Loading...
HomeMy WebLinkAboutCorrespondence with Fire DistrictJohn Plano From: Karl Oliver <koliver@carbondalefire.org> Sent: Wednesday, July 8, 2026 3:55 PM To: John Plano Subject: RE: Extreme Hocky Tent Structure That is correct John, we exempted the sprinkler requirement based on 903.2.1.4 Group A-4 (skating rinks) and 2015 IFC unless one of the following conditions exists. 1. Fire area exceeds 12,000 sq ft. Plans indicated 11,520 sq ft. (LO.O Occupant Load Sec). 2. Occ load exceeds 300. Plans indicated 230 for Occupancy. 3. The floor area of the building is all on the level of exit discharge. Thanks, �,��*� .� w..o o� o It- 0 Karl Oliver Prevention Division Chief Fire Marshal Carbondale & Rural Fire Protection District 300 Meadowood Drive Carbondale, CO 81623 Office - (970) 963-2491 Cell - NUMBER CHANGE — (970) 505-0577 www.carbondalefire.orq From: John Plano <jplano@garfieldcountyco.gov> Sent: Wednesday, July 8, 2026 2:22 PM To: Karl Oliver <koliver@carbondalefire.org> Subject: Extreme Hocky Tent Structure External (jplano@garfieldcountyco.gov) A GUARDIAN Hi Karl, I thought the Fire District is waiving the sprinkler requirements, because of the lack of fire Loading, the Letter you provided does not state that. From your letter: Garfield County Ordinance NO. 2018-02: • Section 903 Automatic Sprinklers systems where required (903.2 (2)). o Covered rink + 2-B building with maximum floor area <= 9,000 sq/ft total floor area will be exempt from needing a sprinkler system. 1 Two Questions: Are you waiving the amendment to the Fire Code and allowing this structure to be non -sprinkled? I was wondering if you received the information on the tent? Thankyou, John Plano Chief Building Official Garfield County Building Department 108 8th Street #401 Glenwood Springs, CO 81601 (970) 945-1377 Ext. 1560 Garfield County's email domain has changed to @garfieldcountyco.gov. arfieldcountyco.gov. Please take a moment to update my contact information. John Plano From: Karl Oliver <koliver@carbondalefire.org> Sent: Wednesday, July 8, 2026 5:00 PM To: John Plano Subject: RE: Extreme Hocky Tent Structure FABRIC MATERIAL MATERIAL: RU88X-6(FR), 400 NOVA SHIELD II TM MEMBRANE STRUCTURE FABRICS WEAVE: WOVEN CLEAR HDPE SCRIM WITH UV TAPES COATING: LDPE, 4 MIL AVERAGE EACH SIDE (95 G/M42/SIDE) WEIGHT: 12.4 OZND^2 (407 G/MA2) +/-5% THICKNESS: 23 MILS (0,59 MM) ASTM D5199 FIRE RATING: NFPA-701 (1989) LARGE SCALE; CAN/ULC S109-M87 (LARGE SCALE), AND ASTM E84-OOA (CLASS 1) PERFORMANCE WARP VVEFT TESTING METHOD GRAB TENSILE, L8$, (N) 370 06641 5 (1555) ASTM D5034-09 H r ItNSiLt. LBS.iINCH fN/5CM) 260 (2311) 240 (2100) ASTM D5035-11 TRAPE70IDAL TEAR. LBS. 90 (400) 90 (400) ASTM D4533.01 M (2009) TONGUE TEAR. LBS, (N) 115 (510) 110 {489) ASTM D2261-07A MULLEN BURST 1 670 PSV4623 KPA ASTM D37BE-09 ASTM 36-02 COLD RESISTANCE -60 DEGREES C (200707) ACCELERATED UV 5 90% STRENGTH AFTER 2000 G154-06 WFATHFRING I HR5. John, this is the Fabric testing on the plans. Question: does the NFPA— 701(1989) indicate the age of the material? In other words, is it used? The new standard for NFPA -701 is 2023 that I have referenced for testing. The rating, based on this document, appears to meet standards. Thanks, o a y a i�: i• f 14f Rtti c Karl Oliver Prevention Division Chief Fire Marshal Carbondale & Rural Fire Protection District 300 Meadowood Drive Carbondale, CO 81623 Office - (970) 963-2491 Cell - NUMBER CHANGE — (970) 505-0577 www.carbondalefire.orsl From: John Plano <jplano@garfieldcountyco.gov> Sent: Wednesday, July 8, 2026 2:22 PM To: Karl Oliver <koliver@carbondalefire.org> Subject: Extreme Hocky Tent Structure 1 External Oplano@garfieldcountyco.gov) GUARDIAN Hi Karl, I thought the Fire District is waiving the sprinkler requirements, because of the lack of fire loading, the Letter you provided does not state that. From your letter: Garfield County Ordinance NO. 2018-02: Section 903 Automatic Sprinklers systems where required (903.2 (2)). o Covered rink + 2-13 building with maximum floor area <= 9,000 sq/ft total floor area will be exempt from needing a sprinkler system. Two Questions: Are you waiving the amendment to the Fire Code and allowing this structure to be non -sprinkled? I was wondering if you received the information on the tent? Thank you, John Plano Chief Building Official Garfield County Building Department 108 8` Street #401 Glenwood Springs, CO 81601 (970) 945-1377 Ext. 1560 Garfield County's email domain has changed to @garfieldcountyco.go_v_. Please take a moment to update my contact information.