HomeMy WebLinkAbout25216 - GARCO PREMIER HANGERS - ELEC - REVISED UTILITY LOCATIONS -STAMPED- 8-26-2025A.SUBSTITUTIONS: SUBSTITUTION OF SPECIFIED EQUIPMENT WILL BE ALLOWED THROUGH A PRIOR APPROVAL PROCESS INITIATED BY THE CONTRACTOR. CONTRACTOR SHALL SUBMIT INTENDED SUBSTITUTION AT LEAST FIVE DAYS PRIOR TO BID FOR APPROVAL FROM ENGINEER. SUBMITTAL SHALL INCLUDE CAPACITIES, DIMENSIONS AND OPERATING INSTRUCTIONS FOR EACH PIECE OF EQUIPMENT. SUBSTITUTION SHALL OCCUR AT NO COST TO THE OWNER. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF APPROVED SUBSTITUTION AND SHALL INCUR ALL COSTS ASSOCIATED WITH THE SUBSTITUTION INCLUDING STRUCTURAL MODIFICATIONS, SPACE LAYOUT AND REDESIGN COSTS. SEE ALSO DIVISION I GENERAL REQUIREMENTS. EXAMINATION OF SITE, DRAWINGS, SPECIFICATIONS: A.EXAMINE CAREFULLY THE SITE AND CONDITIONS OF THE SITE. PROVIDE ALL NECESSARY EQUIPMENT AND LABOR TO INSTALL A COMPLETE WORKING SYSTEM WITHIN THE SITE CONDITIONS. B.EXAMINE THE DRAWINGS AND SPECIFICATIONS AND 5 DAYS PRIOR TO BIDDING REPORT ANY ERRORS, OMISSIONS, INCONSISTENCIES, AND CONFLICTS TO THE ENGINEER TO BE REMEDIED IN AN ADDENDUM TO THE PROJECT PRIOR TO BID TIME. C.DRAWINGS ARE DIAGRAMMATIC AND CATALOG NUMBERS GIVEN ARE FOR REFERENCE ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE CAPACITY OF THE EQUIPMENT MEETS THE DRAWING REQUIREMENTS AND SHALL NOT DIMENSION FROM THE MECHANICAL, PLUMBING, OR PIPING DRAWINGS. D.THE LATEST ADOPTED VERSIONS OF THE INTERNATIONAL BUILDING CODES SHALL BE USED AS REQUIRED. THIS WILL ALSO INCLUDE THE LATEST ADOPTED VERSIONS OF THE MECHANICAL, PLUMBING, AND ENERGY CONSERVATION CODES. ALL METHODS AND MATERIALS REQUIRED BY THESE CODES SHALL BE REQUIRED BY THESE SPECIFICATIONS UNLESS INDICATED OTHERWISE. OTHER APPLICABLE LOCAL CODES AND ORDINANCES SHALL BE AS REQUIRED AND IT SHALL BE THE CONTRACTOR’S RESPONSIBILITY TO BE KNOWLEDGEABLE OF THESE REQUIREMENTS. E.WHERE INSTALLATION PROCEDURES OR ANY PART THEREOF ARE REQUIRED TO BE IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE MANUFACTURER OF THE MATERIAL BEING INSTALLED, PRINTED COPIES OF THESE RECOMMENDATIONS SHALL BE FURNISHED TO THE ENGINEER PRIOR TO INSTALLATION. INSTALLATION OF THE ITEM WILL NOT BE ALLOWED TO PROCEED UNTIL THE RECOMMENDATIONS ARE RECEIVED. FAILURE TO FURNISH THESE RECOMMENDATIONS CAN BE CAUSE FOR REJECTION OF THE MATERIAL. 44”MOUNTING HEIGHT ABOVE FINISHED FLOOR TO CENTER OF DEVICE A AMPS A.D.ACCESS DOOR AAV AIR ADMITTANCE VALVE ABV ABOVE AC AIR CONDITIONING UNIT AC ABOVE COUNTER AD AREA DRAIN (SEE SYMBOLS) A.F.C.ABOVE FINISHED CEILING A.F.G.ABOVE FINISHED GRADE AIC AMPERE INTERRUPTING CAPACITY AFCI ARC FAULT CIRCUIT INTERRUPTERS A.F.F.ABOVE FINISHED FLOOR AHU AIR HANDLING UNIT ALUM ALUMINUM AP ACCESS PANEL OR DOOR ATS AUTOMATIC TRANSFER SWITCH AV AUDIO / VIDEO AVG AVERAGE AWG AMERICAN WIRE GAGE BAS BUILDING AUTOMATION SYSTEM BB BASEBOARD BD BACK DRAFT DAMPER BFP BACK FLOW PREVENTOR BL BOILER BLDG BUILDING BLW BELOW BOB BOTTOM OF BEAM BOD BOTTOM OF DUCT BOP BOTTOM OF PIPE BSMT BASEMENT BTU BRITISH THERMAL UNIT C CHILLER CAFCI COMBINATION ARC FAULT CIRCUIT INTERRUPTERS CAP CAPACITY CB CIRCUIT BREAKER CBV CIRCUIT BALANCING VALVE CCT CORRELATED COLOR TEMPERATURE CKT CIRCUIT CFH CUBIC FEET PER HOUR CFM CUBIC FEET PER MINUTE CHWR CHILLED WATER RETURN CHWS CHILLED WATER SUPPLY CI CAST IRON CL CENTER LINE CLG CEILING CMU CONCRETE MASONRY UNIT CO