Septic System Inspection Report
Property Address: 91 Michels Circle, No Name, Colorado
Inspection Date: October 16, 2025 – Revisions made March 27, 2026
Inspector: Altitude Septic
System Description:
• Septic Tank: 1,250-gallon concrete tank 2 compartment
• Risers: Inlet riser: 3 feet to the surface Outlet riser: 30 inches to the surface
• Inlet Line: Cast iron
• Outlet Line: Cast iron
Inspection Findings:
During inspection, the septic tank was found to be failing due to a visible leak along the mid-seam of the tank.
The tank contained only approximately 2 feet of liquid and one foot of solids which indicates that effluent is
escaping through the crack rather than maintaining proper operating levels.
Both inlet and outlet sewer lines were video inspected:
• Inlet Line: Constructed of cast iron. The line appears functional and intact at this time.
• Outlet Line: Also constructed of cast iron but found to be in very poor condition, with several sections
partially filled with dirt and debris, suggesting possible breaks or infiltration.
The leach field area could not be located or accessed during this inspection; therefore, its condition could not be
verified. -On 3/27/26, we were able to locate a drywell. Drywell appeared to be in good condition, but was dry
due to the line being broken.
System Condition:
• Tank: Failed — leaking from mid-seam.
• Inlet Line: Fair condition.
• Outlet Line: Poor condition — partially collapsed or obstructed.
• Leach Field: Unknown — unable to access or evaluate. -Went back 3/27/26 and located a drywell. Pipe
is broken.
Recommendations:
1. Replace the septic tank due to structural failure and leakage.
2. Replace or repair the outlet line, as it is compromised and allowing dirt intrusion.
3. Locate and evaluate the leach field to determine its current condition and functionality. – 3/27/26 Repair
line to drywell
4. Install new risers and lids as needed once system repairs or replacements are completed.
Overall System Status:
System Fails — Septic tank leaking at mid-seam and outlet line in poor condition.
Altitude Septic, LLC
Please be aware of the following disclaimer: Altitude Septic accepts no responsibility for the proper operation of this septic system. The septic system is the
property of the homeowner who is responsible for the maintenance and operation of the system. This inspection does not constitute a guarantee nor is
any warranty expressed or implied that the system will function properly in the future. Altitude septic can only make observations based on the condition
of the septic system at the time of inspection and will make no prediction on the future functionality of any part of the septic system. The normal life
expectancy of a septic system is 25 years.