DESCRIPTION:
Gaco OnePaSSTm HFO F1860
Revised: 0112412023
GACO ONEPASSTm HFO F1860
CLOSED CELL SPRAY FOAM INSULATION
GaccOnePass HFO F1860 is a two component low GWP (Global Warming Potential) liquid spray system that cures to a
medium -density rigid cellular polyurethane insulation material. It contains polyols derived from naturally renewable oils,
post -consumer recycled plastics, and pre -consumer recycled materials.
GacoOnePass HFO F1860 is a Class A (Class 1) fire rated foam that meets or exceeds the requirements of ICC-ES AC377
Acceptance Criteria for Foam Plastic Insulation. It is a Type II foam in accordance with ASTM C1029. GacoOnePass HFO
F1860 is designed to be installed in up to 4" (10 cm) passes when applications instructions are followed.
This closed cell foam is designed to provide: excellent thermal performance, air impermeable insulation, and an integral part of
an air barrier assembly. Unprotected trade workers can safely reenter sprayed work areas one hour following application of
GacoOnePass HFO F1860 formulations —given adequate ventilation.
USAGE:
GacoOnePass HFO F1860 will provide excellent performance in a wide range of residential, commercial and industrial
applications where in service temperatures are between -40°F and 200°F including:
Walls
Attics
Concrete Slabs
Cold Storage age Tanks
Ceilings
Crawlspaces
I Residential Ducts
Freezers
Flotation
Floors
Foundations
Plenums
Piping
Industrial Application
TYPICAL PROPERTIES:
The following physical property tests were conducted by independent certified laboratories with traceable samples in
accordance ICC-ES AC377 and ASTM C1029 for Type II foam.
PROPERTY
TM TEST
VALUE
UNIT
Core Density
tC518
2 ± 10%
Ib/ft3
Aged R Value'"`
R 7.2 at 1" 2.54 cm **"
h-ft2•°F/Btu
R 28 at 4" (10.16 cm)***
Compressive Strength (Parallel to Rise):
D1621
25 (nominal)
psi
Tensile Strength
D1623
50 (nominal)
psi
Water Vapor Permeance
E96—Method A
< 2
perm -in
Dimensional Stability @ 158 °F (70 °C) and
97 /o RH
D2126
< 10 %
%linear change
Closed Cell Content
D6226
> gp
Air Permeance @ 75Pa
Infiltration/Exfiltration
E2178
0.001 at 1" 2.54 cm
( )
Us•m 2
Water Absorption (96 hrs, 2" head, 70-74 °F
21 0
D2842
0.29
% by volume
Fungi Resistance
C1338
Pass
no growth
Global Warming Potential
n/a I
1
gaco.com 800.813.1346
Gaco OnePassT1 HFO F1860
Page 2
*** These items are provided for general information. *"Federal Trade Commission regulations published in the Federal
Register 16 CFR Part 460 require that R value testing of polyurethane foam insulation must be conducted on aged samples
at a 75 "F (24 "C) mean test temperature. Failure to comply can result in substantial fines by the FTC. —To determine R
values for thickness not listed:
A. between 1" (2.54 cm) and 3.5" (9 cm) can be determined through linear interpolation or,
B. 3.5" (9 cm) and greater can be calculated based on R 7.21 inch
Gaco requires uniform ventilation of the immediate and adjacent work areas at minimum of 10 air exchanges per hour. Once
spraying is completed and for 1 hour following, ventilation should continue at this minimum (10 ACH) rate. It is then
recommended ensuring passive ventilation (overnight) by opening a window on each level of the structure in the vicinity of the
spray installations.
SURFACE BURNING CHARACTERISTICS:
The following physical property tests were conducted by independent certified laboratories with traceablity.
GacoOnePass HFO F1860 meets Class A (Class 1) requirements when tested in accordance with ASTM E84
(UL723) as defined in NFPA 101 and Section 803 of the Intemational Building Code (2009, 2012, 2015).
SYSTEM FLAME SPREAD INDEX SMOKE DEVELOPhl
Gaco F1860' <_ 25 <_ 450
Sample tested at 4" (10.2 cm) thickness. May be installed at unlimited thicknesses when
LARGE SCALE FIRE TESTING:
with%" (1.27 cm) gypsum board.
TEST PERFORMANCE LOCATION FOAM THICKNESS 1 COATING
Vertical surfaces Up to 8" (20.3 cm) / No Coating Required
AC377 Ignition Barrier
Horizontal or sloped surfaces Up to 12" (25.4 cm) / No Coating Required
Vertical surfaces Up to 7.5" (19.1 cm) / DC315 -14 mil wet
��NFPA286 Thermal Barrier Horizontal or sloped surfaces Up to 9.5" (24.1 cm) / DC315 -14 mil wet
See Table 2 ER0374
VAPOR RETARDER:
GacoOnePass Low GWP F1860 meets the requirement of 1 perms or less for a Class II vapor retarder per the International
Code Council and ASHRAE when installed at 1.6" (4 cm) in depth. Water vapor permeability as described below:
Thickness WVP Thickness WVP
1.7" (4.3 cm) 1.00 perms 3" (7.6 cm) 0.53 perms
1" (2.54 cm) 1.60 perms 4" (10.2 cm) 0.40 perms
2" (5.2 cm) 0.8 perms
CHEMICAL PROPERTIES:
"A" Component contains polymeric isocyanate. "B" Component contains polyols, catalysts, fire retardants, surfactants, and
blowing agents.
