HomeMy WebLinkAboutEngineer's OWTS Design PlanCB0.1- April 10, 2026 129 CAINS LANE CARBONDALE, CO a 1623 970.309.5259 CA RLA.OSTBE=RG C?)G MA[ L.CO M Milton Arroyo realtormiltonarroyo0cimail.com Project No. C2025 Verification of Soils and Location of Waterline for Onsite Wastewater Treatment System (OWTS) Design 3-Bedroom Residence 144 Navajo Street Garfield County, Colorado Milton, CBO Inc. has completed an onsite wastewater treatment system (OWTS) design for the subject residence. Documents dated February 24, 2026 should be followed. In this letter, we describe verification of the soils, locate the water line, and clarify the depth of the required liner on the south side of the soil treatment area (STA). The 0.152-acre property is located outside of New Castle, in an area where OWTSs are necessary. Legal Description: Section: 25 Township: 5 Range: 91 Subdivision: ELK CREEK DEV. Block: 3 Lot: 9 UNIT 1 Parcel ID: 2125-251-02-009 WATERLINE LOCATION The residence is served by a community water system. The water meter is indicated on the survey in the northwest comer of the property. As shown, the water meter or curb stop is approximately 36-feet from the proposed STA. The water line runs to the east and enters the northern portion wall of the residence. A minimum 25-foot separation from the proposed STA to the waterline must be maintained. SUBSURFACE The subsurface was investigated on April 10, 2026 by digging one soil profile test pit excavation (Test Pit). Only one Test Pit was excavated due to the limited space available on the property. A visual and tactile soil analysis was completed by Carla Ostberg at the time of excavation.' The materials encountered in Test Pit #1 consisted of medium loamy topsoil and rootzone to 3.0-feet, underlain by medium brown loam to a maximum depth explored of 6.0-feet. No bedrock or groundwater was encountered. The existing STA (chambers) was encountered at approximately 5.0-feet below native grade. There was evidence of sludge in the chambers, but because the house has been vacant for several months, the soils were not saturated. A sample of the soil was taken from Test Pit #1 at 3-feet below grade. Soil structure grade was moderate. The soil formed a ball and a ribbon approximately 1-inch in length before breaking. Soil structure shape was blocky and consistence was friable. Soil texture was both gritty and smooth. ' Carla Ostberg holds a Certificate of Attendance and Examination from the CPOW Visual and Tactile Evaluation of Soils Training. Page 2 The soil is consistent with Soil Type 2, Loam, with moderate structure grade. A long-term acceptance rate (LTAR) of 0.6 gallons per square foot was used to design the STA. This sizing is appropriate based on verification of the soil. Test Pit #1 between the septic tank and existing STA 1 existing STA encountered Page 3 Yam-. + �,• r�`. ;��.."�,:- ' =�(��� � � � •„� , �J, R is IM Sieved sample -1 1 V44. Ribbon less than 1-inch CLARIFICATION OF LINER INSTALLATION r 5' A 30 mil PVC liner must be installed on the downhill (south side) of both beds. The liner will be installed at the edge of the beds to a depth level with the lowest portion of the first tier of the retaining wall to the south. PERMIT APPUC Al ION INS 1 RUCTIONS An OWTS Permit Application must be submitted to Garfield County Environmental Health Department. htt s://www. arfiield-count .com/environmental-health/ iles cco/sites/16/OWTS-A Iication-Com lete- Packet-Dec.-2019.pdf. If the OWTS Permit Application will be submitted with a Building Permit Application, it should be submitted directly to Garfield County Building Department. All questions regarding permit submission can be directed to Garfield County Environmental Health Department, 970-945-6614 x8150. Please call with questions. Sincerely, CBO Inc. 0a X, (a N't h u, 8 Carla Ostberg, MPH, REHS I a E, o a a zozCf c m m o M (Q7 cn 06 N p m CD a . o � f1 I mmw S O [O0E- r 1A �N O-- mmr KO� D D ncn =v n mmc� �0 --- — _ =z Z zZ m ID m=- mA�^ f �0 Omn I II � om0111- � m =v m-� v Oz = NAVAJO STREET 09 II m zLYrA "E m0m o 60.00' mrnmn zzmD mzr �.47.'i31W r- n Or D r r m m �° —EEE� z T N O b A c P 2 mo m o n� >Q z O m MO D Z D D� < Z m I _CD nm 0c i vi z j �p 3_ A L) x ? D O �o_m r�r 1m O� �m D;o r z m -i O co D 129 CAI INS LANE CARBONDALE, CO 81623 970.309.5259 �.I�;+�� ,k r � C:AF�LA.CJSI-BE.f�GLjGNlA1L.C.UNI February 24, 2026 Project No. C2025 Milton Arroyo reallormiltonarrgymiDgmaiLcom Onsite Wastewater Treatment System Design 3-Bedroom Residence 144 Navajo Street Garfield County, Colorado Milton, CBO Inc. has completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 0.152-acre property is located outside of New Castle, in an area where OWTSs are necessary. Legal Description: Section: 25 Township: 5 Range: 91 Subdivision: ELK CREEK DEV. Block: 3 Lot: 9 UNIT 1 Parcel ID: 2125-251-02-009 SITE CONDITIONS The property is currently developed with a 3-bedroom residence. The residence is served by an existing OWTS which was inspected by Voskuil Operations on December 29, 2025. The OWTS consists of a 1000-gallon, two -compartment Copeland Concrete septic tank followed by a soil treatment area (STA) with gravelless chambers (permit is difficult to read). The system was sized to accommodate 3 