CLEAN OUT COL COLUMN COMP COMPRESSOR CONC CONCRETE COND CONDENSATE CONN CONNECTION CONT CONTINUATION CONTR CONTRACTOR CRI COLOR RENDERING INDEX CT COOLING TOWER CT CURRENT TRANSFORMER CU CONDENSING UNIT CU COPPER CUH CABINET UNIT HEATER CVB CONSTANT VOLUME BOX CWR CONDENSER WATER RETURN CWS CONDENSER WATER SUPPLY DB DRY BULB DEPT DEPARTMENT DF DRINKING FOUNTAIN DIA DIAMETER DIAG DIAGRAM DIFF DIFFERENTIAL DISCH DISCHARGE DIV DIVISION DN DOWN DS DUCT SILENCER DWG DRAWING DX DIRECT EXPANSION (E) EXISTING EA EXHAUST AIR GRILLE/REGISTER EAT ENTERING AIR TEMPERATURE EC ELECTRICAL CONTRACTOR ECC ECCENTRIC EF EXHAUST FAN EFF EFFICIENCY EL ELEVATION ELEC ELECTRIC ELEV ELEVATOR EM EMERGENCY FUNCTION ENT ENTERING EMT ELECTRIC METALLIC TUBE EQ EQUAL EQUIP EQUIPMENT EQUIV EQUIVALENT ES END SWITCH ESP EXTERNAL STATIC PRESSURE ET EXPANSION TANK EWC ELECTRIC WATER COOLER EWT ENTERING WATER TEMPERATURE EX EXHAUST EXPAN EXPANSION EXT EXTERNAL F DEGREES FAHRENHEIT FA FREE AREA FC FAN COIL UNIT FC FOOTCANDLE FCV FLOW CONTROL VALVE FD FIRE DAMPER FD FLOOR DRAIN FIN FINISHED FLA FULL LOAD AMPS FLEX FLEXIBLE FLR FLOOR FOB FLAT ON BOTTOM FOT FLAT ON TOP FP FIRE PROTECTION FP FIRE PUMP FPM FEET PER MINUTE FPS FEET PER SECOND FS FLOW SWITCH FSD FIRE/SMOKE DAMPER FT FEET FXC FLEXIBLE CONNECTION GND GROUND GA GAUGE GAL GALLON GALV GALVANIZED GEC GROUND ELECTRODE CONDUCTOR GFCI / GFI GROUND FAULT CIRCUIT INTERRUPTER GC GENERAL CONTRACTOR GPH GALLONS PER HOUR GPM GALLONS PER MINUTE GRS/LB GRAINS PER POUND H 2O WATER HB HOSE BIBB HD HEAD (SEE SCHEDULES) HP HEAT PUMP HP HORSEPOWER HR HOUR HT HEIGHT HTR HEATER HWR HEATING WATER RETURN HWS HEATING WATER SUPPLY HX HEAT EXCHANGER HZ HERTZ ID INSIDE DIAMETER IG ISOLATED GROUND IN INCHES INV INVERT JBOX JUNCTION BOX K KELVIN KW KILOWATT KVA KILO VOLT - AMPS L LENGTH LAT LEAVING AIR TEMPERATURE LV LAVATORY LB POUND LD LINEAR DIFFUSER LF LINEAR FEET LIN LINEAR LIQ LIQUID LM LUMEN LRA LOCKED ROTOR AMPS LV LOUVER LVG LEAVING LWT LEAVING WATER TEMPERATURE MBH THOUSANDS OF BTU PER HOUR MC MECHANICAL CONTRACTOR MCA MINIMUM CIRCUIT AMPACITY MCB MAIN CIRCUIT BREAKER MD MOTORIZED DAMPER MDP MAIN DISTRIBUTION PANEL MED MEDIUM MFR MANUFACTURER MIN MINIMUM MISC MISCELLANEOUS MLO MAIN LUG ONLY MOCP MAXIMUM OVERCURRENT PROTECTION MTD MOUNTED MUA MAKE-UP AIR UNIT N NEUTRAL NC NORMALLY CLOSED NEG NEGATIVE NIC NOT IN CONTRACT NL NIGHT / SECURITY LIGHT - DO NOT SWITCH NO NORMALLY OPEN NOM NOMINAL NTS NOT TO SCALE OA OUTSIDE AIR OBD OPPOSED BLADE DAMPER OC ON CENTER OCC OCCUPIED OCP OVER CURRENT PROTECTION OD OUTSIDE DIAMETER OL OVERLOAD ORD OVERFLOW ROOF DRAIN OZ OUNCE PBD PARALLEL BLADE DAMPER PD PRESSURE DROP PH PHASE POS POSITIVE PRESSURE POS POINT OF SALES PRV PRESSURE REDUCING VALVE PS PRESSURE SWITCH PSI POUNDS PER SQUARE INCH PT PRESSURE TRANSMITTER PTAC PACKAGED TERMINAL AIR CONDITIONER PV PLUG VALVE PVC POLYVINYL CHLORIDE QTY QUANTITY RA RETURN AIR GRILLE / REGISTER RCP REFLECTED CEILING PLAN RD ROOF DRAIN REL RELIEF REQD REQUIRED RF RETURN FAN RH RELATIVE HUMIDITY RHC REHEAT COIL RLA RATED LOAD AMPS RM ROOM RPM REVOLUTIONS PER MINUTE SA SUPPLY AIR GRILLE / REGISTER SC SHORT CIRCUIT SCA SHORT CIRCUIT AVAILABLE SCCR SHORT CIRCUIT CURRENT RATING SCH SCHEDULE SD SMOKE DAMPER SEF SMOKE EXHAUST FAN SF SUPPLY FAN SH SENSIBLE HEAT SH SHOWER SP STATIC PRESSURE SPD SURGE PROTECTION DEVICE SPEC SPECIFICATION SQ SQUARE SS STAINLESS