PROPERTY
Viscosity — "A" Component
Viscosity— "B" Component
TEST TEMPERATURE
77 °F (25 °C)
ASTM TEST
D2196
D1638
VALUE
+
7000+ 200
LINI7
cps
— ' " Component
Specific Gravity 'A P
"B"
77 F (25 C)
1.24
1.23
S.G.
S.G.
Specific Gravity — Component
"A"
10.3
lb/gal
Weight/Gallon — Component
77 "F (25 °C)
1
Ib/ al
Weight/Gallon — "B" Component
1 :1
b volume
MixingRatio — "A" & "B" Component
Stability When Stored at 50 °F to 77 °F
A Component 12
months
(10"C to 25°C)
B Component 6
months
gaco.com 1 800.813.1346
Gaco OnePassTm HFO F1860
Page 3
BARRIER PERFORMANCE:
GacoOnePass HFO F1860 is an air impermeable insulation and an air barrier material based on testing in accordance with
ASTM E2178 at 1" (2.54 cm) depth or more.
APPLICATION:
To ensure optimum performance, a minimum pass thickness of 3/4" (1.9 cm) is recommended with the maximum not to exceed
4" (10 cm) per pass. To obtain optimum results substrate temperature should be within the ranges as stated below. All
substrates must be dry at the time of application. Do not apply to wood surfaces with a moisture content of above 18%. Follow
applicable spray guides and GW 6-2 Gaco General Application Guide.
MATERIAL SUBSTRATE TEMPERATURE
Gaco F1860 50 °F to 110 °F (10 °C to 50 °C)�
Gaco F1860W 30 °F to 80 °F (-1 °C to 27 °C)
EQUIPMENT
SETTINGS
_ REACTIVITY TIME
Cream Time 1 second
Pre -Heaters - Iso (A)
120 °F to 140 °F (50 °C to 60 °C)
Pre -Heaters - Poly (B)
120 °F to 140 °F (50 °C to 60 °C)
Rise Time
3 - 6 seconds
Hose Heat
120 °F to 140 °F (50 °C to 60 °C)
Tack Free Time
4 - 8 seconds
Recommended Spray Pressure
1,000 to 1,500 psi (dynamic)
Cure Time
24 hours
The information herein is believed to be reliable but unknown risks may be present. ALL WARRANTIES OF ANY KIND,
EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND THAT GOODS
ARE OF MERCHANTABLE QUALITY, ARE SPECIFICALLY DISCLAIMED. See Gaco for information concerning its limited
warranty and its availability.
For specific Safety and Health information, please refer to Safety Data Sheet.
gaco.com 1 800.813.1346
Gaco-
*E�a
polyurethane systems
Insulation Certificate
Date Installation Completed 3 / 20 / 2025
Building Address 252 Co Rd 167
City/State/Zip Glenwood springs CO
Application Contractor (company name) Nova Insulation
Address 140 Park St unit B
Citv/State/Zip Gypsum CO 81637
Phone 970-401-5534 Email Novainsul@gmail..com
Area Insulated
Exterior Stud Wall Average Thickness
Ceiling Average Thickness 5.5"
Roof Deck Average Thickness
Crawl Space/Basement Average Thickness
Additional Areas Insulated Basement Rims Joist 3" R-21
R-Value
R-Value
R-Value
R-Value
l:a«:�
1 (print name) Jorge Calzadillas as an independent contractor, certify that
the Gaco1SES insulation installed on this project was applied in accordance with the Gaco1SES recommenda-
tions and specifications as stated on the product data sheet and the Gaco1SES Application Specifications in
the amount as indicated on this certification.
(signature)
/ 7/24/2024
(date)
Product
R-Value
3.5"
5.5"
R-13
R-20
R-30
R-38
R-49
GacoProFill (FR6500R)
R-4.04 at 1" I R-3.93/inch at >3.5"
R-14
R-22
3.3"
5.1"
7.6"
9.7"
12.5"
GacoFireStop2 (F5001)
R-4.1 at 1" I R-3.94/inch at >3.5"
R-14
R-22
3.3"
5.1"
7.6"
9.6"
12.4"
Gaco 052N (F052N)
R-4.2 at 1" I R-3.91/inch at >4"
R-14
R-22
3.3"
5.1"
7.7"
9.7"
12.5"
Gaco 183M (F183M)
R-6.4 at 1" I R-6.67/inch at >35,
R-23
R-37
2.0"
3.0"
4.5"
5.7"
7.4"
GacoONEPass (F1850R)
R-6.5 at 1" I R-7.2/inch at >3.5"
R-25
R-40
1.9"
2.8"
4.2"
5.3"
6.8"
GacoONEPass HFO (F1860)
R-7.2 at 1" I R-7.2/inch at >3.5"
R-25
R-39
1.9"
4.3"
5.4"
7"
GacoONEPass Low GWP (F1880)
R-7.1 at 1" I R-7.5/inch at >3.5"
R-26
R-41
1.8"
L2.7
4.0"
5.1"
6.6"
:_� H0LCIM
VE5
Originally Issued: 02/14/2023
GACO WESTERN, LLC (A DIVISION OF
FIRESTONE BUILDING PRODUCTS)
1245 Chapman Drive
Waukesha, WI 53186
www.gaco.com
GacoOnePass HFO SPRAY FOAM
INSULATION
CSI Section:
07 2100 Thermal Insulation
1.0 RECOGNITION
GacoOnePass HFO Spray Foam Insulation recognized in this
report has been evaluated for use as spray foam insulation
complying with IBC Section 2603, IRC Section R316, 2018,
2015 and 2012 IECC Sections C303, C402, R303 and R402
and 2009 IECC Sections 303 and 402. The surface burning,
physical properties, thermal resistance and applications in
Type V construction and exterior walls of Types I -IV
construction of GacoOnePass HFO Spray Foam Insulation
has been evaluated to comply to the intent of the following
codes and regulations:
• 2018, 2015, 2012 and 2009 International Building
Code® (IBC)
• 2018, 2015, 2012 and 2009 International Residential
Code® (IRC)
■ 2018, 2015, 2012 and 2009 International Energy
Conservation Code® (IECC)
• 2020 Florida Building Code, Building (FBC, Building)
2020 Florida Building Code, Residential (FBC,
Residential)
e 2020 Florida Building Code, Energy (FBC, Energy) -
supplement attached.