bedrooms. Garfield County Individual Sewage Disposal Permit 2189 documents the system. The permit received final approval on December 1, 1993. The inspection report is enclosed with recommendations, including replacing the STA due to failing the hydraulic load test. The residence is served by a community water system. The water meter is indicated on the survey in the northwest corner of the property. As shown, the water meter or curb stop is approximately 36-feet from the proposed STA. The water line should be located as part of the layout of the proposed STA to assure the 25-foot setback is maintained. The manufactured home has been placed on footers and stacked cinder blocks. The proposed STA is approximately 13.5-feet from the manufactured home. A retaining wall has been constructed along the southern portion of the property. A 30 mil PVC liner will be installed on the southern portion of the proposed STA to prevent lateral migration of effluent towards the retaining wall. The proposed soil treatment area (STA) location is vegetated with grasses as part of the yard area. Page 2 There should be no traffic or staging of material over the future STA site to avoid compaction of soils prior to construction of the STA. SUBSURFACE To minimize disturbance in the area of the proposed STA, we have utilized previous soil investigations and other resources to assess soils for sizing the STA. A Test Pit must be excavated prior to installation of the STA. This office must be called to verify soils are consistent with what has been outlined in this design. If soils are not consistent with our assumptions, design changes may be necessary. We have researched soils in the area through USGS Web Soil Survey. The report is enclosed. The area of the proposed STA is identified by map unit symbol 58. The map unit name is Potts-Ildefonso complex, 12 to 25% slopes. Typical soil profile from 0 to 4-inches consist of loam, 4 to 28-inches consist of clay loam, and 28 to 60-inches consist of loam. Garfield County ISDS Permit 2189 documents the percolation rate of 27 to 30 minutes per inch (MPI). Based on information provided from the available documented resources and our knowledge of soils in the area, we are assuming soils to be consistent with Soil Type 2. A long-term acceptance rate (LTAR) of 0.6 gallons per square foot will be used to design the STA. Soils must be verified by this office prior to construction of the STA. Photos provided document soils on a property (112 Navajo Street, Parcel ID: 2125-251-02-018) located approximately 200-feet south of the subject property. A seepage pit was installed, with excavation extending approximately 10-feet below native grade. Soils were consistent with light brown loam to sandy loam with minimal rock content. Page 3 4 3.:.: '- Photos of excavation at 112 Navajo Street - DESIGN SPECIFICATIONS Recommendations from Voskuil Operations inspection report dated December 29, 2025, Correct the slope (due to belly) in the 3" sewer pipe under residence. Install exterior cleanout between residence and septic tank. Replace the broken concrete lid on the outlet side of the septic tank. Install a new stainless -steel handle on the inlet side of the septic tank. Install effluent filter on outlet side of septic tank. Replace STA. Page 4 ❑esi n Calculations: Average Design Flow = 75 GPD x 2 people/bedroom x 3 Bedrooms = 450 GPD LTAR = 0.6 GPD/SF 450 GPD / 0.6 GPD/SF = 750 SF x 1.2 (gravity, bed) x 0.7 (chambers) = 630 SF 630 SF / 12 SF/chamber = min. 53 `Quick 4' Infiltrator@ chambers The OWTS design is based on 3-bedrooms. An average daily wastewater flow of 450 GPD will be used. For the purposes of this OWTS design, Benchmark Elevation has been established as 100' (existing sewer line exiting residence). CBO Inc. should be notified of any discrepancies or problems with grade elevations of proposed components during installation of the OWTS. OWTS Component Primary Tank Inlet Invert Distribution Box Minimum Elevation Approximate horizontal distance 13' / SEWER LINE EXISTING / V of risers on existin septic tank Approximate horizontal distance 40' / min min. 5" fall 1%fall / Infiltrative Surface Approximate horizontal distance 11' / min. 1% tall to STA / min. 1.375" fall *Elevations are based upon standard OWTS installation practices. Component elevations may change during installation due to site conditions. Minimum grade refers to piping between components. The existing 3-inch diameter sewer line under the residence should be corrected to eliminate the belly and achieve the correct slope. This sewer line will tie into the existing 4-inch sewer line. A double -sweep clean out must be installed on the sewer line between the residence and the septic tank. The sewer line must have a minimum 2% grade to the septic tank. The existing septic tank will remain. The manhole lids must be repaired and/or replaced. An Orenco® Biotube effluent filter must be installed on the outlet tee. The existing STA will be abandoned in place. If saturated soils are encountered, the soils should be excavated and staged for drying prior to disposal. If over -excavation is necessary in the proposed STA, soils may be replaced with concrete (washed) sand. Sand filter material must be clean, coarse