STEEL SS SAFETY SHOWER STD STANDARD STL STEEL SYS SYSTEM TEMP TEMPERATURE TR TRANSFER GRILLE / REGISTER TR TAMPER RESISTANT TT TEMPERATURE TRANSMITTER TTB TELECOMMUNICATIONS TERMINAL BACKBOARD TYP TYPICAL TX TRANSFORMER UC UNDERCUT DOOR UH UNIT HEATER UNO UNLESS NOTED OTHERWISE UNOCC UNOCCUPIED UR URINAL V VOLTS VA VOLT AMPERE VA VALVE VAV VARIABLE AIR VOLUME UNIT VFD VARIABLE FREQUENCY DRIVE VRF VARIABLE REFRIGERANT FLOW VOLT VOLTAGE VTR VENT THROUGH ROOF W WIDTH W WATTS W/ WITH W/O WITHOUT WB WET BULB WC WATER COLUMN WC WATER CLOSET WG WATER GAUGE WP WEATHERPROOF WPIU WEATHERPROOF IN-USE WSR WITHSTAND RATING XFMR TRANSFORMER SUBSTITUTIONS:RESPONSIBLE DIVISION: UNLESS OTHERWISE INDICATED ALL HEATING, VENTILATING, AIR CONDITIONING, PLUMBING, AND OTHER MECHANICAL EQUIPMENT, MOTORS, AND CONTROLS SHALL BE FURNISHED, SET IN PLACE AND WIRED AS FOLLOWS: ITEM FURNISHED SET POWER CONTROL WIRED WIRED EQUIPMENT 23 23 26 -- COMBINATION MAGNETIC MOTOR STARTERS, MAGNETIC MOTOR STARTERS, VFD'S AND CONTACTORS 23(1)26 26(2)23 FUSED AND UNFUSED DISCONNECT SWITCHES, THERMAL OVERLOAD SWITCHES AND HEATERS, MANUAL MOTOR STARTERS 26 26 26 -- MANUAL-OPERATING AND MULTI-SPEED SWITCHES 23 26 26 26 CONTROLS, RELAYS, TRANSFORMERS 23 23 26 23 THERMOSTATS (LOW VOLTAGE) AND TIME SWITCHES 23 23 26 23 THERMOSTATS (LINE VOLTAGE) 23 23 26 26 TEMPERATURE CONTROL PANELS 23 23 26 23 MOTOR AND SOLENOID VALVES, DAMPER MOTORS, PE & EP SWITCHES 23 23(2)--23(2) PUSH-BUTTON STATIONS AND PILOT LIGHTS 23 23(2)-- 23(2) HEATING, COOLING, VENTILATION AND AIR CONDITIONING CONTROLS 23 23 26 23 EXHAUST FAN SWITCHES 23 26 26 23(2) SUBSCRIPT FOOTNOTES: 1.MOTOR STARTER TO INCLUDE CONTROL TRANSFORMER, HOA SWITCH, (1) NO AND (1)NC AUXILIARY CONTACT, AND “ON” AND “OFF” PILOT LIGHTS. 2.IF ITEM IS FOR LINE VOLTAGE, SET IN PLACE AND CONNECT UNDER DIVISION 26. WHERE FACTORY MOUNTED ON EQUIPMENT OR ATTACHED TO PIPING OR DUCTS AND USING LINE VOLTAGE FURNISH AND SET UNDER DIVISION 23, CONNECT UNDER DIVISION 26. ABBREVIATIONS: SECURITY CAMERA SECURITY SYSTEM LEGEND ADA DOOR OPERATOR PUSH BUTTONHC F LA-7 BRANCH CIRCUIT PANELBOARD TELEPHONE TERMINAL BOARD ELECTRIC MOTOR FUSED SAFETY SWITCH / DISCONNECT COMBINATION MOTOR STARTER CONTACTOR CIRCUITRY HOMERUN: PANEL LA - CIR. #7 CONDUIT OR WIRE CONCEALED IN WALL/CLG. (SOLID LINE TYPE) CONDUIT OR WIRE UNDERFLOOR/UNDERGND. (CENTER LINE TYPE) FUSED DISCONNECT 100A = AMP RATING 2P = NUMBER OF POLES CIRCUIT BREAKER IN A PANEL BOARD PAD MOUNTED UTILITY TRANSFORMER M ELECTRICAL METER SHOWN ON ONE-LINE DIAGRAMS MAIN DISTRIBUTION GEAR ELECTRICAL POWER PANEL WITH MAIN LUG OR MAIN BREAKER PP1= PANEL NAME 225A MLO = MAIN LUG OR BREAKER SIZE 120/208V = PANEL VOLTAGE 3PH, 4 WIRE = PANEL PHASE, DISTRIBUTION TYPE 100 A 2 POLE FUSED DISCONNECT PP1 225A MLO 120/208V 3PH, 4W PP1 225A MCB 120/208V 3PH, 4W C INTERCOM PUSH TO CALL SWITCH CLOCK / PA SPEAKER WALL MOUNTED CLOCK ONLY COMMUNICATION LEGEND ABOVE THE CEILING PROJECTOR CONNECTION WALL MOUNTED HDMIHDMI PLAIN DATA OUTLET PROJECTOR WIRELESS ACCESS POINT ABOVE THE CEILING ROUND CEILING MOUNTED SPEAKER WAP PLAIN DATA OUTLET WITH MOUNTING HEIGHT80" SQUARE SPEAKERS ELECTRICAL EQUIPMENT LEGEND S S S S S S S S S S S S S OS EMR A WALL MOUNTED SCONCE LIGHT FIXTURE RECESSED DOWNLIGHT CAN FIXTURE SURFACE CEILING OR PENDANT MOUNTED FIXTURE DOUBLE FACE EXIT SIGN, WALL AND CEILING MOUNTED SINGLE FACE EXIT SIGN, WALL AND CEILING