the General Notes of the structural drawings. Geotechnical observation is required when the excavation is complete and written verification be supplied at footing inspection, 1500psf. Combustible material is limited in Type I and Type II Construction. See IBC 603 for allowed combustible materials. All exterior lighting is to be downcast and shielded. Safety glazing is not designated on the plans. Safety glazing will be checked during the framing and final inspection. (IBC 2406.4) A Knox Box is required to be mounted adjacent to the gate. Please contact the Local Fire District for exact location. All accessible door hardware shall have a shape that is easy to grip, including pocket and sliding doors. (ANSI A117.1 — 404.2.6) 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (970)945-8212 A passing blower door test for the office is required to be submitted prior to issuing the Certificate of Occupancy. The required landscaping and irrigation along the east side of the property is to be in place prior to the Final Building Inspection. A separate Building Permit is required for the Future Employee Housing shown on the Civil Drawings. All infrastructure piping and stormwater drainage is to be inspected by the engineer of record. A stamped letter from the engineer accepting all infrastructure installation is required prior to the final inspection. Sincerely, John Plano Building Official CC via email: Mark Gould Jr., Owner/Contractor Robin Pitt, Glenwood Fire Department Glenn Hartmann, Garfield County Community Development 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (970)945-8212 Garfield County Community Development Department 01 /16/2026 Owner: MMME WG LLC 6874 Highway 82 Glenwood Springs Cc 81601 Guy Duplantier Architect: None Contractor Gould Construction PO Box 130 Glenwood Springs, CO 81602 Re: Corrections and Conditions of Approval .lob Address: 49893 Highway 6 &24 Dear Mr. Duplantier, The County Building Department has performed the review on the building permit application and plans for the new buildings proposed at the above address. There are items that need to be addressed prior to considering issuance of the building permit and items that can be addressed after the issuance of the building permit. Please provide a response letter addressing each item listed in the "Items to address prior to issuing a building permit". Response not required for the "Conditions to be addressed during construction" but please address if clarification is needed. Please provide 2 complete sets of corrected sheets, with clouded areas reflecting changes, for the resubmittal. 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (970) 945-8212 Corrections to address prior to issuing a building_ permit: 1 Cover — The Code Summary is indicating the Snow Load as 40psf Ground Snow Load, the County's amendment is to accommodate 40psf Roof Snow Load. Please see the attached design criteria. Please change the drawings accordingly. 2 Cover — The Wind Speed is indicated as 105 mph; the county minimum is 115 mph. Please change the drawings accordingly. 3 131.0 — The foundation is proposed without the required 36" of frost depth the County has adopted. Please change the drawings to accommodate the required frost depth. There is an allowance to utilize ASCE 32, which will require quite a bit of insulation to protect unheated buildings from frost heave. (2015 IBC 1809.5) signed acknowledgement attached 4 The IBC required 5% of the Self -Storage units to be accessible, 4 units in this phase. Please explain or show how that will be accommodated. (2015 IBC 1108.3) ADA procedures by self storge operator attached 5 A3.0 and 11.0 — The plans indicate an office enclosed by insulated walls. There is not enough detail to verify compliance with the 2018 International Energy Conservation Code. Please see the attached Insulation Table and indicate the following on the plans: The type of insulation in the wall and R-Values The type of insulation for the roof and R-Values ® The U-Value for the door and window associated with the Office. Provide details for the Slab Insulation with the type of insulation and R-Values. Also known as "Slab Edge Insulation" the IBC Commentary is included that explains the code and gives examples: If the Prescriptive Method of insulation cannot be achieved, then a ComCheck Report will be necessary to obtain compliance. office has been eliminated 6 Please show on the plans the method of heating the office, please include the make a model of the heating appliance. (2015 IMC 303 and IECC C403) office has been eliminated 7 Please explain or show how plumbing fixtures will be compliant. Please bear in mind that the restroom facilities are to be within 500'. (2015 IBC 2902 and 2902.3.2) office has been eliminated 8 There is a letter in the submittal documents indicating that the City of Glenwood Springs will be providing water to the site. Please provide a "Will Serve Letter" from the City of Glenwood Springs. The city contact in the past has been Emery Ellingson in the Planning Department. (LUDC 7-104) Attached 9 Please provide the CDOT Special Use/Utility Permit for the new water line in the right-of- way. Correspondence attached, utility permit should not be required for a building permit especially given that this is under three jurisdictions 10 Please provide fence and gate details. (#6 of Resolution 2023-02) attached 11 Please provide a Geotech/Soils Report. (#7 of Resolution 2023-02) attached 12 Please submit the Landscape Plan. (#11 of Resolution 2023-02) attached 13 Please supply the Engineering Certification required in the Land Use Change Permit. (#14 of Resolution 2023-02) Site work is not 100% complete, we do not want to bother the county 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (970)945-8212 with an additional grading permit, we are asking to complete the site work under the building