sand, all passing a screen having four meshes to the inch. The sand must have an effective size between 0.15 and 0.60 mm. The uniformity coefficient must be 7.0 or less. Material meeting ASTM 33, for concrete sand, with three percent or less fines passing 200 mesh sieve may be used. If needed, a gradation of the sand media must be submitted to this office prior to obtaining the sand. Effluent will gravity flow to a distribution box, and then to two gravelless chamber beds. The distribution box must be accessible from grade and must have flow equalizers, or similar product, installed on each outlet pipe in the distribution box to assure equal flow to each bed. Each chamber bed will consist of 4 rows of 7 'Quick 4' Infiltrator@ Low Profile chambers for a total of 56 chambers and 672 square feet of infiltrative area. A 4-inch diameter SDR-35 level manifold must be installed to connect two rows in each bed (see W3.1 Chamber Bed Plan). Inspection ports must be installed at each corner of the beds. Ports may be cut to grade and placed in sprinkler boxes for access. A 30 mil PVC liner must be installed on the downhill (south side) of both beds. The installer should work with this office to determine the best placement of the liner to protect from lateral migration of effluent. Page 5 COMPONENT SPECIFICATIONS The component manufacturers are typical of applications used by contractors and engineers in this area. CBO Inc. must approve alternative components prior to installation of the OWTS. Requests must be submitted, in writing, to our office for approval prior to installation. Component technical data sheets are available upon request. COMPONENT MANUFACTURER MODEL NO. COMMENTS Effluent Filter Orenco@ Full size, 4-inch diameter Distribution Box Polylok Distribution box, risers, lid and 4 flow equalizers m Chabers Infiltrator@ 'Quick 4' us Standard Low Profile chambers 56 'Quick 4' chambers Construction must be according to the jurisdiction's adopted On -Site Wastewater Treatment System Regulations, the OWTS Permit, and this design. PERMIT APPLICATION INSTRUCTIONS An OWTS Permit Application must be submitted to Garfield County Environmental Health Department. https://www.garfield-county-com/environmental-healtli/filesgcco/sites/I6/OWTS-A olication-Complete= Packet-Dec.-2019.radf. If the OWTS Permit Application will be submitted with a Building Permit Application, it should be submitted directly to Garfield County Building Department. All questions regarding permit submission can be directed to Garfield County Environmental Health Department, 970-945-6614 x8150. VALIDITY PERIOD OF DESIGN DOCUMENTS This design is valid for submission of an application for permitting for l.vvo (2) years from the date of the design packet or upon a change in the county OWTS Regulation that could impact compliance with code requirements. Continued use beyond this period or following a change in the regulation is not recommended without review and update of design documents. INSTALLATION CONTRACTOR CBO Inc. expects that the installer be experienced and qualified to perform the scope of work outlined in this design. The installer must review this design thoroughly and coordinate with our office in advance of installation. Any additional conditions in this design or county permit must be completed and documented prior to final approval of the OWTS installation. Communication between the installer and this office is expected throughout the installation. INSTALLATION OBSERVATIONS CBO Inc. must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. CBO Inc. should be notified 48 hours in advance to observe the installation. In an effort to improve the accuracy of the record drawing, we request that the installer provide a sketch of the installation, including path of the sewer lines, water line installation (if applicable), septic tank location, STA location, and measurements from building corners or another fixed objects on the property. This sketch is most easily provided on Sheet W2.0 of the OWTS Design Page 6 Packet. Photographs of the installation and final cover are also requested to supplement our installation documentation. REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irrigation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo-fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials should be placed on the backfilled STA. Machines with tracks (not wheels) should be used during construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. If an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. If the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non -biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES If design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high- water conditions and shall be connected to a control breaker separate from the high-water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in the excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3-inch. LIMITS: The design is based on information submitted. If soil conditions encountered are different from conditions described in this report, CBO Inc. should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Page 7 Please call with questions. Sincerely, CBO Inc. Carla Ostberg, MPH, REHS r-00 i � z m 1 w