2.0 LIMITATIONS
Use of GacoOnePass HFO Spray Foam Insulation recognized
in this report is subject to the following limitations:
2.1 GacoOnePass HFO shall be installed in accordance with
the manufacturer's published installation instructions. The
insulation shall also be installed in accordance to this
evaluation report and the applicable code, and if there are any
conflicts between the manufacturer's published installation
instructions and this report, the more restrictive governs.
2.2 Except as indicated in Section 3.3.3 of this report or by
the applicable code, the insulations shall be separated from
the interior of the building by a code approved thermal
barrier.
2.3 As noted in Sections 3.3.3 and 3.3.4 of this report, the
insulation shall not exceed the nominal density and thickness.
Im
Valid Through: 02/28/2024
2.4 During installation, the insulation and the surfaces to
which they are applied shall be protected from exposure to
weather.
2.5 The contractors that will be installing the insulations shall
be certified by Gaco Western, LLC or by the Spray
Polyurethane Foam Alliance (SPFA).
2.6 Use of the insulation in areas of "very heavy" termite
infestation shall be in accordance with 2018 and 2015 IBC
Section 2603.8, 2012 IBC Section 2603.9, or 2009 IBC
Section 2603.8, or IRC Section 318.4, as applicable.
2.7 Labeling and jobsite certification of the insulation and
coatings shall comply with 2018 and 2015 IRC 1101.10, 2012
IRC Sections 1101.12, 2009 IRC Sections N1101.4 and
N1101.4.1, IECC Sections C303.1.1 and C303.1.2, as
applicable.
2.8 Foam Plastic used in plenums as interior finish or interior
trim shall comply with Section 2603.7 of the IBC.
2.9 The insulation recognized in this report is produced in
Waukesha, Wisconsin and Spring, Texas.
3.0 PRODUCT USE
3.1 General: When installed in accordance with Section 3.3
of this report, GacoOnePass HFO Spray Foam Insulation
may be used in wall cavities, floor assemblies or ceiling
assemblies, and in attic and crawl spaces as nonstructural
thermal insulation material. The spray -applied foam plastic
insulations are used in Type V-B construction under the IBC
and in dwellings under the IRC. The spray -applied foam
plastic Insulations also may be used in Type I, II, III or IV
construction when installed in accordance with Section 3.4 of
this report.
GacoOnePass HFO Spray Foam Insulation may be used as
air impermeable insulation when installed in accordance with
Section 3.2.4 of this report.
3.2 Design:
3.2.1 General. GacoOnePass HFO Spray Foam Insulation
shall comply with requirements in 2018, 2015 and 2012
IECC Sections C402.1 and R402, or 2009 IECC Section 402,
as applicable.
3.2.2 Thermal Resistance. (R-Values): GacoOnePass HFO
Spray Foam Insulations have a thermal resistance (R-Value)
at a mean temperature of 75°F (24°C) as shown in Table 1 of
this report.
The product descrlbad in this Uniform Evaluation Service (UES) Report has boon avaluatad as an alternative mefer9al, design or method of construction in order to satisfy and comply wilh
the infant of the provision of the code, as noladin this report, and for at least equivalence to that prescribed in the cads In quatfy, strength, effectiveness, fire resi&anco, durability and safoty.
as applicable, in accordance with IBC Section 104.11. This document shall only be reproduced in its entirety.
Copyright 0 2023 by Int mationalAssoaation of Plumbing and Mechanicat Oftials. All rights reserved. Printed in the United States. Ph: 1-677-4IESRPT - Fax: 909.472.4171
wub: www.uniform-es.org • 4755 East Philadelphia Street Ontario, Cellfomla 91761-2616 — USA
Page 1 of 7
VES
Originally Issued: 02/14/2023
TABLE 1— Thermal Resistance (R-Value)
("F-W-hlBtu)
Thickness
(inch)
GacoOnePass BFO
1
7.2
2
14
3
21
3.5
25
4
28
5
35
6
42
7
49
8
56
9
64
10
71
11
78
12
84
For SI: 1 inch = 25.4 mm, 1 °F•ft2 •h/Btu = 0.176 110 K-m'-Iw.
R-Values are calculated based on tested K values at 1-inch and 3.5-
inch thicknesses.
2R-Values greater than 10 are rounded to the nearest whole number.