MOUNTED WALL MOUNTED EMERGENCY LIGHT EMERGENCY EXTERIOR EGRESS FIXTURE SWITCHES LIGHT FIXTURES EM EX1 EX2 A A A DR D 4 3 2 LV TO MA SINGLE POLE SWITCH TWO POLE SWITCH THREE-WAY SWITCH FOUR-WAY SWITCH DIMMER SWITCH DOOR ACTIVATED SWITCH LOW VOLTAGE LIGHT SWITCH MANUAL MOTOR STARTER OS MA P PILOT LIGHT SWITCH AUTO ON / AUTO OFF LIGHT SWITCH A 3D 3 WAY DIMMER SWITCH - (4D INDICATES A 4WAY DIMMER) NOTES: SYMBOLS SHOWN ARE STANDARD. VARIATION AND/OR COMBINATIONS MAY BE USED ON THE PLANS. THIS LIST SHOWS STANDARD SYMBOLS AND ALL MAY NOT APPEAR ON THE PROJECT DRAWINGS; HOWEVER, WHEREVER THE SYMBOL ON THE PROJECT DRAWINGS OCCUR, THE ITEM SHALL BE PROVIDED AND INSTALLED. VARIATION AND/OR COMBINATION MAY BE USED ON THE PLANS. A NUMBER NEXT TO A RECEPTACLE OR DEVICE INDICATES A CIRCUIT NUMBER. AN UPPER CASE LETTER NEXT TO A SWITCH INDICATES THE FUNCTION OF THE SWITCH. A LOWER CASE LETTER INDICATES THE SWITCH CIRCUIT. AN UPPER CASE LETTER NEXT TO A LIGHT FIXTURE INDICATES THE TYPE OF FIXTURE. REFER TO THE LUMINAIRE SCHEDULE FOR FIXTURE SPECIFICATIONS. A LOWER CASE LETTER NEXT TO A LIGHT CORRESPONDS TO THE SWITCH DESIGNATION. OS CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH WALL MOUNTED DUAL TECHNOLOGY MANUAL ON / AUTO OFF VACANCY SENSOR SWITCH A 2'x4' LED TROFFER OR DIRECT/INDIRECT TYPE FIXTURE GRID, FLANGE OR SURFACE MOUNTED 1'x4' LED TROFFER OR DIRECT/INDIRECT TYPE FIXTURE GRID, FLANGE OR SURFACE MOUNTED 2'x2' LED TROFFER OR DIRECT/INDIRECT TYPE FIXTURE GRID, FLANGE OR SURFACE MOUNTED S S K T KEY OPERATED LIGHT SWITCH MANUAL ON / AUTO OFF DIMMING LIGHT SWITCH SSC SCENE CONTROL STATION SMS UNIT LIGHTING MANAGEMENT CONTROL STATION, LIGHTING LEGEND ELECTRIC DOOR STRIKEDS CARD READER FOR DOOR OPERATORCR S SMO COMBINATION DATA/TELEPHONE FLOOR MOUNTED COMBINATION DATA/TELEPHONE CEILING MOUNTED COMBINATION DATA/TELEPHONE TELEVISION OUTLET DUAL TECHNOLOGY MOTION / OCCUPANCY SENSOR LIGHT SWITCH MANUAL ON - TIMED OFF LIGHT SWITCH WALL BRACKET LINEAR FIXTURE OPEN STRIP FIXTUREJ D MA MA CEILING MOUNTED DUAL TECHNOLOGY MANUAL ON / AUTO OFF VACANCY SENSOR RL F FLOW SWITCH PIR DETECTOR SMOKE DETECTOR - PHOTOELECTRIC REMOTE LAMP D DUCT DETECTOR CEILING MOUNTED SPEAKER FIRE ALARM HORN/STROBE FIRE ALARM STROBE FIRE ALARM HORN FIRE ALARM PULL STATION FIRE ALARM EQUIPMENT LEGEND TAMPER SWITCH FS PIR TS P H 135°135° STANDARD HEAT DETECTOR S DOOR HOLD - MAGNETIC HOLDDH FIRE ALARM CONTROL PANELFACP T D J J ROOM 100 CEILING JUNCTION BOX - SURFACE/FLUSH WALL JUNCTION BOX - SURFACE/FLUSH DUPLEX RECEPTACLE FLOOR MOUNTED RECEPTACLE SPLIT WIRED DUPLEX RECEPTACLE CEILING MOUNTED DUPLEX RECEPTACLE FOURPLEX RECEPTACLE FLOOR MOUNTED FOURPLEX RECEPTACLE APPLIANCE RECEPTACLE - 3 WIRE THERMOSTAT DRAWING KEY NOTES ROOM DESIGNATION ELECTRIC HAND DRYER OPEN/CLOSE/STOP PUSH BUTTON ELECTRICAL DEVICE LEGEND 1 ABBREVIATIONS PERTAIN TO ALL DUPLEX AND FOURPLEX RECEPTACLES: AC ABOVE COUNTER AC GF ABOVE COUNTER - GROUND FAULT CIRCUIT INTERRUPTER AC USB ABOVE COUNTER WITH USB PORT AF ARC FAULT PROTECTED AF USB ARC FAULT PROTECTED WITH USB PORT AF GF ARC FAULT WITH GROUND FAULT CIRCUIT INTERRUPTER D DEDICATED RECEPTACLE D USB DEDICATED RECEPTACLE WITH USB PORT EM RECEPTACLE CIRCUITED TO THE EMERGENCY PANEL WITH RED COVER PLATE GF GROUND FAULT CIRCUIT INTERRUPTER GF WP WEATHER PROOF GROUND FAULT CIRCUIT INTERRUPTER PL PLUG LOAD 72"GENERAL PURPOSE WITH MOUNTING HEIGHT. DUPLEX RECEPTACLE DS DS CEILING MOUNTED DAYLIGHT HARVESTING SENSOR GENERAL ELECTRICAL NOTES: 1.ALL ELECTRICAL WORK TO COMPLY WITH LATEST EDITION OF NEC, IECC AND ALL APPLICABLE GOVERNING CODES. 