x z z 1 m i ��m I u —� Z ozc o �• N;� U) �:U N co b �n�•5 mom ' QJN N N Gi Z - f1 3 nmi o I 0 o m W D s A, C Ta�� z 0z =°•coo m c O W cn n o m a N N N ^ , U p ci O m r z m NAVAJ O STREET -�- -�--� NO2'23' 1 1 "E 60.00' m ■Ems MUM MINE loss NONE MEN NONE ■og■ ti MEOW M D D m 74. zz -u T I! /\ :j 1 60.00' m z co V r ;a CA) m60 �2m 00 mX z0 00 mg: m d 0 s 3 O Z t ) z 4) c o 3 m v (p (� o m Q No o m m n r. 7 o CD 00 0 m wto m r n 0 Q N r 0m o �00 co m O 0) (n -n m ` C N N -� o � 0 { p O* �O DC) D a m 0 I m DD m� i O� 0� x 0 �+ OC z co 0 III O w ---- — •— -- -- - m n D S � m r O Z :0 vt Z z --- - --- -- -- - -- b Z �O m 030 mx 0 �- mx T.F - O -- -- --- - --- - -^-- mcm) .Z1D `n m ? m cod my Oz • NAVAJO STREET Do o o1 1 Km m �O D o z ' NO2'231 1" 60.00 pNW�N m O - u x m O m �Z w0 en mD m m zz m-i ri ? c V A -ta rsN I ? D O O cn ma O--1 mLa oC i O z r z m 0 0 D- m x co m 0 m CD o mo m� �D Or �O Z Z 00 mn m0 3 D K, .D z D n� �m mm mz rn m m m mm x m m D z O 0 O x m D z D m m K m m X *2 xLU nw me � z �o . G) X ?D 0 0 r W r �+ �cn og mm D X r z m 1 O 1 D cn D m N I O W > � `^ \ \0 zU) _ �f 2q)§§ . §9mo0 /�{2\ §§ [��§ ( ean- _ - [§ §§ coz rn k¢\) §\ mo, )©! °° �- 0�0 % /f; .a m ° ! q M( -- >® (% - §] 0. i ? o � � R } \ ) O x 2 m § \§ 2 . 7 ( \ \M \ )k) (k /7) / ) §m :)§ :) ®! 2§| k( | ! e 2§ ® M� �\ _ o _ m ) _ 7/] ,! °o ) ,g i! ��)\ co E 0 m0 \ 2{ k f q)2| : zoz■ ` § C, \ \\n C) ak°R ° e ( en �\) §`® \( \ k§§ On \ �0 ° %d ° �� ` a ,§% © ® ! / § .` ) § ~ - � - - 2 f m 2 $ - %§ =§2 m 0 ;;o 9 9 035 \ aD / \ \\ .,0 cl g F Z. E\ 2 3 m / � 2 � n O \}M>00 \ § ` > \ / m q%-n v JS2\ o >mm \ \xk /«w 2 ®©E 2§§ j! #ky\/m o $mom �0m 0)0 ��/�T> \ \�5 Blees J� /& �23@>m > ,@z (pa. $ ® �I�%§> R �§m k§}� \) - };o0 Z 9 2 3 _ �� - 2®xi§± ®o (�) \ Go \ 0 / �. ` \/� \ 03 m § ] K q d " > � o r ° o a2 -G 2 \ § ± \ $ § -n / / o $ z } � > £ § � �e D \ a cn znz■ {BCD k\ \0 \ § CL k ( § a(�§ ` ° k O §� \ 2 40 U) `O m @ '\j cMw co \ - _§mg § J ) CA § 2 \ k ,00 ;§\ (CD jf \cn 0 0 2 D f � n O ) 2) § � k § GS)4- ƒ \ / � k k � � ( m � § \� § ) ) 4 ]2 ) i � k )) � ) I §$ ` ` ° �§ § m\ f q - ; 2 k§ \ �) � apS DRAIN �yt 40 0C% : w EST. 2011 VOSKUIL OPERATIONS • OWTS (Onsite Wastewater Treatment System) Inspection Report Prepared For: Joy White joy@ masonmorse.com Address: 144 Navajo St, New Castle, CO 81647 Date Inspected: December 29, 2025 Observations/Results: - At the time of inspection, the septic tank has not been pumped. The three -bedroom residence is currently occupied. A two-way exterior cleanout was located in the front yard off the porch (southeast side of residence) just downstream from the septic tank. There is a drain grate as the cap for the cleanout. - There is no exterior cleanout present between the residence and the septic tank and we were unable to inspect this portion of the sewer line. The septic tank is located in the front yard on the southeast side of the residence. Garfield County records show final inspection of the tank and system components in December 1993 (see additional documents at end of report). Both concrete lids were at surface grade. The concrete tank is a dual compartment style with 2 concrete lids for access. The lid on the outlet side of the septic tank is broken and cracked. The handle on the lid of the inlet side of septic tank is rusted out of the concrete. The approximate tank capacity is 1000 gallons. The concrete risers were probed and found solid at time of inspection. The inlet pipe is located under the top of the tank. ~ ' E . Y fin• �'�:� �• . i�•,`, yr fit_ ,}:_:• f # ?r r»Fr �f�: •max. %� ��� .�i �_• •' , r t ,,,� + } �; •! ley .� - r'�� a s���� 161 0, VIEW sue:+ �. - :A4F �. 'i-. •c •. �,'��� , . _. k�:.u, �'' � ti.' - ~ti , b We video inspected from the cleanout under the residence downstream approximately 50 feet, but unable to round the corner where the sewer line exits from under the residence. The pipe consists of 3" ABS sewer pipe under the residence before transitioning to 4" sewer pipe as it leaves the residence. There is a belly in the 3" section of ABS sewer line under the residence just downstream from the cleanout. We video inspected from the exterior cleanout located downstream of the septic to the manifold until we could not push the camera to continue the inspection due to several bends. The discharge pipe consists of 4" PVC pipe to the manifold and STA (soil treatment area). Hydraulic Load Test: Using a garden hose, we applied 135 gallons of water at a rate of 9 gallons per minute down the exterior cleanout on the discharge side of septic tank. Water was back flowing into the septic tank outlet at 15 minutes and STA was not accepting flow. Recommendations: - Because the soil treatment area did not pass the hydraulic load test, it is highly recommended that the soil treatment area be replaced. Pump septic tank every 3 - 5 years depending on use and prior to transfer of title. The existing tank is adequate for current design criteria according to Garfield County OWTS regulations. For a 3-bedroom residence, the septic tank must be at least 1000 gallons, have two compartments with x2 accessible lids at the surface. Replace the broken concrete lid on outlet side. Install a new stainless -steel handle on the concrete lid on the inlet side. - It is recommended