3.2.3 Surface Burning Characteristics. At a maximum
thickness of 4 inches (102 mm) and a nominal density of 2.0
pcf (32 kg/m3), the GacoOnePass HFO Spray Foam
Insulations has a flame spread index of 25 or less and smoke -
developed index of 450 or less when tested in accordance
with ASTM E84. Thicknesses are not limited for ceiling
cavities and wall cavities when covered by a code complying
prescriptive thermal barrier, such as minimum '/2-inch thick
(12.7 mm) gypsum board.
3.2.4 Air Permeability. When tested in accordance with
ASTM E2178 at a minimum thickness of 1 inch (25.4 mm),
GacoOnePass HFO Spray Foam Insulation is classified as
air -impermeable insulations in accordance with Section
1202.3 of the 2018 IBC, Section 1203.3 of the 2015 IBC, and
Section R806.5 of the 2018, 2015 and 2012 IRC or Section
R806.4 of the 2009 IRC, as applicable.
3.2.5 Vapor Permeance: When tested in accordance with
the ASTM E96 desiccant method (Procedure A),
GacoOnePass HFO Spray Foam Insulation has a vapor
permeance of less than 1.0 perms [57.4 x 101 g/(Pa•s•mZ)], at
a minimum thickness of V/s inches (41.3 mm) and qualify as
a Class II vapor retarder in accordance with IBC Section 202
and IRC Section R202.
3.2.6 Fire -Protective Coatings and Coverings: Fire
protective coatings, for use as part of an alternative thermal
barrier assembly, shall be in accordance with Table 2 of this
report, as applicable, and installed in accordance with Section
4.6 of this report.
859
Valid Through: 02/28/2024
3.3 Installation:
3.3.1 General. The manufacturer's published installation
instructions for GacoOnePass HFO Spray Foam Insulation
and this report shall be available on the jobsite during
installation for quality control purposes.
GacoOnePass HFO Spray Foam Insulation shall be spray -
applied on the jobsite using a volurnetric positive
displacement pump in accordance with the manufacturer's
published installation instructions. The applied insulation
shall be sprayed in multiple passes having a maximum
thickness of 4 inches (50.8 mm) per pass up to the maximum
insulation thickness specified in this report. The maximum
in-service temperature for all areas shall not exceed 180°F
(82°C). The spray -applied foam plastic insulation shall not be
used in electrical outlets or junction boxes or in continuous
contact with rain or water. The spray -applied foam plastic
insulation shall be sprayed onto a substrate that is protected
and clean from any debris or weather -related conditions
during application.
3.3.2 Installation with a Prescriptive Thermal Barrier:
GacoOnePass HFO Spray Foam Insulation shall be separated
from the interior by an approved thermal barrier of minimum
'/2 inch thick (12.7 mm) gypsum wallboard or an equivalent
thermal barrier. When installed in accordance with this
section the spray foam may be any thickness when installed
behind a prescriptive thermal barrier. The barrier shall
comply with, and be installed in accordance with, IBC
Section 2603.4 or IRC Section R316.4, as applicable.
3.3.3 Installation with an Alternative Thermal Barrier
Assembly: The thermal barrier required by IBC Section
2603.4 or IRC Section R316.4 may be omitted when applied
as part of an alternative thermal barrier assembly as shown in
Table 2 of this report.
3.3.4 Installation for Attics and Crawl Spaces: When used
in an attic or crawl space where entry is made only for service
of utilities, GacoOnePass HFO Spray Foam Insulation shall
be installed in accordance with this section. The insulation
shall be separated from the interior of the building by an
approved thermal barrier as described in Sections 3.3.2 and
3.3.3 of this report, as applicable.
3.3.4.1 Installation with a Prescriptive Ignition Barrier:
Where entry is made only for the service of utilities,
GacoOnePass HFO Spray Foam Insulations may be installed
within attics or crawl spaces with an ignition barrier in
accordance with IBC Section 2603.4.1.6, or IRC Sections
R316.5.3 and R316.5.4, as applicable. The ignition barrier
shall be installed in a manner such that the foam plastic
insulation is not exposed and is consistent with the
requirements of the type of construction required by the
applicable code.
3.3.4.2 Installation with an Alternative Ignition Barrier
Assembly: When installation is in accordance with this
Page 2 of 7
YE5
Originally Issued: 02/14/2023
section, the ignition barrier specified by Section 2603.4.1.6
of the IBC or Sections R316.5.3 and R316.5.4 of the IRC, as
applicable, may be omitted.
3.3.4.2.1 General: When GacoOnePass HFO Spray Foam
Insulations are installed in attics and crawl spaces without a
prescriptive ignition barrier, the following conditions apply:
a. The thickness of the foam plastic insulation applied to
the underside of the top of the space shall not exceed
11'/z inches (292 mm).
b. The thickness of the foam plastic insulation applied to
the vertical surfaces shall not exceed 7'/z inches (190
m).
c. Entry is only to service utilities in the attic or crawl
space and no storage is permitted.
d. Attic or crawl space areas cannot be interconnected.
e. Air from the attic or crawl space cannot be circulated to
other parts of the building.
f. In accordance with 2018 IBC Section 1202.2, the 2015
and 2012 IBC Section 1203.2 or IRC Section R806, as
applicable, attic ventilation is provided, as applicable.
g. In accordance with 2018 IBC Section 1202.4, 2015 and
2012 IBC Section 1203.4 or IRC Section R408.1, as
applicable, crawl -space ventilation is provided, as
applicable.
h. In accordance with IMC (International Mechanical
Code®) Section 701, combustion air is provided.