2.FIELD COORDINATION DURING CONSTRUCTION IS IMPERATIVE. CONTRACTORS BIDDING THIS WORK MUST MAKE REASONABLE ALLOWANCES FOR UNFORESEEN CONTINGENCIES. 3.ELECTRIC UTILITY TO ADVISE OWNER AND/OR THE ELECTRICAL ENGINEER PRIOR TO SERVICE MODIFICATION REQUIRING COST TO THE OWNER. WIRING: 1.ALL WIRING IS SHOWN DIAGRAMMATICALLY ON DRAWING, FIELD VERIFY ALL CONDITIONS PRIOR TO ROUGH-IN. 2.ALL CONDUITS AND CONVEYANCES SHALL BE CONCEALED. IN THE EVENT THAT A NEW DEVICE IS BEING INSTALLED IN AN EXISTING DRYWALL PARTITION, PROVIDE A CUT IN TYPE BOX AND FISH FLEXIBLE CONDUIT DOWN INSIDE THE WALL FROM ABOVE THE CEILING AND REPAIR THE DRYWALL AROUND THE CONDUIT. TRANSITION TO EMT ONCE ABOVE THE CEILING. 3.SIZES OF WIRE AND CABLES ARE BASED UPON COPPER CONDUCTORS, UNLESS OTHERWISE INDICATED. ALL CIRCUITS SHALL CONTAIN (2) #12 AWG WITH (1) #12 GND IN 1/2" CONDUIT UNLESS NOTED OTHERWISE. 4.ALL BRANCH CIRCUITS WITH HOME RUNS OVER 50 FEET, WILL BE SIZED ONE SIZE LARGER. 5.ALL PENETRATIONS IN OR THROUGH FIRE RATED PARTITIONS SHALL BE FIRE STOPPED IN SUCH A WAY THAT THE PENETRATION MATCHES THE FIRE RATING OF THE WALL. 6.THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL COORDINATION BETWEEN THE APPROPRIATE DISCIPLINES AND CONTRACTORS. 7.COORDINATE ALL DEVICE, FIXTURE AND HARDWARE COLOR SELECTIONS WITH THE ARCHITECT PRIOR TO MAKING SHOP DRAWING SUBMITTALS. 8.COORDINATE THE MOUNTING HEIGHTS OF ALL RECEPTACLES MOUNTED ABOVE COUNTERS, CASEWORK AND APPLIANCE RECEPTACLES WITH ARCHITECTURAL ELEVATIONS. 9.BRANCH CIRCUIT AND SPECIAL SYSTEMS WIRING FOR DEVICES ON WALLS IN FINISHED AREAS WHICH CANNOT BE CONCEALED SHALL BE INSTALLED IN SURFACE MOUNTED RACEWAY. 10.ALL EXPOSED CONDUITS, BOXES, ETC. IN ROOMS TO BE PAINTED SHALL BE PAINTED TO MATCH THE SURROUNDING SURFACE. EXPOSED CONDUITS, BOXES, ETC. IN ROOMS WHICH ARE NOT PAINTED MAY BE LEFT UN-PAINTED. EXPOSED CONDUIT, BOXES, ETC. ON THE EXTERIOR OF BUILDINGS SHALL BE PAINTED TO MATCH THE SURROUNDING SURFACE AS CLOSELY AS POSSIBLE. 11.THE CONTRACTOR IS RESPONSIBLE FOR PATCHING, PAINTING, REPAIRING OR REPLACEMENT OF ALL WALLS, CEILING OR OTHER BUILDING ELEMENTS WHICH ARE DISTURBED AS PART OF THE DEMOLITION AND/OR INSTALLATION OF ELECTRICAL WORK. 12.PROVIDE ELECTRICAL CONNECTION TO ALL FIRE, SMOKE, AND FIRE / SMOKE DAMPERS INCLUDING POWER AND FIRE ALARM. VERIFY EXACT SIZE AND FINAL LOCATION OF ALL DAMPERS WITH THE MECHANICAL CONTRACTOR. ALL ROOFTOP UNITS RATED AT MORE THAN 2000 CFM WILL BE OUTFITTED WITH A DUCT DETECTOR IN THE RETURN DUCT. ALL ROOFTOP UNITS RATED AT MORE THAN 15000 CFM WILL BE OUTFITTED WITH A DUCT DETECTOR IN BOTH THE SUPPLY AND RETURN DUCT AT ROOFTOP LEVEL AND IN THE RETURN DUCT AT EVERY LEVEL THAT IS SERVED. ELECTRICAL CONTRACTOR WILL PROVIDE A REMOTE TEST STATION AND ALL WIRING NECESSARY TO COMPLETE INSTALLATION. 13.REFER TO THE MECHANICAL EQUIPMENT SCHEDULE FOR ADDITIONAL REQUIREMENTS ASSOCIATED WITH PLUMBING AND HVAC EQUIPMENT AND OWNER/GENERAL CONTRACTOR FURNISHED EQUIPMENT. LUMINAIRES: 1.COORDINATE THE LOCATION OF ALL LIGHTING EQUIPMENT INCLUDING BUT NOT LIMITED TO THE LUMINAIRES, SWITCHES WITH THE ARCHITECTURAL, STRUCTURAL AND MECHANICAL DRAWINGS AND ALL OTHER TRADES AS REQUIRED. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLANS FOR DIMENSIONAL LOCATION OF LIGHT FIXTURES. 2.LIGHTING FIXTURES SHALL BE SUPPORTED FROM THE STRUCTURE ABOVE AND SHALL NOT BE SUPPORTED FROM THE T-BAR CEILING GRID. 3.THE ELECTRICAL CONTRACTOR IS TO CONFIRM THE LIGHT FIXTURES ORDERED WILL BE COMPATIBLE WITH THE CEILING TYPES AS SHOWN ON THE ARCHITECTURAL REFLECTED CEILING PLANS. NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO ORDERING THE FIXTURES. 4.VERIFY LUMINAIRE MOUNTING REQUIREMENTS AND OVERALL HEIGHT OF ALL PENDANT MOUNTED FIXTURES PRIOR TO ORDERING. 5.ALL LIGHT FIXTURES NEED TO BE COMPATIBLE WITH THE SWITCHES AND CONTROLS BEING PROVIDED. 6.THE LIGHTING PACKAGE SHALL BE APPROVED BY BOTH THE ARCHITECT AND ENGINEER AS APPROVED EQUAL BEFORE BID. NO LIGHT FIXTURE SHALL BE ORDERED UNTIL THE LIGHT FIXTURE SUBMITTAL PACKAGE HAS BEEN APPROVED IN WRITING BY THE ARCHITECT, GENERAL CONTRACTOR AND ELECTRICAL ENGINEER. 7.COORDINATE LUMINAIRE MOUNTING REQUIREMENTS PRIOR TO PLACING ORDER. DATE:ISSUED FOR: SHEET NUMBER: August 26, 2025 - 8:52:31am DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 DATE: CHECKED BY: JOB NO: DRAWN BY: SCALE: 7/01/25 PERMIT REVIEW 8/26/25 PERMIT - REVISION #1 E0-1 EL E C T R I C A L - CO V E R S H E E T GA R C O P R E M I E R H A N G A R S 37 5 C R 3 5 2 RB DB 07/01/2025 25-216 RI F L E , C O L O R A D O HANGAR BAY 1 HANGAR BAY 2 ADA RESTROOM JJ GF 44 " GF 44 " GF 44 " GF 44 " GF 44 " GF 44 " GF 44 " GF 44" GF 44" GF 44" GF 44" GF 44" GF 44" GF 44 " GF 44 " GF 44 " GF 44 " GF 44 " GF 44 " GF 44 " GF AC GFWP GF WP P1 P2 P1-2 P1-1 P1-3 P1-5,7,9 HP HP-4 GENERAL ELECTRICAL NOTES: 1.INSTALL ELECTRICAL EQUIPMENT PER ARTICLE 513 NEC 2017 PER ARTICLE 513.3C(1). 2.AIRCRAFT WILL NOT BE PARKED WHERE THE WING WILL BE WITHIN 5 FEET OF A WALL HORIZONTALLY AND THERE WILL NOT BE ANY ELECTRICAL EQUIPMENT WITHIN 5' OF THE WING OR ENGINE COWLING VERTICALLY. 3.REFUELING OR MAINTENANCE DOES NOT OCCUR WITHIN THE HANGAR SPACE. ELECTRICAL KEYNOTES: 1.CIRCUIT EXHAUST FAN WITH LIGHTING CIRCUIT 2.CIRCUIT FANS SEPARATELY FROM LIGHTING CONTROLS. 3.INSTALL PANELS SUCH THAT THE BOTTOM OF THE ENCLOSURES ARE GREATER THAN 24" ABOVE FINISHED FLOOR 4.JUNCTION BOX TO SUPPLY DOOR POWER TRACK. COORDINATE WITH DOOR CONTRACTOR FOR FINAL LOCATION. 1 22 METER STACK 3 3 4 4 GF GF GF GF P1-2 P2-3 P2-5,7,9 P2-2 P2-1 P2-8 HP-2,4 HP-3 FIRE SUPPRESSION SYSTEM LOCATION 2 TAMPERS, 1 FLOW COORDINATE WITH FIRE PROTECTION ENGINEER FOR DETAILS DATE:ISSUED FOR: SHEET NUMBER: August 26, 2025 - 8:52:31am DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 DATE: CHECKED BY: JOB NO: DRAWN BY: SCALE: 7/01/25 PERMIT REVIEW 8/26/25 PERMIT - REVISION #1 E2-1 EL E C T R I C A L - FL O O R P L A N GA R C O P R E M I E R H A N G A R S 37 5 C R 3 5 2 RI F L E , C O L O R A D O ELECTRICAL - FLOOR PLAN SCALE: NORTH SCALE:1/8" = 1'-0" RB DB 07/01/2025 25-216 AS SHOWN 400A 120/208V 3 POLE NEMA 3R CLASS RK1 A UTILITY TRANSFORMER ONE-LINE DIAGRAM NOTES: 1.PROVIDE GROUNDING AND BONDING TO MEET THE 2023 NEC ARTICLE 250 REQUIREMENTS. 2.PROVIDE LABELING TO MEET THE REQUIREMENTS OF NEC 110.21. 