Loading...
HomeMy WebLinkAboutBlower Door TestResidential Air Infiltration Test Report Test date:11/5/2025 Project name:1887 Cty Rd 237 Address:1887 Cty Rd 237, Silt CO Garfield Code:2018 IECC Conditioned volume:11,799 Cubic Feet Attic:vented attic Crawlspace:NA Garage:excluded Measured airflow:571 CFM50 Cubic Feet per Minute at 50 Pascal Temperature; Inside:65 Temperature; Outside:57 Elevation:5,950 Corrected airflow:581 CFM50*Cubic Feet per Minute at 50 Pascal 2015 IECC maximum allowed leakage rate:3.0 ACH50 Air Changes Per Hour at 50 Pascal Tested air leakage rate:3.0 ACH50 Air Changes Per Hour at 50 Pascal Test code compliance:PASS Test notes: Tests were performed by Chris Taylor; Rated Field Inspector, RFIIN #CY5MPL * Test results have been corrected for elevation and air density temperature differential. final blower door test