3.3.4.2.2 Attics and Crawl Spaces: GacoOnePass HFO
Spray Foam Insulations may be spray -applied in attics to the
underside of roof sheathing, roof rafters and/or vertical
surfaces, and in crawl spaces to the underside of floors and/or
vertical surfaces as described in this section. When applied to
the underside of the top of the space, and the thickness of the
GacoOnePass HFO Spray Foam Insulation does not exceed
11'/z inches (292 mm), and when applied to vertical surfaces
the maximum thickness does not exceed 7'/2 inches (190
mm), the GacoOnePass HFO Spray Foam Insulation do not
require the application of either an ignition barrier or a fire
protective coating.
Optional: If desired, GacoOnePass HFO Spray Foam
Insulation may be applied as part of an alternative ignition
barrier assembly with a fire coating as shown in Table 3 of
this report.
3.3.4.2.3 Unvented Attics: GacoOnePass HFO Spray Foam
Insulation may be installed in unvented attic assemblies and
unvented enclosed rafter assemblies in accordance with
Section 1202.3 of the 2018 IBC, Section 1203.3 of the 2015
IBC or Section R806.5 of the 2018, 2015 and 2012 IRC, or
Section R806.4 of the 2009 IRC, as applicable.
3.4 Exterior Walls of Buildings of Type I, II, III or IV
Construction. When GacoOnePass HFO Spray Foam
Insulations are used in exterior walls of buildings of Type I,
II, III or IV construction of any height the insulation shall
comply with Section 2603.5 of the IBC and this section.
TE
Valid Through: 02/28/2024
GacoOnePass HFO Spray Foam insulation shall be installed
at a maximum thickness of 4-inches (102 mm).
3.4.1 Complying Exterior Wall Assemblies. Wall
assemblies that comply with Section 2603.5 of the IBC and
this report that may be used in exterior walls of buildings of
Type I, II, III or IV construction of any height are described
in Table 4 of this report.
3.5 Use as a Water -resistive- Barrier. GacoOnePass HFO
when applied to form a minimum 1.5-inch thick (38.1 mm)
continuous layer may be used as an alternative water -resistive
barrier specified in Section 1403.2 of the 2018 IBC and
Section 1404.2 of the 2015, 2012 and 2009 IBC and Section
R703.2 of the IRC, as applicable.
3.6 Weather Protection. GacoOnePass HFO, when applied
to form a minimum 1.5-inch thick (38.1 mm) continuous
layer, may be used to meet the requirements for weather
protection applied to sheathing over framing spaced at 16
inches on center as provided in Exception 2 of Section 1402.2
of the 2018 IBC and Exception 2 of Section 1403.2 of the
2015, 2012 and 2009 IBC.
4.0 PRODUCT DESCRIPTION
GacoOnePass HFO Spray Foam Insulations are a spray -
applied, polyurethane foam plastic and comply as medium -
density insulation in accordance with Section 3.1.1 and Table
1 of AC377. The insulation is a two -component spray foam
plastic with a nominal in -place density of 2.0 pcf (32 kg/m3).
The spray -applied insulation is mixed in the field by
combining a polymeric isocyanate (A component) and a resin
blend (B component). The liquid components shall be stored
in 55-gallon (208 L) drums at temperatures between 507 and
70°F (10°C and 21°C). When Component A and Component
B are stored in factory -sealed containers at the recommended
temperatures, the maximum shelf life is six months.
5.0 IDENTIFICATION
The spray foam insulation containers are identified with the
following:
a. Manufacturer's name (Gaco Western, LLC)
b. address and telephone number,
c. the product trade name (GacoOnePass HFO Spray
Foam Insulation)
d. use instructions
e. density, flame -spread and smoke -development indices
f. date of manufacture or batch/ran number
g. the IAPMO Uniform ES evaluation report number (ER-
859)
h. the name or logo of the inspection agency (IAPMO
QCC)
Page 3 of 7
UEsEVALUATION REPORT 859
tW, Originally Issued: 02/14/2023 Valid Through: 02/28/2024
Either Mark of Conformity may also be used as shown below: 7.0 STATEMENT OF RECOGNITION
IAPMO or UEs
ES
0
IAPMO UES ER-859
6.0 SUBSTANTIATING DATA
This evaluation report describes the results of research
completed by IAPMO Uniform Evaluation Service on SES
Foam's GacoOnePass HFO Spray Foam Insulations to assess
conformance to the codes shown in Section 1.0 of this report
and serves as documentation of the product certification.
Products are manufactured at the location noted in Section
2.9 of this report under a quality control program with
periodic inspection under the supervision of IAPMO UES.
For additional information about this evaluation report please visit
ww .uniform_ep.ure or email us at infoAuniform-es.ore
6.1 Data in accordance with the ICC-ES Acceptance Criteria
for Spray -applied Foam Plastic Insulation, AC377, dated
February 2020, including reports of tests in accordance with
Appendix X of AC377.
6.2 Reports of room comer testing in accordance with NFPA
286.
6.3 Reports of fire characteristics testing in accordance with
NFPA 285.
6.4 Reports of potential heat of building material testing in
accordance with NFPA 259.
6.5 Reports of water vapor transmission testing in accordance
with ASTM E96.
6.6 Reports of testing in accordance with ASTM E331.
6.7 Test reports are from laboratories in compliance with
ISO/IEC 17025.