to include an effluent bio filter on the outlet tee of the septic tank. The bio filter should be inspected and cleaned depending on use (refer to manufacture recommendations, or more often if use patterns indicate). Correct the slope (due to belly) in the 3" ABS pipe under the residence. Install an exterior cleanout between the residence and the septic tank. Based on what we were able to observe and our experience with onsite wastewater technology, we submit this Onsite Wastewater Treatment System Inspection Report based on the present condition of the OWTS. Voskuil Operations has not been retained to warrant, guarantee, or certify the proper functioning of the entire system for any period of time in the future. Because of the numerous factors (usage, soil characteristics, previous failures, etc.) which may affect the proper operation of a wastewater treatment system, this report shall not be construed as a warranty by our company that the entire system will function properly for any particular buyer, seller or property owner. '/)-� , t .1 -Y Thank you, Jorden Voskuil, CWP NAWT Inspector ID: 170851TC Voskuil Operations, LLC PO Box 312 New Castle, CO 970-384-2487 jordenvoskuil@rocketmail.com ----- - - - - -. ...---------- - 4 GARFIELD COUNTY BUILDING AND SANITATION DEPARTMENT 109 8th Street Suits 303 - Gtenwood 8prings, Colors do $1601 Phone (303) 945.8212 INDIVIDUAL SEWAGE DISPOSAL PERMIT PROPERTY Permit N_- \ L4 8 Assessor's Parcel No. ! This does not constitute a building or use permit. Owner's Name Philip b i AU" Or ig 11 Present Address P.O. Sox 2588 161anwo" Phone 984-2417 ."I System Location__ 0149 Re jgs Lot 9. 8 k CrWek 8ubdivits,UWm & r Cali tl Legal Description of Assessor's Parcel No. SYSTEM DESIGN Septic Tank Capacity (gallon) Other , . f 9 A. Pe a atiort Pla a (minut rnch) Number of Bedrooms (or other) � Required Absorption Area - See Altaabad ' ! r f Zr r-i 1 �'!• 11' * 9.3 Special Setback Requirements: }7 r �;r rf,3- Date 11napeclor FINAL SYSTEM INSPECTION AND APPROVAL (as Installed) Call for Inspeotion,(24 hoyM n.q.tice)-Before Covering IrAtallatl�n _ ! 5eptlnk•�Carfl� c I Septic Tank -Manufacturer or Trade Name'!t - r Septic Tank Accsab within 8" of surface A dlatirptlon•Area 1 '\x i �•-- ', `' . •,ham a Absorption Area Type and/or Manufacturer or Trade Name Adequate compliance with County and State reguiatlonelrequiremente Other R s I.� rr inepeotor 1 ' Date �..� �-���. -- - r RI{TARj WITH flEaIPT RECORDSIATWNS''TRiJrMN S TE *CONDITIONS: y I 1. All Installation must compiywit h all requirements of th v WO red o-State 8osrd fo Nealth Individual fie +age t]ispasal Systems Chapter 26. Article 10 C.R.S.1073. Revised 11984. k •�-• • ' # ' 2. This permit Is valid only for connection tostructures which have fully compiled with ` county zoning and building requlremenls: Con• i nection to or use with any dwelling or structures not approved by the Bullding Ond zoning 0 to shall automalicapy be a violation or a requirement of the permit and cause for both legal action and revocation of the permit. 3. Any person who constructs, alters, orinstallsanindividual seWagsdisposal system ins mannerwhloh involves a knowing and materlai variation from the terms or Specifications contained In the applIasi Ion of permit commits a Class 1, Petty Offenee (".00 fine — 8 months In Jail or both). Applicant: green Copy Department: Pink Copy " INDIVIDUAL SEWAGE DIS 5ALAMTOWA ,CAI 1.1N 'i OWNER I __..._.......,_._---.,_.._....:. Ca PHONE ADDRESS- ADDRESS 7 Application Approval by County Official: CONTRACTOR_ �] f�., ADDRESS PHONE `7 �3' a�3�_' PERMIT REQUEST FOR: 1/rNew Installation ( ) Alteration ( ) Repair Attach separate sheets or report showing entire area with respect to surrounding areas, topography of area, habitable building, location of potable water wells, soil percolation test holes, soil profiles in test holes. (See page 4.) LOCATION OF PROPOSED FACILITY: County_ 21A Near what City of Town Lot Size ! Legal Description C -- WASTES TYPE; ( ✓) Dwelling ( ) Transient Use ( ) Commercial or Institutional ( ) Non -domestic Wastes ( ) Other - Describe BUILDING OR SERVICE TYPE: CMD f N m of bedrooms Number of persons ( garbage grinder ( Automatic washer ( ) Dishwasher S URCi= AND TYPE OF WATER SUPPLY: ( ) well ( ) spring ( ) stream or creek Give depth of all wells within 180 feet of system: If supplied by community water, give name or supplier: e l{ e GROUND CONDITIONS: DewclOrm' Depth to bedrock: Depth to first Ground Water Table: Percent ground slope: DISTANCE TO NEAREST C ITY SEWER SYSTEM: Was an effort made to connect to couinuni ty system? rY14 TYPE OF INDIVIDUAL SEWAGE DISPOSAL SYSTEM PROPOSED: Septic Tank ( ) Vault Privy ( ) Pit Privy ( ) Chemical Toilet FINAL DISPOSAL BY: (� Absorption ( ) Underground Aeration Plant Composting Toilet Incineration Toilet Trench, Bed or Pit Dispersal ( } Above Ground Dispersal ( ) other - Describe: ____ Other - Describe: ( ) Vault Recycling, potable use { ) Recycling, other use ( ) Evapotranspiration ( ) Sand Filter ( ) Wastewater Pond WILL EFFLUENT BE DISCHARGED DIRECTLY INTO WATERS OF THE STATE? SOIL PERCOLATION ZEST RESULTS: (To be completed by Registered Professional Engineer.) Minutes per inch in hole No. 1 Minutes -per inch in hole No. 