7.7kA SCA G1 B P1 200A MCB 120/208V 3Ø,4W 10kAIC NEMA 1 WIRE SCHEDULE: A (2) 3"C - (4#250kCMIL(AL,THWN)) B #2AWG CU TO METAL WATER PIPES AND STRUCTURAL STEEL #4AWG CU TO 20' UNCOATED CONCRETE ENCASED ELECTRODE 2"C - (4#3AWG(CU,THHN) + 1#8AWG(CU)G) G1 C P2 200A MCB 120/208V 3Ø,4W 10kAIC NEMA 1 D HP 60A MLO 120/208V 3Ø,4W 10kAIC NEMA3R C 2"C - (4#3AWG(CU,THHN) + 1#8AWG(CU)G) D 2"C - (4#6AWG(CU,THHN) + 1#10AWG(CU)G) 200A 60A 200A METER STACK 120/208V 3Ø, 4W PANEL SCHEDULE - HP TYPE:PANELBOARD BUS SIZE:60 PHASES:3 NEUTRAL BUS:YES VOLTAGE:120/208 MAIN BRKR:NONE WIRES:4 GROUND BUS:YES ENCLOSURE:NEMA3R MOUNTING:SURFACE SC RATING:10000 LOAD TYPE LOAD DESCRIPTION AMPS CKT#0/CKT#AMPS LOAD TYPE LOAD DESCRIPTION POLES LOAD LOAD POLES LIGHTING EXTERIOR LIGHTS 20A 1 A 2 40A MECH YEAR ROUND EUH-1 ---1P 324 2507 2P --- LIGHTING BATHROOM LIGHT + EF 20A 3 B 4 ---MECH YEAR ROUND --- ---1P 125 2507 ------ MECH HEATING WH-1 30A 5 C 6 20A RECEPTACLE RESTROOM ---1P 2400 180 1P GROUND FAULT BREAKER 5 MA SPACE ------7 A 8 ---SPACE --- ------0 0 ------ SPACE ------9 B 10 ---SPACE --- ------0 0 ------ SPACE ------11 C 12 ---SPACE --- ------0 0 ------ SPACE ------13 A 14 ---SPACE --- ------0 0 ------ SPACE ------15 B 16 ---SPACE --- ------0 0 ------ SPACE ------17 C 18 ---SPACE --- ------0 0 ------ SPACE ------19 A 20 ---SPACE --- ------0 0 ------ SPACE ------21 B 22 ---SPACE --- ------0 0 ------ SPACE ------23 C 24 ---SPACE --- ------0 0 ------ SPACE ------25 A 26 ---SPACE --- ------0 0 ------ SPACE ------27 B 28 ---SPACE --- ------0 0 ------ SPACE ------29 C 30 ---SPACE --- ------0 0 ------ LOADS BY TYPE:LOADS BY PHASE: LOAD CONNECTED DEMAND DEMAND CONNECTED CONNECTED BALANCE TYPE LOAD (VA)FACTOR LOAD (VA)PHASE LOAD (VA)LOAD (AMPS)(PERCENT) LIGHTING 449.00 1.25 561.25 A 2830.50 23.59 A-B: 93 KITCHEN 0.00 0.00 0.00 B 2631.50 21.93 B-C: 98 PROCESS 0.00 1.00 0.00 C 2580.00 21.50 C-A: 91.1 RECEPTACLES 180.00 1.00 180.00 MECH HEATING 2400.00 1.00 2400.00 TOTAL/AVERAGE 8042.00 22.34 94.1 MECH COOLING 0.00 1.00 0.00 MECH YEAR ROUND 5013.00 1.00 5013.00 NOTES: APPLIANCE 0.00 1.00 0.00 MISCELLANEOUS 0.00 1.00 0.00 1. THE LARGEST CONNECTED MOTOR LOAD IS INCLUDED IN MECHANICAL, PROCESS, OR MOTOR LOADS. MOTOR 0.00 1.00 0.00 SPARE 0.00 1.00 0.00 LARGEST MOTOR 1 ABOVE 0.25 1253.25 TOTAL 8042.00 9408.00 PANEL SCHEDULE - P1 TYPE:PANELBOARD BUS SIZE:225 PHASES:3 NEUTRAL BUS:YES VOLTAGE:120/208 MAIN BRKR:200 WIRES:4 GROUND BUS:YES ENCLOSURE:NEMA1 MOUNTING:SURFACE SC RATING:10000 LOAD TYPE LOAD DESCRIPTION AMPS CKT#0/CKT#AMPS LOAD TYPE LOAD DESCRIPTION POLES LOAD LOAD POLES RECEPTACLE HANGAR WEST RECEPT 20A 1 A 2 20A MOTOR FAN CIRCUIT GROUND FAULT BREAKER 5 MA 1P 1080 54 1P --- RECEPTACLE HANGAR EAST RECEPT 20A 3 B 4 20A LIGHTING LIGHTING B GROUND FAULT BREAKER 5 MA 1P 900 1704 1P --- MOTOR ------5 C 6 20A LIGHTING LIGHTING A ------3333 852 1P --- MOTOR HANGAR DOOR 35A 7 A 8 20A MECH YEAR ROUND IR-1, IR-2 ---3P 3333 540 1P --- MOTOR ------9 B 10 ---SPACE --- ------3333 0 ------ SPACE ------11 C 12 ---SPACE --- ------0 0 ------ SPACE ------13 A 14 ---SPACE --- ------0 0 ------ SPACE ------15 B 16 ---SPACE --- ------0 0 ------ SPACE ------17 C 18 ---SPACE --- ------0 0 ------ SPACE ------19 A 20 ---SPACE --- ------0 0 ------ SPACE ------21 B 22 ---SPACE --- ------0 0 ------ SPACE ------23 C 24 ---SPACE --- ------0 0 ------ SPACE ------25 A 26 ---SPACE --- ------0 0 ------ SPACE ------27 B 28 ---SPACE --- ------0 0 ------ SPACE ------29 C 30 ---SPACE --- ------0 0 ------ SPACE ------31 A 32 ---SPACE --- ------0 0 ------ SPACE ------33 B 34 ---SPACE --- ------0 0 ------ SPACE ------35 C 36 ---SPACE --- ------0 0 ------ SPACE ------37 A 38 ---SPACE --- ------0 