permit. Engineering Certification will be provided upon completion of site work prior to CO 14 Please have the engineer provide a statement of special inspection. (2015 IBC Chapter 7, 1704.2.3, 170511.2, 1705.12.3, and Table 1705.3) 15 Typically the code requires a Hazardous Materials Report be submitted. Compliance with this report is difficult as the storage for each tenant varies. A lease agreement has been submitted in past applications that limits/disallows hazardous material storage. Please submit a proposed lease agreement for verification. (2015 IBC 414) attached Conditions to be addressed during construction: The plans have been designed to the 2021 International Building Codes. The adopted codes in Garfield County are the 2015 International Codes except for the 2018 International Energy Conservation Code. The code analysis is to complies with the 2015 IBC. There could be conflicts in the different versions of the codes, I am not comparing codes during the review. The approved plans are to be on -site for inspections. Sanitary facilities are required to be provided for workers. A list of required inspections will be attached to the plans. The State is to permit and approve the electrical work. httr)s://www.colorado_gov/pacific/dora/DPO Electrical Plumbing Permits Underground utility locates is the responsibility of the owner or contractor. 811 is the Colorado Utility Locate Hot Line. Separate Sign Permits are required for any external signs. Please see the County website for the application. Electrical Code compliance will be determined based on field inspections performed by the State Electrical Inspector, (303) 869-3458. Please have the inspector sign the building card or provide written documentation of the inspections. Any water supply that feeds a fire suppression systems or fire hydrants are to be inspected by the Fire Marshal prior to backfilling. Please provide special inspections reports to the Building Department as specified within the General Notes of the structural drawings. Geotechnical observation is required when the excavation is complete and written verification be supplied at footing inspection, 1500psf. Combustible material is limited in Type I and Type II Construction. See IBC 603 for allowed combustible materials. All exterior lighting is to be downcast and shielded. Safety glazing is not designated on the plans. Safety glazing will be checked during the framing and final inspection. (IBC 2406.4) 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (970) 945-8212 A Knox Box is required to be mounted adjacent to the gate. Please contact the Local Fire District for exact location. understood All accessible door hardware shall have a shape that is easy to grip, including pocket and sliding doors. (ANSI All 17.1 — 404.2.6) understood A passing blower door test for the office is required to be submitted prior to issuing the Certificate of Occupancy. Office has been eliminated The required landscaping and irrigation along the east side of the property is to be in place prior to the Final Building Inspection. understood A separate Building Permit is required for the Future Employee Housing shown on the Civil Drawings. understood All infrastructure piping and stormwater drainage is to be inspected by the engineer of record. A stamped letter from the engineer accepting all infrastructure installation is required prior to the final inspection. understood Sincerely, John Plano Building Official CC via email: Mark Gould Jr., Owner/Contractor Robin Pitt, Glenwood Fire Department Glenn Hartmann, Garfield County Community Development 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (970) 945-8212 TBS TRACHTE 6Z Building Systems O February 19, 2026 Mark Gould PO Box 130 Glenwood Springs, CO RE: Storage buildings for Glenwood Springs, CO (Trachte Plan #62146) Dear Mr. Gould: This letter is in response to comments made by Garfield County relating to the self -storage permit for Hwy 6 & 24, Glenwood Springs, CO. We have listed each comment as an "ITEM" followed with our "RESPONSE" that pertains to our scope of work. ITEM 1: Cover Sheet RESPONSE: The building calculations have been revised to IBC 2015 with 40psf Roof snow load. All pertaining documents have been updated accordingly. ITEM 2: Cover Sheet RESPONSE: The wind speed has been updated from 105mph to 115mph. Please refer to the revised building calculations and code summary. ITEM 3: Foundation Plan RESPONSE: We have enclosed a foundation letter. ITEM 4: Table 1108.3 Accessible Self -Service Storage Facilities RESPONSE: There is a total of 614 units on the proposed buildings and the calculation for accessible units is 10 + 2% of units over 200, Table 1108.3 of IBC 2015. The number required would be 10 + 0.02*(614-200) =18.28 units or 19 units. We have added 19 units of accessible units to the floor plans. ITEM 5: Roof and Wall Insulation Information RESPONSE: The office from Building A3 has been removed so this provision of -the code is not applicable. ITEM 11: Geotech/Soil Report RESPONSE: This is outside the scope of Trachte Buildings Systems and will be addressed by others. However, Trachte must be informed if the soil report indicates an allowable pressure to be less than the 1500psf that is currently used in design. ITEM 14: Statement of Special Inspection RESPONSE: We have enclosed the statement of inspection form. 314 Wilburn Road • Sun Prairie, WI 53590 P: 800.356.5824 • F: 800.981.9014 • E: tbs@trachte.com • W: trachte.com TRS TRACHTE 6010 Building Systems If you have any questions or need additional information, please contact Jeff Bouchard, or myself at (800) 356-5824. Sincerely, Joel G. oward Professional Engineer JGH:CZR enclosures OAEG/ 9/2026 314 Wilburn Road • Sun Prairie, WI 53590 P: 800.356.5824 • F: 800.981.9014 • E: tbs@trachte.com • W: trachte.com -?L,p5Rsh,sit -M Z►afl Lu7vq, Garfield County Community