's Minutes per inch in hole No. 2 Minutes _ per inch in hole No._ Name, address and telephone of RPE who made soil absorption tests: Name, address and telephone of RPE responsible for design of the system: Applicant acknowledges that the completeness of the application is conditional upon such further mandatory and additional tests and reports as may be required by the local health department to be made and furnished by the applicant or by the local health department for purposes of the evaluation of the application; and the issuance of the periiift,i•s subject to such terms and conditions as deemed necessary to insure compliance with rules and regulations adopted under Article 10, Title 25, C.R.S. 1973, as amended. The undersigned hereby certifies that all statements made, information and reports submitted herewith and required to be submitted by the applicant are or will be represented to be true and correct to the best of my knowledge and belief and are designed to be relied on by the local. department of health In evaluating the same for purposes of issuing the permit applied for herein. I further under- stand that any falsification or misrepresentation may result in the denial of the application or revocation of any permit granted based upon said applica on and in legal action for per- jury as provided by law. r (- Date "1� Signe PLEASE DRAW AND ACCURATE MAP TO YOUR PROPERTY PAnp I • rl LL LL O CO c LO Residential Biotube' Effluent Filters Applications Our patented* 4-in. (100-mm) Biotube Effluent Filters, Biotube Jr., Biotube Insert Filters, and Biotube Base Inlet Filters are ideal for residential septic tanks and have a lifetime warranty. They prevent large solids from leaving the tank, dramatically improving wastewater quality and extending the life of residential drainfields. 4-in. (100-mm) Biotube Ef rtent Filter (100-mm) Biotubejr. n. Biotube cartridge avail - separately as Insert Filter) 8-in. (200-mrn) Base Inlet Filter 4-in. (100-min) Insert Filter Orencds superior efflaaent filters resist clogging better tfmn all other brands. Our Stan- drard, full-sized 4-in. (100-min) Hieuebe Effluent Filter provides maximum long-te► n protection in a complete package ivith bousing. Our 4-in. (100-mnj) Biotube fr., at ljaf tlae size of our standard model bas more filtering capacity than the fill -sized filters sold by other manufactrerers For tanks with existing outlet tees, the Biotarbe Insert Filter is ideal. And for 1mv profile tanks, tberes the Base Inlet Filter. ' Covered by patent numbers 5,492,635 and 4,439,323 To Order Call your nearest Orenco Sysrems', Inc. distributor. For nearest distribu- tor, call Orenco at 800-348-9843 or go to www.orenco.com and click on "Distributor Locator." APSTN Rev. 3.4 ©11/10 Orenco Systems®, Inc. Standard Features & Benefits Has 5-10 times more flow area than other brands, so lasts many times longer between clean- ings, increasing homeowner satisfaction • Installs in min- utes inside new or existing tanks; extendible tee handle for easy removal Optional Features & Benefits • Alarm available, to signal the need for cleaning • Flow modulating discharge orifices available to limit flow rate leaving tank, mitigat- ing surges and increasing retention time • Custom and commercial sizes available • Easy to clean by simply hosing off whenever the tank needs pumping • Removes about two-thirds of sus- pended solids, on average, extending drainfield life • Corrosion -proof construction, to ensure long life • Lifetime warranty Biotube Filtering Process Effluent from the relatively clear zone of the septic tank, between the scum and sludge layers, horizontally enters the Biotube Effluent Filter. Effluent then enters the annular space between the housing and the Biotubes, utilizing the Biotubes' entire surface for filtering. Particles larger than the Biotube's mesh are prevented from leaving the tank. Orenco Systems Incorporated Cbengin� the RGty the World Does Weistervrner" www.orenco.com Nomenclatures 4-in. Biotube Filter (standard) Fri 04Cl Tptions: Blank = no options M = flow modulation plate installed A = float bracket attached Cartridge height: 28" and 36" are standard Housing height: 36" and 44" are standard Fitter diameter (inches) W = fits Type 3034 outlet pipe S = fits Schedule 40 outlet pipe Blank - 1 /8" filtration P = 1/16" filtration Biotube effluent filter series 8-In. Blotube Filter (base inlet model) Ff U 08 22 -14 B Options: A = float bracket FS = 2" out orifice FSO = 2" outlet orifice and overflow plate' Base inlet model Cartridge height:14" standard Housing height: 22" standard Filter diameter (inches) 08 = 8" Blank = 1/8"filtration P = 1/16" filtration Biotube effluent filter series `Also available with coupling and sleeve as a "kit": FT-OVERFLOWKIT 4-In. Biotube Jr. (includes cartridge and housing) FT J 0 [104 18 =� I Options: Blank = no options M = flow modulation plate installed A = float bracket attached Cartridge height (inches) Fitter diameter (inches) W = fits Type 3034 outlet tee S = fits Schedule 40 outlet tee Blank = 1/8"filtration P = 1/16" filtration Junior series Biotube effluent filter series 4-in. Biotube Filter Insert (cartridge only) Fr i 004 18 -❑-U — tFor customized options (e.g., NC indicates North Carolina