0 ------ SPACE ------39 B 40 ---SPACE --- ------0 0 ------ SPACE ------41 C 42 ---SPACE --- ------0 0 ------ LOADS BY TYPE:LOADS BY PHASE: LOAD CONNECTED DEMAND DEMAND CONNECTED CONNECTED BALANCE TYPE LOAD (VA)FACTOR LOAD (VA)PHASE LOAD (VA)LOAD (AMPS)(PERCENT) LIGHTING 2556.00 1.25 3195.00 A 5007.30 41.73 A-B: 84.3 KITCHEN 0.00 0.00 0.00 B 5937.30 49.48 B-C: 70.5 PROCESS 0.00 1.00 0.00 C 4185.30 34.88 C-A: 83.6 RECEPTACLES 1980.00 1.00 1980.00 MECH HEATING 0.00 1.00 0.00 TOTAL/AVERAGE 15130.00 42.03 79.5 MECH COOLING 0.00 1.00 0.00 MECH YEAR ROUND 540.00 1.00 540.00 NOTES: APPLIANCE 0.00 1.00 0.00 MISCELLANEOUS 0.00 1.00 0.00 1. THE LARGEST CONNECTED MOTOR LOAD IS INCLUDED IN MECHANICAL, PROCESS, OR MOTOR LOADS. MOTOR 10054.00 1.00 15081.00 SPARE 0.00 1.00 0.00 LARGEST MOTOR 1 ABOVE 0.25 2500.00 TOTAL 15130.00 18269.00 PANEL SCHEDULE - P2 TYPE:PANELBOARD BUS SIZE:225 PHASES:3 NEUTRAL BUS:YES VOLTAGE:120/208 MAIN BRKR:200 WIRES:4 GROUND BUS:YES ENCLOSURE:NEMA1 MOUNTING:SURFACE SC RATING:10000 LOAD TYPE LOAD DESCRIPTION AMPS CKT#0/CKT#AMPS LOAD TYPE LOAD DESCRIPTION POLES LOAD LOAD POLES RECEPTACLE HANGAR EAST RECEPT 20A 1 A 2 20A MOTOR FAN CIRCUIT GROUND FAULT BREAKER 5 MA 1P 1080 54 1P --- RECEPTACLE HANGAR WEST RECEPT 20A 3 B 4 20A LIGHTING LIGHTING B GROUND FAULT BREAKER 5 MA 1P 900 1704 1P --- MOTOR ------5 C 6 20A LIGHTING LIGHTING A ------3333 852 1P --- MOTOR HANGAR DOOR 30A 7 A 8 20A MECH YEAR ROUND IR-1, IR-2 ---3P 3333 540 1P --- MOTOR ------9 B 10 ---SPACE --- ------3333 0 ------ SPACE ------11 C 12 ---SPACE --- ------0 0 ------ SPACE ------13 A 14 ---SPACE --- ------0 0 ------ SPACE ------15 B 16 ---SPACE --- ------0 0 ------ SPACE ------17 C 18 ---SPACE --- ------0 0 ------ SPACE ------19 A 20 ---SPACE --- ------0 0 ------ SPACE ------21 B 22 ---SPACE --- ------0 0 ------ SPACE ------23 C 24 ---SPACE --- ------0 0 ------ SPACE ------25 A 26 ---SPACE --- ------0 0 ------ SPACE ------27 B 28 ---SPACE --- ------0 0 ------ SPACE ------29 C 30 ---SPACE --- ------0 0 ------ SPACE ------31 A 32 ---SPACE --- ------0 0 ------ SPACE ------33 B 34 ---SPACE --- ------0 0 ------ SPACE ------35 C 36 ---SPACE --- ------0 0 ------ SPACE ------37 A 38 ---SPACE --- ------0 0 ------ SPACE ------39 B 40 ---SPACE --- ------0 0 ------ SPACE ------41 C 42 ---SPACE --- ------0 0 ------ LOADS BY TYPE:LOADS BY PHASE: LOAD CONNECTED DEMAND DEMAND CONNECTED CONNECTED BALANCE TYPE LOAD (VA)FACTOR LOAD (VA)PHASE LOAD (VA)LOAD (AMPS)(PERCENT) LIGHTING 2556.00 1.25 3195.00 A 5007.30 41.73 A-B: 84.3 KITCHEN 0.00 0.00 0.00 B 5937.30 49.48 B-C: 70.5 PROCESS 0.00 1.00 0.00 C 4185.30 34.88 C-A: 83.6 RECEPTACLES 1980.00 1.00 1980.00 MECH HEATING 0.00 1.00 0.00 TOTAL/AVERAGE 15130.00 42.03 79.5 MECH COOLING 0.00 1.00 0.00 MECH YEAR ROUND 540.00 1.00 540.00 NOTES: APPLIANCE 0.00 1.00 0.00 MISCELLANEOUS 0.00 1.00 0.00 1. THE LARGEST CONNECTED MOTOR LOAD IS INCLUDED IN MECHANICAL, PROCESS, OR MOTOR LOADS. MOTOR 10054.00 1.00 15081.00 SPARE 0.00 1.00 0.00 LARGEST MOTOR 1 ABOVE 0.25 2500.00 TOTAL 15130.00 18269.00 DATE:ISSUED FOR: SHEET NUMBER: August 26, 2025 - 8:52:33am DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 DATE: CHECKED BY: JOB NO: DRAWN BY: SCALE: 7/01/25 PERMIT REVIEW 8/26/25 PERMIT - REVISION #1 E3-1 EL E C T R I C A L - DE T A I L S GA R C O P R E M I E R H A N G A R S 37 5 C R 3 5 2 RB DB 07/01/2025 25-216 RI F L E , C O L O R A D O