HomeMy WebLinkAbout2536 \ chen and associates CONSULTING GEOTECHNICAL ENGINEERS 5080 RD. 154 GLENWOOD SPRINGS.COLORADO 81801 303/945 -7458 April 8, 1982 Subject: Excavation Observation, Addition to Los Desperados Restaurant, West Glenwood Springs, Colorado Job No. 24,000 Mr. Jim Griffin 0055 Mel -Rey Rd. Glenwood Springs, CO 81601 Dear Sir: As requested, we observed the foundation excavation at the subject site on April 7, 1982 to determine the general subgrade conditions for foundation support.. At the time of our site visit, footing trenches had been excavated from 1 1/2 to 3 feet below the relatively level adjacent ground surface. The soils exposed at bearing level consisted of medium stiff, porous clays underlying fill consisting of gravelly clay and silt with scattered cobbles. Several areas containing gravelly fill adjacent to existing structures had not been completely excavated to footing grade at this time. Results of consolidation tests performed on relatively undisturbed samples of the natural clays obtained at footing grade in the trenches indicate moderate to high settlement potential when subjected to con- ditions of loading and wetting. The clays encountered were in a natural moist condition. Some minor wet areas were noted in the trenches adjacent the existing building where water was dripping from the eaves. We understand the addition will be a single story structure with typically light foundation loadings. The existing gravelly fill that overlies the natural clays appears to vary in depth, consistency and density. This fill should not be used for foundation bearing. The excavation should be stepped down to completely expose natural subsoils. Considering the conditions of the natural clays exposed in the excavation, we recommend the use of spread footings placed below all fill, topsoil and loose material and designed for a maximum bearing pressure of 1,200 psf for support of the structure. A final bearing check should be made once the excavation is cut to natural soils. Initial settlements of the foundation should be minor but additional differential movement can be expectefi if the subsoils were to become wet. Minimum footing width OFFICES: CASPER • COLORADO SPRINGS • DENVER • SALT LAKE CITY J U CALCULATION FOR WALL r `-- LINE 1 TABLE W -1 WALL AREAS ' SQ. FT. 1. GROSS WALL AREA (Ao) 1 2 4. g r 2. . WINDOW AREA (Az) 2 2. i 2 V 3. DOOR AREA (Ad) 350 t i 1 , 4. ; OTHER (SPECIFY) FIT 5. : OTHER (SPECIFY) .... FRAMING AND CAVITY RATIO 6. OPAQUE WALL AREA (A°D) LINE 1. - SUM 2 THRtT 5 9 fer ,2 q _ STUD FRAMING CAVITY 7. FRAMING AREA (Afr) SPACING RATIO RATIO LINE 6. X TABLE W -4 1 2 Y .22 .78 8. i CAVITY AREA (A y 16" .20 .80 I LINE 6. X TABLE W -4 f e 24" 15 .85 TABLE W- OPAQUE WALL CALCULATIONS FRAMING AND CAVITY SOURCE OF WALL THERMAL MATERIALS WINTER HEATING R VALUES RESISTANCE CAVITY 1F'•TING 0 HER 9. OUTSIDE AIR FILM Ili IIM -.. MIMI 0. EXTERIOR FINISH . mill OUTSIDE SHEATHING FRAMING -~ M ® 11.011 CAVITY INSULATION c!+ �� •V T • R SPACE 15. INTERIOR FINISH Elmorms 16. INSIDE AIR FILM rirMilla 7 . • . : (' ) MEMO :. OTHER SPECIFY - -..- .. 1.111111.0111.1111= 9. TOTAL RESISTANCE f ' - ■ SUM OF` `LINSS' 9 THRU ' 79 _ • U fr FRAMING WM l /Rt (FRAMING COLUMN) mill U CAVITY 70 _•� 1/R (CAVITY COLUMN) 2. U OTHER - IIIIIII.' �. 1 /Rt (OTHER COLUMN) TABLE W -3 SUMMATION OF TRANSMISSION VALUES FOR WALL SOURCE U -VALUE FROM LINE' ARE • FROM LINE U -VALUE X • FRAMING -------- LINE 20. ----- LINE 7. __.• CAVITY r LINE Wri.MMAIIIIMIUMOIMMVA514 OTHER._. LINE . ----- OTHER . R ,------- L NE 5. WINDOWS R LINE . � DOORS R �� LINE . _ MI r TOTAL �' �� Ao = �i�>� SUM U X A = , e p J ,r U WALL 4 SUM OF (U- VALUES X CORRESPONDING AREAS) ° GROSS WALL AREA (A0) GARJ I F LU CULIN f Y STATE of Colorado • ' Office of Building Official • •✓ {FOUEST FOR INSPECTION +}r Date_ 4/0 / 4 _ Permit No._ Tim • Q 1._ - Rrreived_. / �Le .>� I M. District No. rte. • Job Address Locality Owner's Name _ ► 1 4 _Contractor 4 .1 BII rr '' AAM PLASTERING ELECTRICAL PLUMBING HEATING 4Tat∎drl'V Wire_ ❑ Rough Wiring .0 Rough ❑ Rough ❑ Chimney__ _ -- / .- _---- _..__.__❑ Finish Wiring_.❑ Final ❑ Final ❑ Framin • re tch_ ❑ Fixtures ❑ Sewers. ❑ Water Heate•.. ❑ g _ ❑ Motors. ❑ Gas ❑ Food ngsf U U Finish_—. ❑ Cczrpool ❑ Wea h er ❑ Wallboard ❑ Underground ❑ Insulat on ❑ READY FOR INSPECTION A.M Mon: Tues. Wed. Thum Fri. - , r �� �/4 3/ C.? . 7 C] 4- / �" ... _ ��.__... Inspection head C? • Inspeetof • CI, i 1 I L D rUN I Y, • STA 1 1: OF CO7OradO • Office of f3uilcling Official _e flEOUEST iNsPucTioN P e r mit No. :IL' Moe _ kEnc7i,•ed er: y5 • • District NO. (1) ci ['ten 5 ' Locality Ovwner's Name Njj tv;-/ C _contr.ctor BUILDING * PLA T RING ELECTFHCAL PLUMBING HEATING F-0,.dzoon 0 Rough Wir ing sou - 0 Rough 0 Chirnneyie .41 • 0 Finish Wi•ing. 0 Final 0 Final F rarning fo ch 0 Fixtures ServerT 0 Wale/ Healer.. 0 I Final, -.— _0 0 MOIOr%_ a Gas foot] n g _ e s;_',o 0 Weatberprf LY,Ilboard u derground 0 Insulation 0 READY FOR INSPECTION A NA_ Mon: Tue:.A 0- Wed. - Thurt. Fri. P t7 7,-„pecoon Macli Inspector