regions) W = fits Type 3034 outlet tee S = fits Schedule 40 outlet tee Cartridge height (inches) Filter diameter (inches) Blank = 1/8"filtration P = 1/16" filtration Insert Blotubo effluent filter series 4-in. Biotube Effluent Filter Extendiblf Stainless st e G Top s Air Biotube° Soli Filter Distributed By: 4-in. Biotube Jr. UD-BOX 6 & UD-BOX s 22.45" - F 16" SIDE CUT OUT TO ACCEPT POLYLOK SEAL NO.3001 "n-aoX 6" MIUMD UD43OX 12" RISER 20" COMER FOR RISER & D-BOX Wabr & NrWa*Wwatar • Systems V1�LEY ■ Products PRECAST o Inc. a Service "OX SEAL MAERYDa ccoMMH 4 eEAL� � r9��) TEAR OUT FOR 4" SDR-35 OR SCHD-40 NOT TO SCALE ROTO FLOW 4" NOT TO SCALE POLYLOCK EQUALIZER W-HOTCH' WEIR �! FSHAM 0 LEVELM RI88 PRCVDE FR10TION FIT FOR ALL V PIPE f) 171 NOT TO SCALE GASKETED SEAL ON LID $ RISER (719) 39"7" 28005 Co. Rd. 317 P.O. B®c 925 Fwc (719) 395-3727 Bu"Vmt% C081211 Wabsks: www.v3IIeylxeca8t.00m Em n: fi onbdesk@vwwAw9casLconn v The Quick4° Plus INFILTRATOR" Standard Low Profile (LP) Chamber water technologies The Quick4 Plus Standard Low Profile (LP) offers maximum strength through its four center structural columns. This chamber can be installed in a 36-inch-wide trench. It is shorter in height than Infiltrator's other Standard model chambers, allowing for shallower installation. Like the original line of Quick4 chambers, it offers advanced contouring capability with its Contour Swivel Connection TM, which permits turns up to 150, right or left. The Quick4 Plus All -in -One 8 and Quick4 Plus Endcaps provide increased flexibility in system design and configurations. Maximum Strength Quick4 Plus Standard' Chamberp• Size 34"W x 53"L x 8"H (864 mm x 1346 mm x 203 mm) Effective Length 48" (1219 mm) Lower Height 6.3" (160 mm) Storage Capacity 32 gal (121 Q Invert Height 3.3" (84 mm), 9.6" (244 mm) i Qui Sta Chamber Benefits: • Low profile design makes this chamber ideal for shallow applications • Reduces imported fill needed for cap and fill systems • Four center structural columns offer superior strength • Advanced contouring connections • Latching mechanism allows for quick installation • Four -foot chamber lengths are easy to handle and install • Supports wheel loads of 16,000 Ibs/axle with 12" of cover Quick4 Plus All -in -One Periscope Benefits: • Allows for raised invert installations • 1800 directional inletting • 12" raised invert is ideal for serial applications 8 Endcap Benefits: • May be used at the end of chamber row for an inlet/outlet or can be installed mid -trench • Mid -trench connection feature allows center feed inletting of chamber rows • Center -feed connection allows for easy installation of serial distribution systems • Variable pipe connection options allow for side, end or top inletting • Piping drill points are set for gravity or pressure pipe Quick4 Plus Endcap Benefits: • Simple, flat design • Allows installation of a pipe from the end only • Piping drill points are set for gravity or pressure pipe Certified by the International Association of Plumbing and Mechanical Officials (IAPMO) 1 AP0 APPROVED in Qaickl Qu1ck4 Plus Standard Low Profile Chamber 8„ 1 34" Quick4 Plus All -in -One 8 Endcap 8' It- 18 T� 3.3" INVERT Quick4 Plus All -in -One Periscope 10.4" EFFECTIVE LENGTH l When installed between 2 chambers. 13.3" EFFECTIVE LENGTH* When installed at the end of a trench. f INVERT 9.6" FFIL 1 "�9 01, 5 9' INFILTRATOR° water technologies 4 Business Park Road P.O. Box 768 Old Saybrook, CT 06475 860-577-7000- Fax 860-577-7001 1-800-221-4436 www.inf t Itratorwater.com 48" (EFFECTIVE LENGTH) Quick4 Plus Endcap 4.5" EFFECTIVE LENGTH` 8" 3.3" - 6" INVERT INFILTRATOR WATER TECHNOLOGIES, LLC ("INFILTRATOR") Infiltrator Water Technologies, LLC STANDARD LIMITED Drainfield WARRANTY (a) The structural integrity of each chamber, endcap, ;rZilow expanded polystyrene andlor other accessory manufactured by Infifiralor ('Unils'), when installed and operated in a Ieachfield of all onsite septic system in accordance with fniilttator'8 instructions, Is warranted to the original purchaser {"Holdee) against detective materials and workmanship for one year from the date Thal the septic permit Is Issued for the septic system containing the Units; provided, however, that If a septic permit is not requhed by applicable law, the warranty period will begin upon the date that installation of the septic system commences. To exercise its warranty rights, Holder must notify Infiltrator in writing at its Corporate Headquarters in Old Saybrook, Connecticut within fifteen (15) days of the alleged defect Infiltrator will supply replacement Units for Units determined by Infiltrator to be covered by this Limited Warranty. Infiltrator's Gabi6ly specifically excludes the cost of removal and/or installation of the Units. (b) THE LIMITED WARRANTY AND REMEDIES IN SUBPARAGRAPH (a) ARE EXCLUSIVE. THERE ARE NO OTHER WARRANTIES WITH RESPECT TO THE UNITS, INCLUDING NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE (c) This Limited Warranty shall be void if any part of the chamber system is manufactured by any- one other than Infiltrator. The Limited Warranty does not extend to incidental, consequential, spe- cial or indirect damages. Infiltrator shall not be liable for penalties or liquidated damages, including