Development Department 02/25/2026 Owner: MMME WG LLC 6874 Highway 82 Glenwood Springs Co 81601 Guy Duplantier Architect: None Contractor: Gould Construction PO Box 130 Glenwood Springs, CO 81602 Re: Corrections and Conditions of Approval .lob Address: 49893 Highway 6 &24 Dear Mr. Duplantier, The County Building Department has performed a review on the resubmitted plans addressing the comments from the correction letter dated 01/16/2026 for the new buildings proposed at the above address. There are items that were not addressed adequately. Prior to considering issuance of the building permit further attention to these items is needed. Item address adequately has been removed. Please provide a response letter addressing each item listed in the "Items to address prior to issuing a building permit". Response not required for the "Conditions to be addressed during construction" but please address if clarification is needed. Please provide 2 complete sets of corrected sheets, with clouded areas reflecting changes, for the resubmittal. 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (970)945-8212 Corrections to address prior to issuing a building permit: The physical resubmittal only included (2) sets of 6 sheets. Several more sheets were revised while addressing comments. Please submit all revised sheets. Missing sheets: A1.0, A2.0, A3.0, A4.0, A5.0, A8.0, A10.0, B1.0, B1.1, B1.2, B1.3, B1.4, C1.0, C1.1, C1.2, C1.3-new sheet, C1.4-new sheet,C2.2, C3.1, C3.2, C3.3, Stopped the comparison. Based on the extent of the changed sheets, Please resubmit (2) FULL sets of coordinated plan sets. Civil Drawings are unchanged and are not required to be resubmitted. Resubmitted 2 Full Physical Sets and one Digital. 1 Cover — The Code Summary is indicating the Snow Load as 40psf Ground Snow Load, the County's amendment is to accommodate 40psf Roof Snow Load. Please see the attached design criteria. Please change the drawings accordingly. The digital drawings and the physical drawings still display 40psf Ground Snow Load. Please revise both the digital and submit revised sheets. Corrected See physical and digital Resubmission 11 Please provide a Geotech/Soils Report. (#7 of Resolution 2023-02) A Geotech/soils Report was not found in the resubmittal. Submitted 2 physical and 1 digital see File 19-7-437 (08-20-19) Subsoil Study Conditions to be addressed during construction: The plans have been designed to the 2021 International Building Codes. The adopted codes in Garfield County are the 2015 International Codes except for the 2018 International Energy Conservation Code. The code analysis is to complies with the 2015 IBC. There could be conflicts in the different versions of the codes, I am not comparing codes during the review. The approved plans are to be on -site for inspections. Sanitary facilities are required to be provided for workers A list of required inspections will be attached to the plans. The State is to permit and approve the electrical work. https://www.colorado.gov/pacific/dora/DPO Electrical Plumbinq Permits Underground utility locates is the responsibility of the owner or contractor. 811 is the Colorado Utility Locate Hot Line. Separate Sign Permits are required for any external signs. Please see the County website for the application. Electrical Code compliance will be determined based on field inspections performed by the State Electrical Inspector, (303) 869-3458. Please have the inspector sign the building card or provide written documentation of the inspections. 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (970)945-8212 Any water supply that feeds a fire suppression systems or fire hydrants are to be inspected by the Fire Marshal prior to backfilling. Please provide special inspections reports to the Building Department as specified within the General Notes of the structural drawings. Geotechnical observation is required when the excavation is complete and written verification be supplied at footing inspection, 1500psf. Combustible material is limited in Type I and Type II Construction. See IBC 603 for allowed combustible materials. All exterior lighting is to be downcast and shielded. Safety glazing is not designated on the plans. Safety glazing will be checked during the framing and final inspection. (IBC 2406.4) A Knox Box is required to be mounted adjacent to the gate. Please contact the Local Fire District for exact location. All accessible door hardware shall have a shape that is easy to grip, including pocket and sliding doors. (ANSI A117.1 — 404.2.6) A passing blower door test for the office is required to be submitted prior to issuing the Certificate of Occupancy. The required landscaping and irrigation along the east side of the property is to be in place prior to the Final Building Inspection. A separate Building Permit is required for the Future Employee Housing shown on the Civil Drawings. All infrastructure piping and stormwater drainage is to be inspected by the engineer of record. A stamped letter from the engineer accepting all infrastructure installation is required prior to the final inspection. The County is in receipt of the compaction reports that were performed during the Grading Permit. The condition below, from the Resolution, is to be satisfied prior to the final inspection approval for the structures. 14. Prior to the issuance of building permits, the applicant shall provide engineering certification that all site improvements including but not limited to rockfall protection, debris flow mitigation and associated structures and fire protection system to include the 4 hydrants and water storage tank have been installed and completed. Sincerely, P444 ;V&" John Plano 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (970)945-8212 Building Official CC via email: Mark Gould Jr., Owner/Contractor 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (970)945-8212