Page 4 of 7
10M
Originally Issued: 02/14/2023 Valid Through: 02/28/2024
TABLE 2 - ALTERNATIVE THERMAL BARRIER ASSEMBLIES
FIRE -PROTECTIVE COATING/COVERING' MAXIMUM SPF THICKNESS
(inch)
THEORETICAL
WALLS AND
CEILING AND
TYPE
,I � S
APPLICATION RATE
VERTICAL
OVERHEAD
(COATINGS ONLY)
SURFACES
SURFACES
DC315 2
14 mils WFT (9
0.87 gal/100 ft2
5.5
10.25
mils DF
Plus ThB3
14 mils WFT (9
0.87 gal/100 ft2
6
9.5
mils DF
For SI: 1 inch = 25.4 mm, 1 gallon = 3.785 L, 1 it' = 0.0929 m=
' Fire -protective coatings and coverings shall be applied over all exposed SPF surfaces in accordance with the
coating/covering manufacturer's instructions and this report.
2 International Fireproof Technology, Inc, recognized in lAPMO UES ER-499 and nested to therequirements: of NFPA
286.
-'No-Bum, Inc, recognized in IAPMO UES ER-305 and tested to the requirements of UL 1715.
TABLE 3 - ALTERNATIVE IGNITION BARRIER ASSEMBLIES
FIRE -PROTECTIVE COATING/COVERING-1
MAXIMUM SPF THICKNESS
inch)
THEORETICAL
WALLS AND
CEILING AND
TYPE
S
APPLICATION RATE
VERTICAL
OVERHEAD
,I HICKNE
(COATINGS ONLY)
SURFACES
SURFACES
DC315Z
4 mils WFT (3
0.25 gal/100 ft
10
12
mils DFT)
For SI: 1 inch = 25.4 mm, 1 gallon = 3.785 L, 1 h2 = 0.0929 rn'
' Fire -protective coatings and coverings shall be applied over all exposed SPF surfaces in accordance with the
coating/covering manufacturer's instructions and this report.
'International Fireproof Technology, Inc, recognized in IAPMO UES ER-499.
Page 5 of 7
EVALUATION REPORT
Originally Issued: 02/14/2023
E.9w7
Valid Through: 02/28/2024
TABLE 4 — NFPA 285 COMPLYING EXTERIOR WALL ASSEMBLIES
Wall Component
Material Description
Base Wall System (BWS)
1— Concrete wall
Use either 1, 2 or 3
2 — Concrete masonry wall
3 —1 layer of 5/s-inch thick Type X gypsum wallboard installed on the interior side of minimum
3'/8-inch-deep minimum No. 20-gauge thick steel studs spaced a maximum or 24 inches on
center. Lateral bracing installed minimum every 4 feet vertically or as required. Wall stud
cavities shall be filed at each floor line with minimum 4 pcf density mineral wool (e.g.
Thermafiber) friction fit between steel wall studs.
Resilient Channel
Double -leg `hat' shaped steel resilient channel, minimum 30 gage, installed perpendicular to
when used with BWS 3 above
the wall studs (interior side only) and spaced a maximum of 24-inches on center between steel
studs and Type X gypsum wallboard. Entire perimeter of window opening to be framed with
resilient channel.
Perimeter Fire Barrier System
Perimeter fire barrier system complying with Section 715.4 of the IBC shall be installed, as
applicable, to fill the void created at the intersection of the exterior curtain wall assembly and
the concrete floor slab.
Interior Insulation
1—None
Use either 1, 2, 3, 4 or 5; or combination of
2 — Maximum V/s-inch thickness of SES EasySeal.5 (SES Sucraseal 0.5) applied to the interior
3 and 4; or combination of 3 and 5
surface of BWS 1 or 2 above.1, a
3 — SES EasySeal.511. (Sucrasea10.5) applied to the full depth of the wall stud cavity, our less,
with exterior gypsum sheathing (see BWS 3 above) as the substrate covering the width of
the cavity and the inside of the steel wall stud framing flange.°
4 — Fiberglass batt insulation (faced or unfaced)
5 — Mineral wool insulation faced or unfaced
Exterior Sheathing
1 —None (for BWS 1 or 2 above)
Use either 1, 2 or 3
2 —'/z inch thick exterior gypsum sheathing (for BWS 3 above)
3 - 5/s-inch-thick Type X exterior type gypsum sheathing for BWS 3 above
Exterior Insulation
Maximum 4-inch thick GacoOnePass HFO Spray Foam Insulation 3
Exterior Wall Covering'
1 — Brick - steel brick veneer anchors, installed a maximum 24-inches on -center, vertically on
Use either 1, 2, 3, 4 or 5
each stud with maximum 2-inch air gap between exterior insulation and brick Brick to be
standard nominal 4-inch-thick clay brick installed in a running bond pattern using Type S
mortar.
2 — Stucco - minimum'/. -inch thick, exterior cement plaster and lath. A secondary water -
resistive banger (WRB) shall be installed between the exterior insulation and the lath. The
Secondary WRB shall not be full -coverage asphalt or butyl -based self -adhering membranes.
3 — Minimum 2-incb- thick natural stone. Joints shall he mortared (non -open jointed).
4 — Minimum I'/x-inch thick concrete masonry unit, pre -cast concrete or artificial cast stone.
Joints shall be mortared.