loss of production and profits, labor and materials, overhead casts, or other losses or expenses incurred by the Holder or any third party. Specilically excluded from Limited Warranty coverage are damage to the Units due to ordinary wear and tear, alteration, accident, misuse, abuse or neglect of the Units; the Units being sut>fected to vehicle traffic or other condhions which are not permitted by the Tnstaifation instructions; failure to maintain the minimum ground covers set forth In the installal[on instructions; the placement of improper materials into the system containing the Units; failure of the Units or the septic system due to improper siting or improper sizing, excessive water usage. Improper grease disposal, or improper operation; or any ather event not caused by Infillrator, This Limited Warranty shall be void 4 the Holder fails to comply with so of the terms set forth in this Limited Warranty. Further, in no event shall Infiltrator be responsible for any loss or damage to the Holder, the Units, or any third party resulting from installation or shipment. or from any product fiabiI4 claims of Holder or any third party. For this LiWed Warranty to apply, the Units must be installed In accordance with all site conditions required by slate and local codes; all other applicable laws; and Infiltrator's installation instructions. (d) No representative of Infiltrator has the aulhority, to change or extend Ibis Limited Warranty. No warranty applies to any party other than the original Holder. The above represents The Standard Limited Warranty offered by Infiltrator. A tlmiled number of states and counties have different war - rarity requlrements. Any purchaser of Units should contact Infiltrator'$ Corporate Headquarters In Old Saybrook. Connecticut, prior to such purchase, to obtain a copy of the applicable warranty, and should carefully read that warranty prior to the purchase of Units. U.S. Patents: 4,759,661: 5,017,041; 5,156,488; 5,336,017:5,401,116; 5,401,459: 5,511,903; 5,716,163; 5.588,778; 5.839,844 Canadian Patents: 1,329,959; 2,004,564 Other patents pending. Infiltrator, Equalizer, Quick4, and SideWlnder are registered trademarks of Infiltrator Water Technologies. Infiltrator is a registered trademark in France. Infiltrator Water Technologies is a registered trademark in Mexico. Contour, Microl-saching, PolyTuff, ChamberSpacer, MUIIIPort, PoslLock, QuickCut, QuickPlay, SnapLock and StraightLock are trademarks of Infihrator Water Technologies. PolyLok is a trademark of PolyLok, Inc. TUF-TITE is a registered trademark of TUF-TITE, INC. Ultra -Rib is a trademark of IPEX Inc. 0 2016 Infiltrator Water Technologies, LLC. All rights reserved. Printed In U.S.A.PLUS01 0816 intact Infiltrator Water Technologies' Technical Services Department for assistance at 1-800-221-443t f gPublic.net Garfield County, CO Overview NATFIAN B 8 P' INA R013061 L .• 212525103008 " .y ,.. ! ° _,� R�y1303213 t- 1'2/2525100 1 7. J Fri 11013046 ' ■ * ► 2125251020AJ .h ,C r, R013110 "I�p�':.., ��r-^- ❑OBBS� '21252511330Q7 "ROBERT, M S BEV * l .. Legend SILVrf A' DAM L, ��! '� � `- Lj Parcels x Roads 4 ACOSTA 3UAREZ + Parcel/Account JUAN PABLO ;, Numbers R043255 - �" ; 41 R013143 Owner Name 12525103015 RqW l 212525, 01 2009 R0.13034 r �R .W rt - Lakes & Rivers ..;. 23252530201a f v -. Mi4RIG OLD HOLDINGS LLCM — County Boundary + � 14 Line R005052 r r~ 21.2525102017 t R0aa25a .. +, 'l25251030;f4 GQNZALEz 11hA.lANO ERIGkC ALEXANDER A Q MCCARTHY TRUST DTD 03�25f20,12 _ ' - F R605D53 �� �� R 13 8 212525102018 212525a1.02065 Account Number R013143 Physical Address 144 NAVAJO ST Total Actual Value ' $0 Last 2 Sales Parcel Number 212525102009 NEW CASTLE 81647 Date Price Acres 0 Owner Address ACOSTA JUAREZ, JUAN PABLO 5/30/2023 $245,000 Land SgFt 0 144 NAVAJO STREET 8/8/2005 $70,000 Tax Area 013 NEW CASTLE CO 81647 Mill Levy 63.4510 Date created:1/17/2026 Last Data Uploaded: 1/16/202610:05:46 PM Develo ed b p V-0 SCHNEIDER � GEO6PPTIAL c O U cu L M1 z a 0 J M .1' U O m W Y W w U Y J W C � O 00 L O � U a J m ~ C � Q K U Ln a L Z CD 0 ~ N Y N Q C K y M Inz O N F + U w N In O O W N C W � v` _a a o � _ p n N L. W c O a z W W CO W W H O mo w z U aw z v N m C�7 O N U -o U 07 a d d 2 a O 7 O U 'o a N O O a c� a H U Z � W p a. LL3 cr K N N F LU W w 0 O m O NN O N N G c O N n N N cl O N H tq N N O N C C O N N N N Oi t7 N N N M C1 O fO N A p NO Oo G C Q C N O N � n O � � .ti w s w li , J I A m I o N S C n o cei 4. Ln O m O O N O N N O O C - in n N N Cl O� N + I to c - W to W CL 0 W uj u �> LL ¢ r uj Q W Q O O m U a F p { LU P �j QJ O N W c O, a, M N U' O W LL N c-i N � Z g u; v W > � v W W o v J z_ a = o Ln II N O O �yy Ln n o m m y w n o F H Uba luEn 7 ? fs o t c y C T 0LL`1 yp�p it r W i0 U. boo C C J x C C O H L% I E. !V`o yea y y O c 9 c a u o Bi A w d .— o o F Q y) F Z N C Q �¢ mein Lt ��mmxxac� �, O1 m Q a ri �a a N p G � N N C-j 10 N \ 0 . � C C � N yn N " O N O N n N 10 N of N N M N a C C N co O O N N O W NLn I I to O C C N co N �I Ln G N lo �IIn N cn `O N V d U 2 L O n � tL�n o } O J m } y C J F Z !n � H v M w 0 w on 0 0 0� O O aq Cl! w N n n a jd N to W M Y O m a Q a r 0 w w a u V F 5 cr O uj 0 y N N N O Vl O C] 00 10 N N N O O N of of cc h ul I Vl N m s-1 O v-1 m M,- W; 24 L w Z I u 0 JAJ AN: 60 co