9/21/2026
Encompass Design
Attn: Jenn Clary
Project: Aster Place Community Building
Location: Parachute, CO
Re: Stacked Window Framing
To Whom it may concern:
DCI Engineers has reviewed the specific wall framing conditions at the Community
Building described by the Contractor and Inspector, including the header configuration
at the window openings and the framing arrangement between the vertically stacked
windows.
Based on our review, the condition where framing above the windows bears on the built-
up header assembly with approximately 3 inches of bearing is acceptable as
constructed. The header assembly provides an adequate load path to the supporting
king and trimmer studs.
DCI has also reviewed the condition where the cripple studs are interrupted by the
intermediate window openings within the vertically stacked window assembly. Although
the cripple studs are not continuous through the full wall height, the framing
configuration is acceptable provided the framing members are adequately connected to
transfer loads to the supporting king and trimmer studs and maintain a continuous load
path.
This determination is based on the framing members being adequately fastened
together to provide the required load transfer between framing elements. Positive
attachment shall be provided between the headers, king studs, cripple studs, and
adjacent framing members in accordance with the applicable requirements of the
adopted International Building Code and standard wood framing practice.
Based on our review of the specific conditions described above, the framing is
acceptable as constructed.
Sincerely,
DCI Engineers
Matthew Schmidt PE, SE, PEng
Vice President/Principal