5 — Minimum 1'/,-inch thick terra cotta. Joints shall be mortared.
Flashing of windows, doors or other
As an option, flash around windows, doors and other exterior wall penetrations with limited
exterior wall penetrations
amounts of maximum 12-inch-wide flashing tape (acrylic, asphalt or butyl -based) or liquid -
a lied membrane material with or without fiber mesh reinforcement.
61: 1 men = L4.4 mm: 1 pct = 16.0 kglnY; 1 BTU/tt` = U.01128 mJ/m`
Fireblocking per Section 718 of the 2018, 2015 and 2012 IBC and Section 717 of the 2009 IBC and thermal barrier material requirements per
Section 2603.4 of the IBC shall be met for Base Wall Systems 1 and 2, as required by specific wall construction details when a combustible
concealed space is created on interior side of exterior wall assembly.
' Exterior wall coverings shall be installed in accordance with the manufacturer's installation instructions and shall comply with the provisions of
Chapter 14 of the IBC and Chapter 7 of the IRC, as applicable.
3 The potential heat of 4-inch-thick GacoOnePass HFO Spray Foam Insulation is 2,066 Btu/ft per inch of thickness when tested in accordance
with NFPA 259.
4 The potential heat of 3'/8-inch-thick SES 0.5 lb. Spray Foam Insulation is 466 Btu/fl' per inch of thickness when tested in accordance with NFPA
259.
Page 6 of 7
CE EVALUMON REPORT 859
Originally Issued: 02/14/2023 Valid Through: 02/28/2024
FLORIDA SUPPLEMENT
GACO WESTERN, LLC (A DIVISION OF
FIRESTONE BUILDING PRODUCTS)
1245 Chapman Drive
Waukesha, WI 53186
GacoOnePass HFO SPRAY FOAM
INSULATION
CSI Section: 07 2100 Thermal Insulation
1.0 RECOGNITION
GacoOnePass BFO Spray Foam Insulation evaluated in
IAPMO UES Evaluation Report ER-859 is a satisfactory
alternative to the following codes and regulations:
• 2020 Florida Building Code, Building (FBC,
Building)
• 2020 Florida Building Code, Residential (FBC,
Residential)
■ 2020 Florida Building Code, Energy (FBC, Energy)
2.0 LIMITATIONS
2.1 The clearance between the foam insulation installed
above grade and exposed earth shall be in accordance with
Sections 1403.8 and 2603.8 of the FBC, Building or Section
R318.8 of the FBC, Residential, as applicable.
2.2 Verification shall be provided that a quality assurance
agency audits the manufacturer's quality assurance program
and audits the production quality of products, in accordance
with Section (5)(d) of Florida Rule 61 G20-3.008. The quality
assurance agency shall be approved by the Commission (or
the building official when the report holder does not possess
an approval by the Commission).
2.3 This supplement expires concurrently with ER-859.
For additional information about this evaluation report please visit
u r i f�. r n r_._.r-: or email at l u tou: u n i fornt-e5.nr
Page 7 of 7
QUIK=SHIELD YER
All Seasons HFO Spray Foam
QUIK-SHIELD® YETI is a closed -cell spray foam insulation, using Honeywell's Solstice® liquid blowing agent which has a GWP
of 1, 99.9% lower than traditional blowing agents meeting GWP initiatives. It is a high-performance insulation and air barrier,
ideal for residential and commercial construction. QUIK-SHIELD® YETI increases jobsite efficiency, decreases labor and
overhead costs, and delivers a lower install cost.
TYPICAL PHYSICAL PROPERTIES
Properties achieved in a lab environment at 77°F. Field conditions may cause variation in properties.
PROCEDURE VALUES
Air Permeance at 1" (L/s.m') E-2178 <0.02
Closed -Cell, content (%) E-2178 >90
Compressive Strength (psi) D-1621 >15
Core Density (nominal, Ib/ft') D-1622 2.0
Dimensional Stability (%) D-2126 <15
Tensile Strength Ib/inz (psi) D-1623 >15
Water Vapor Permeability (perm -inch) E-96 1.72
Fungi Resistance C-1338 No Growth
THERMAL RESISTANCE (R-Value) (°Fft2.h/Btu)
R-Value at 1" 7.5
R-Value/inch at z 3.5" 7.5
THERMAL//GN/T/ON BARRIERS
For information regarding approved thermal and ignition barriers please refer to
Intertek's Code Compliance Research Report # 0478 (CCRR-0478)
LIQUID PROPERTIES at 77OF (25°C)
A -SIDE (ISO) B-SIDE (RESIN)
Specific Gravity 1.23 1.21
Viscosity (CPS) 250±50 550±100
RECOMMENDED STORAGE AND SHELF LIFE
• Storage temperatures 50-80'F (10-27C). See back for preconditioning of material.
• 6 month shelf life from date of manufacture (unopened containers)
• Keep container tightly sealed
• Store out of direct sunlight, in a cool dry place, avoid freezing
PRODUCT INFORMATION
LEED QUIK-SHIELD® YETI has a minimum of 10.5% total renewable/recycle content, 5.5% pre -consumer recycled, 4.2% post -consumer
recycled, 2.0% rapidly renewable, and IEQ Credit- Low Emitting.
Product Packaging 275 Gallon Tote and 55 Gallon Drum
APPROVALS/ COMPLIANCE
QUIK-SHIELD* YETI has been tested by a third party laboratory (Intertek Testings Services NA, Inc.)
CCRR-0478 GREENGUARD Gold Certified Honeywell's Solstice® liquid blowing agent
O
800-828-1394 1 swdurethane.com
PUBLISH DATE: 09/2024
Technical Data Sheet
QUIK-SHIELD YETI
PREPARATION OF SUBSTRATES
Providing the proper substrate is the responsibility of the owner, the owner's appointed representative, the contractor, and/or inspector. The following are
manufacturer's recommendations. However, other preparation techniques may be required given unique/specialized application circumstances. Contact SWD
Technical Support at 888-380-2022 for additional questions.
It is recommended to remove dust, dirt, oil, paint, and alternative polymers from all surfaces prior to applying SWD products.
See SWD specifications or SPFA guidelines for further details on substrate prep.
Wood Ensure wood is relatively dry and protect surfaces from contamination. For moisture content exceeding 19%, contact SWD
Technical Support.
• Water or oil present may cause poor adhesion or excessive foaming.
• Fill large voids with appropriate backer rods or appropriate fillers.
• If additional information is required, contact SWD Technical Support.
Steel & Other Metals It is the responsibility of the contractor/end user to determine proper adhesion and suitability through field testing. Blasting and/or
priming is not always required. If additional information is required, contact SWD Technical Support.
Concrete If applying foam to concrete, the concrete surface should be structurally sound, clean, and curing for 28 days.
• Fill large voids with appropriate backer rods or appropriate fillers.
• Blasting and/or priming is not always required. It is the responsibility of the contractor/end user to determine proper adhesion and
suitability. If additional information is required, contact SWD Technical Support.
Previously Applied As practical, remove previously applied foam and other polymer products. Application of product over existing materials should be
Foam or Other performed only after adhesion/compatibility is verified by the contractor and accepted by the building owner or owner's appointed
Polymers representative.
Wiring and Plumbing QUIK-SHIELD® YETI is fully compatible with CPVC piping systems (Paschal Engineering Study for the SPFA).
• QUIK-SHIELD' YETI is compatible with typical electrical wiring coverings. (NEMA Bulletin 95)
PROCESSING
Preconditioning 1. If the drum temperature is 80°F (26.6°C) or higher, use caution when opening the drum! The contents will be under pressure.
2. It is recommended to precondition material to 60-80'F (16-27'C) prior to application. Material may thicken at lower temperatures
which can cavitate pumps.
Mixing 3. Mixing of B-Side (resin) is not required.
4. Mixing of A -Side (iso) is not required.
Pressure Settings S. Product should be sprayed with a high pressure plural -component proportioner capable of a minimum of 1100 psi dynamic
pressure.
6. Static pressure is typically set between 1200-1600psi.
Temperature Settings 7. Primary heaters and hose heaters are typically set between 105-145°F (41-63°C). Higher temperatures are utilized in winter
months, lower temperatures are utilized in summer months.
Proper application temperature setting is the responsibility of the end user. Equipment temperature varies and can be dependent on equipment, hose
length, elevation, ambient temperature, substrate temperature, humidity, and other factors. If additional information is required, refer to QUIK-SHIELD YETI
Processing Packet found on swdurethane.com and the SWD mobile app, or contact
SWD Technical Support at 888-380-2022.
APPLICATION
Do not spray foam when substrate surface temperatures are less than 5°F above the dew point.
Clean surfaces according to "Preparation of Substrates" section.
If priming, follow manufacturer recommendations. Ensure primer is adequately cured prior to application.
Substrate temperatures should be between 20-120OF (-6-49'C) Flashing is recommended at lower temperatures. Contact SWD Technical Support for more
details.
Flush an adequate amount of material through the lines/gun prior to spraying desired surface when changing between systems. Flush amount will be
dependent on prior system used. If additional information is required, contact SWD Technical Support for more details.
Do not recirculate.
QUIK-SHIELD' YETI shall not exceed 4" per lift, with a minimum 20-30 minute wait time between lifts.
Before application, test material to ensure that material sprays, cures, and hardens properly.
Inspect applied material intermittently to ensure no problems exist. If problems are detected, discontinue application and inspect all substrates, equipment,
gun, and liquid material for problem source(s).
CLEANING AND MAINTENANCE
1. Spray equipment must be maintained in proper operating condition. Failure to adequately maintain spray equipment may result in poor product
performance. Refer to your equipment manufacturer's maintenance procedures for more details.
2. Contact SWD for long-term equipment storage recommendations.
DThe Information herein Is believed to be reliable; however, unknown risks may be present. SWD Urethane makes no warranty, expressed or Imolled, concerning
this produces merchantability or fitness for any particular use. The product will meet the written liquid component specifications as indicated on the technlcaf data
sheet published at the time of the purchase. The entirety of SWD Urethane's responsibility is limited onty to the cost of the SWI) material. The foregoing constitutes
SWD urethane's sole obBgatlon wlth respect to damages, whether direct, incidental or consequential, resulting from the use or. performance of the product.
Safety is the responsibility of the owner, the owners appointed representative, the contractor, and/or inspector. Become familiar with local, state, and federal regulations
regarding chemical health, safety, and handling. For more information consult the product SDS, contact the SPFA (www.sprayfoam.org) or the ACC (www.spraypolyurethane.org).
SWD Urethane 1 800-828-1394 1 540 South Drew St. I Mesa, AZ 85210 1 swdurethane.com